5

 

Local time setting

 

Hold  F1  to  choose  interface  for  local  time  setting.  Then  hold  F2  to  switch  among 

“Hour-Minute-Second-Year-Month-Date”.  Click  F2,  F1  can  change  the  data  of  flashing  item.  After 
finished, hold F1 can return data detecting interface. 
 

Parameters table 

Num

ber 

Name 

Size 

Description 

Default 

 

Possible 

value 

0x01

 

PM25_Delta_Level

 

1

 

=0    Turn off report 
>=1 Report when change > 

  n * 1ug/m3 

 

0

 

0-127

 

0x02

 

CO2_Delta_Level

 

1

 

=0    Turn off report 
>=1 Report when change > 

n * 5ppm 

 

0

 

0-127

 

0x03

 

Temp_Delta_Level

 

1

 

=0    Turn off report 
>=1 Report when change > 

n*0.5℃

 

0

 

0-127

 

0x04

 

Humidity_Delta_Level

 

1

 

=0    Turn off report 
>=1 Report when change >n%

 

0

 

0-127

 

0x05

 

VOC_Delta_Level

 

1

 

=0    Turn off report 
>=1-127*5ppb Reportchange

 

0

 

0-127

 

0x06 

Lux_Delta_Level 

=0    Turn off report 
>=1  Report  when  change  >     
n*1 Lux 

0-32767 

0x07

 

dB_Delta_Level

 

1

 

=0    Turn off report 
>=1 Report when change > 

n*1dB

 

0

 

0-127

 

0x08 

PIR_Delta_Level 

=0    Turn off report 
=1    Report change 

0-1 

0x09

 

SMOKE_Delta_Level

 

1

 

=0    Turn off report 
=1 Report change

 

1

 

0-1

 

0x0A

 

Smoke_Timer

 

2

 

=0    Turn off report 
>=35  Report  every  n*1s 
interval 

60 

0,35-32767

 

0x0B 

PIR_Timer 

=0    Turn off report 
>=35  Report  every  n*1s 
interval 

60 

0,35-32767 

0x0C

 

PM25_Timer

 

2

 

=0    Turn off report 
>=35Report 

every 

n*1s 

interval 

120

 

0,35-32767

 

0x0D

 

CO2_Timer

 

2

 

=0    Turn off report 
>=35  Report  every  n*1s 
interval

 

120

 

0,35-32767

 

Содержание A8-9

Страница 1: ...82mm Housing Tempered glass PC Alloy Installation Wall mounted Vertical Safety Information To protect yourself and others from danger and to protect the device from damage please read the safety info...

Страница 2: ...e the adaptor Step 3 Put the device back onto the steel frame it will attach with the frame firmly by built in magnets Step 4 Check the installation and power the device is ready for work Operation Po...

Страница 3: ...previous reported value 0x03 set value set value 0 4 Humidity Thevalue difference between current value and previous reported value 0x04 set value set value 0 5 VOC The value difference between curren...

Страница 4: ...EVEL COMMAND_CLASS_ASSOCIATION COMMAND_CLASS_ASSOCIATION_GRP_INFO COMMAND_CLASS_CONFIGURATION COMMAND_CLASS_SENSOR_MULTILEVEL COMMAND_CLASS_FIRMWARE_UPDATE_MD Command Class supported by the device Not...

Страница 5: ...hen change n 0 5 0 0 127 0x04 Humidity_Delta_Level 1 0 Turn off report 1 Report when change n 0 0 127 0x05 VOC_Delta_Level 1 0 Turn off report 1 127 5ppb Reportchange 0 0 127 0x06 Lux_Delta_Level 2 0...

Страница 6: ...x12 dB_Timer 2 0 Turn off report 35 Report every n 1s interval 300 0 35 32767 0x2F Temp unit 1 0 1 0 0 1 0x32 T_OffSet 1 0 127 n 100 10 10 2 7 128 1 156 n 10 2 8 15 5 100 128 127 0x33 RH_OffSet 1 n 20...

Страница 7: ...INSTALLATION ACCIDENT ABUSE MISUSE NATURAL DISASTER INSUFFICIENT OR EXCESSIVE ELECTRICAL SUPPLY ABNORMALMECHANICAL OR ENVIRONMENTAL CONDITIONS OR ANY UNAUTHORIZED DISASSEMBLY REPAIR OR MODIFICATION Th...

Отзывы: