![MBW M300DP Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/mbw/m300dp/m300dp_installation-and-user-manual_1752846012.webp)
M300DP L Series Expansion I/O Module – Installation / User Manual
12
Copyright 2016 MBW Technologies, LLC All Rights Reserved
Auto Start Operation
Auto Start Mode (A/S Mode
)
Selecting the A/S Mode allows the DI1 and/or
DI2 discrete inputs to start and control the
engine. The AI1 and AI2 analog inputs will be
also active.
Analog Input Setup
The M300DP Module has two analog inputs
which may be configured for a number of
senders:
Off
Fuel US (240-33 ohms)
Fuel Euro (10 – 180 ohms)
Water Level US (240-33 ohms)
Water Level Euro. (10- 180 ohms)
When the sender has been connected and the
setup complete, the sender data will appear on
the engine display along with the other engine
parameters. Use the “
▼
” or “
▲
” keys to
highlight the desired sender type. Press and
hold
MODE
key to save changes.
Start Retries
The number of engine start cycles to be
executed after the initial AutoStart (A/S)
sequence is enabled and activated. A start cycle
is 10 seconds of cranking followed by a 5
second wait. The number of start retries can be
configured for 0 to 3 retries. When configured for
0 retries the engine start cycle will activate one time only, on the initial
Auto Start command.
Start Delay(s)
The time (seconds) from the activation of a start
input to the time engine cranking begins. This
time will appear as a countdown on the display.
(0 – 30 seconds). Use the “
▼
” or “
▲
” keys to
adjust delay. Press and hold
MODE
key to
save.
M300DP L Series Expansion I/O Module – Installation / User Manual
Copyright 2016 MBW Technologies, LLC All Rights Reserved
25
Appendix A - Menu Overview
M300DP Main Menu