MBS UBR-01 | Mk II
Configuration
37 von 46
BACNET
Device-object
Enables the configuration of this device for the BACnet.
With <Save> the changes are accepted. <Refresh> updates the
display. To finish <Restart required>.
Device-Instance:
Defines the device instance number of the
router which must be unique within the entire
BACnet network. The value range of this
property is between 0 and 4.194.302.
Device-Name:
Defines the device name of the router, which
must be unique across the entire BACnet
network.
Device-UUID:
U
niversally
U
nique
I
dentifier is a 128-Bit-
number for device identification,
e.g.
4fbb6794-9c57-4b6c-88f8-d728ae328d3b
Description:
Sets the BACnet description - a free
description text - of the device.
Location:
Sets the BACnet location - a free text for the
installation location - of the device.
Vendor-Identifier:
Manufacturer ID for unique identification of
the device manufacturer
Vendor-Name:
Unique name of the device manufacturer
Model-Name:
Type designation
Firmware-Revision:
Firmware version of the device software
APDU Max-Length-
Accepted:
Maximum telegram size in Byte.
Possible are: 50, 206, 480, 1024 und
1476 Byte.