A50 Minimum "On" time, regulation contact 1 
A51 Minimum "Off" time, regulation contact 1 
A52 Minimum "On" time, regulation contact 2 
A53 Minimum "Off" time, regulation contact 2 

These parameters make it possible to ensure that the output contact remains on or off for a specified time in order to reduce the switching frequency. 
The time specified here is the total minimum time for the on or off state of the contact  (factory setting: 0 s). 

A54 Delay after power on 

With this parameter, activation of regulation contacts 1 and 2 can be delayed by a specified period after the mains voltage is switched on. 

A55 Mutual delay, regulation contacts 1 and 2 

This parameter permits the activation of regulation contact 1 to be delayed by a specified period with respect to activation of regulation contact 2 or 
vice versa, depending on which contact is activated first. 

A56 Alarm suppression after power on 

This parameter permits the activation of the alarm contact to be delayed by a specified period after the mains voltage is switched on (factory setting: 
20 minutes). 

A60 Temperature sensor 

This parameter permits selection of the type of PT100 temperature sensor connection (factory setting: three-wire connection). 

A70 Software filter 

The measured value is averaged over the number of measuring cycles specified here. This average value is displayed and used for regulation. A70=1 
deactivates the software filter. 

A80 Temperature scale 

The temperatures can be displayed in Fahrenheit or Celsius (factory setting). Note that the values and setting ranges for the parameters and setpoints 
remain unchanged when the scale is changed. If, for example, a controller whose setpoint is set to 0°C is modified to display the temperatures in 
Fahrenheit, the setpoint is then interpreted as 0 °F, corresponding to a temperature of -32° C. 
In addition, you can specify whether the controller displays the word AUS (German) or OFF (English) when it is in standby mode. 

A81 Not used 

A82 Function of button SET 2  

Setpoint S2 (parameter P1) 

A83 Function of unlabelled button 

The button is disabled. 

A90 Output connection, relay K1 
A91 Output connection, relay K2 
(A92 No connection) 

Depending on the hardware, the relays can be connected to various signals from the regulator: 

Regulator outputs 

Regulation contact 1  Regulation circuit set with the parameters S1, P2, A1 
Regulation contact 2  Regulation circuit set with the parameters P1, P3, A2  
Alarm 

Alarm circuit set with the parameters P30, P31, P32, A30  

Buzzer function 

As for internal horn, intermittent, can be acknowledged with the DOWN button (affected by parameter A31) 

 

 

Status messages 

 

Display Fault 

Action 

F1L 

Sensor fault (short circuit) 

Check the sensor 

F1H 

Sensor fault (open circuit) 

Check the sensor 

–  –  – 

Parameters are locked 

See parameter P19 or A19 

Blinking display 

Temperature alarm (see A31) 

 

EP 

Loss of data in parameter memory 

Have the controller repaired (regulation contacts 1 and 2 
are set to no-current position) 

 

Содержание MTR 3000

Страница 1: ...e setpoint and the alarm acknowledgement All regulation parameters P2 P32 can be set in the second level The third level permits programming of the basic functions A1 A92 of the controller UP button red arrow Down button blue arrow This button is used to acknowledge an alarm SET 1 SET 1 button Pressing this button displays set value S1 If the button is not depressed the actual value is displayed T...

Страница 2: ...er reverts to its normal state Parameter Function Setting range Default value Your setting P0 Actual value P1 Setpoint S2 regulation contact 2 DeltaW regulation contact 2 P4 P5 if A5 0 factory setting 99 99 9K if A5 1 10 0 C K P2 Hysteresis contact 1 0 1 99 0 K 1 0 K P3 Hysteresis contact 2 0 1 99 0 K 1 0 K P4 Lower setpoint limit 99 C P5 99 C P5 Upper setpoint limit P4 999 C 999 C P6 Actual value...

Страница 3: ...mend that this be done after all adjustments In the disabled state the setpoint cannot be adjusted with the buttons on the front panel Any attempt to adjust the setpoint then results in the message on the display P30 Lower limit value for alarm P31 Upper limit value for alarm The alarm output can be used as a limit value or bandwidth alarm It has an asymmetrical hysteresis see parameter P32 In bot...

Страница 4: ...Para meter Function Setting range Default value Your setting A1 Function of regulation contact 1 0 Heating contact 1 Cooling contact 0 A2 Function of regulation contact 2 0 Heating contact 1 Cooling contact 0 A3 Function of regulation contact 1 in case of sensor fault 0 Off on fault 1 On on fault 0 A4 Function of regulation contact 2 in case of sensor fault 0 Off on fault 1 On on fault 0 A5 Operat...

Страница 5: ...ntact 2 0 600 s 0 s A54 Delay after power on 0 600 s 0 s A55 Mutual delay regulation contacts 1 and 2 0 600 s 0 s A56 Alarm suppression after power on 0 60 min 20 min A60 Temperature sensor 11 12 PT100 three wire connection 12 A70 Software filter 1 Disabled Average over 2 2 measured values approx 0 6s 4 4 measured values approx 1 2s 8 8 measured values approx 2 4s 16 16 measured values approx 4 8s...

Страница 6: ...rameter determines whether the controller operates with two independently adjustable contacts A5 0 operation with setpoint factory setting or with two mutually linked contacts A5 1 operation with Delta W This parameter always affects regulation contact 2 A8 Display mode The actual value can be displayed as an integer or with one digit after the decimal point resolution 0 5 C or 0 1 C If a resoluti...

Страница 7: ...n active A sensor alarm display F1L or F1H is always signalled by a blinking display and the buzzer A32 Type of display If A32 0 is set the actual value is displayed If A32 1 is set setpoint S1 is always displayed and the actual value can then be displayed only with the aid of parameter P0 second operating level A33 Not used A40 Hysteresis mode regulation contact 1 A41 Hysteresis mode regulation c...

Страница 8: ... A70 1 deactivates the software filter A80 Temperature scale The temperatures can be displayed in Fahrenheit or Celsius factory setting Note that the values and setting ranges for the parameters and setpoints remain unchanged when the scale is changed If for example a controller whose setpoint is set to 0 C is modified to display the temperatures in Fahrenheit the setpoint is then interpreted as 0...

Страница 9: ...ous current 6 A make contact suitable for electric motors up to 0 5 HP Function see parameter A91 K3 Relay 250 V maximum switched current 6 A cosϕ 1 maximum continuous current 3 A make contact suitable for electric motors up to 0 5 HP Function see parameter A92 Supply voltage 230 V 50 60 Hz maximum power consumption 4 VA Terminals 12 pole screw terminal plug strip spacing 5 0 mm for cables up to 2...

Отзывы: