All values are stored in the non-volatile memory and are retained there even in the case of a power failure. When setting any value, always release 
the UP or DOWN button before releasing the SET button. This applies to the setpoint and all other parameters. 
 

Parameter/but
ton 

Function Setting 

range 

Default 
value 

Your 
setting 

S1 / SET1 

Setpoint for regulation contact K1 

P4...P5 

0.0 °C 

 

S2 / SET 2 

Setpoint for regulation contact K2 

P4...P5 

0.0 °C 

 

 

Second operating level 

 

Setting the regulation parameters 

Pressing and holding the UP and DOWN buttons together for at least four seconds displays a list of regulation parameters (starting with P0). This list 
can be rolled up and down with the UP and DOWN buttons.  
To display the value for a selected parameter, press the SET 1 button. With the SET 1 button depressed, the value can be adjusted with the UP and 
DOWN buttons. When all buttons are released, the new value is saved permanently. If no button is pressed within 60 seconds, the controller reverts 
to its normal state. 
 

Parameter 

Function 

Setting range 

Default value 

Your setting 

P0 Actual 

value 

 

 

P1 

Setpoint S2 / regulation contact 2 
DeltaW regulation contact 2 

P4...P5 if A5=0 (factory setting)] 
-99...+99.9K if A5=1 

10,0 °C/K 

 

P2 

Hysteresis, contact 1 

0.1...99.0 K 

1.0 K 

 

P3 

Hysteresis, contact 2 

0.1...99.0 K 

1.0 K 

 

P4 

Lower setpoint limit 

-99°C...P5 

-99 °C 

 

P5 

Upper setpoint limit 

P4...999°C 

999 °C 

 

P6 

Actual value correction 

-20.0...+20.0 K 

0.0 K 

 

P19 

Disable setpoint adjustment 

0: not disabled 
1: disabled 

0  

P30 

Lower limit for alarm 

-99...999°C/K 

-10°C 

 

P31 

Upper limit for alarm 

-99...999°C/K 

120°C 

 

P32 

Hysteresis for alarm, asymmetrical 

0.1...99.9 K 

1.0 K 

 

 

Parameter descriptions 

 

P0 Actual value 

Display of the current actual value. If parameter A32 is set to 1 to display the setpoint, the actual value can be displayed only with this parameter. 
 

P1 Setpoint / DeltaW for regulation contact 2 

Adjustment of the setpoint S2 for regulation contact 2 at the parameter level. 
If parameter A5 is set to 1 (operation with DeltaW), the DeltaW value of the regulation circuit is displayed and can be adjusted.  
 

P2/P3 Hysteresis for regulation contact 1/2 

The hysteresis is symmetrical with respect to the setpoint (see Figs. 2 and 4). 

Содержание MTR 3000

Страница 1: ...e setpoint and the alarm acknowledgement All regulation parameters P2 P32 can be set in the second level The third level permits programming of the basic functions A1 A92 of the controller UP button red arrow Down button blue arrow This button is used to acknowledge an alarm SET 1 SET 1 button Pressing this button displays set value S1 If the button is not depressed the actual value is displayed T...

Страница 2: ...er reverts to its normal state Parameter Function Setting range Default value Your setting P0 Actual value P1 Setpoint S2 regulation contact 2 DeltaW regulation contact 2 P4 P5 if A5 0 factory setting 99 99 9K if A5 1 10 0 C K P2 Hysteresis contact 1 0 1 99 0 K 1 0 K P3 Hysteresis contact 2 0 1 99 0 K 1 0 K P4 Lower setpoint limit 99 C P5 99 C P5 Upper setpoint limit P4 999 C 999 C P6 Actual value...

Страница 3: ...mend that this be done after all adjustments In the disabled state the setpoint cannot be adjusted with the buttons on the front panel Any attempt to adjust the setpoint then results in the message on the display P30 Lower limit value for alarm P31 Upper limit value for alarm The alarm output can be used as a limit value or bandwidth alarm It has an asymmetrical hysteresis see parameter P32 In bot...

Страница 4: ...Para meter Function Setting range Default value Your setting A1 Function of regulation contact 1 0 Heating contact 1 Cooling contact 0 A2 Function of regulation contact 2 0 Heating contact 1 Cooling contact 0 A3 Function of regulation contact 1 in case of sensor fault 0 Off on fault 1 On on fault 0 A4 Function of regulation contact 2 in case of sensor fault 0 Off on fault 1 On on fault 0 A5 Operat...

Страница 5: ...ntact 2 0 600 s 0 s A54 Delay after power on 0 600 s 0 s A55 Mutual delay regulation contacts 1 and 2 0 600 s 0 s A56 Alarm suppression after power on 0 60 min 20 min A60 Temperature sensor 11 12 PT100 three wire connection 12 A70 Software filter 1 Disabled Average over 2 2 measured values approx 0 6s 4 4 measured values approx 1 2s 8 8 measured values approx 2 4s 16 16 measured values approx 4 8s...

Страница 6: ...rameter determines whether the controller operates with two independently adjustable contacts A5 0 operation with setpoint factory setting or with two mutually linked contacts A5 1 operation with Delta W This parameter always affects regulation contact 2 A8 Display mode The actual value can be displayed as an integer or with one digit after the decimal point resolution 0 5 C or 0 1 C If a resoluti...

Страница 7: ...n active A sensor alarm display F1L or F1H is always signalled by a blinking display and the buzzer A32 Type of display If A32 0 is set the actual value is displayed If A32 1 is set setpoint S1 is always displayed and the actual value can then be displayed only with the aid of parameter P0 second operating level A33 Not used A40 Hysteresis mode regulation contact 1 A41 Hysteresis mode regulation c...

Страница 8: ... A70 1 deactivates the software filter A80 Temperature scale The temperatures can be displayed in Fahrenheit or Celsius factory setting Note that the values and setting ranges for the parameters and setpoints remain unchanged when the scale is changed If for example a controller whose setpoint is set to 0 C is modified to display the temperatures in Fahrenheit the setpoint is then interpreted as 0...

Страница 9: ...ous current 6 A make contact suitable for electric motors up to 0 5 HP Function see parameter A91 K3 Relay 250 V maximum switched current 6 A cosϕ 1 maximum continuous current 3 A make contact suitable for electric motors up to 0 5 HP Function see parameter A92 Supply voltage 230 V 50 60 Hz maximum power consumption 4 VA Terminals 12 pole screw terminal plug strip spacing 5 0 mm for cables up to 2...

Отзывы: