5
Para-
meter
Function
Setting range
Default value
Your
setting
A31
Special function on alarm
0: Inactive
1: Display blinks
2: Buzzer sounds
3: Display blinks and buzzer sounds
4: As for 3, buzzer can be acknowledged
5: As for 4, buzzer sounds again after
10
minutes
6: As for 4, buzzer sounds again after
30
minutes
3
A32
Type of display
0: Actual value
1: Setpoint S1
0
A33 Not
used
0: Disabled
0
0
A40
Hysteresis mode,
regulation contact 1
0: Symmetrical
1: Asymmetrical
0
A41
Hysteresis mode,
regulation contact 2
0: Symmetrical
1: Asymmetrical
0
A50
Minimum "On" time, contact 1
0…600 s
0 s
A51
Minimum "Off" time, contact 1
0…600 s
0 s
A52
Minimum "On" time, contact 2
0…600 s
0 s
A53
Minimum "Off" time, contact 2
0…600 s
0 s
A54
Delay after power on
0…600 s
0 s
A55
Mutual delay, regulation contacts 1 and 2
0…600 s
0 s
A56
Alarm suppression after power on
0…60 min
20 min
A60 Temperature
sensor
11:
12: PT100, three-wire connection
12
A70
Software filter
1:
Disabled
Average over
:
2:
2 measured values (approx. 0.6s)
4:
4 measured values (approx. 1.2s)
8:
8 measured values (approx. 2.4s)
16:
16 measured values (approx. 4.8s)
32:
32 measured values (approx. 9.6s)
64:
64 measured values (approx. 19.2s)
128: 128 measured values (approx. 38.4s)
4
A80
Temperature scale and display in standby
mode
0: Fahrenheit (AUS)
1: Celsius (AUS)
2: Fahrenheit (OFF)
3: Celsius (OFF)
1
A81 Not
used
0: No function
0
0
A82
Function of button SET 2
0: Disabled
1: Regulator On/Off (standby)
2: Setpoint S2 (parameter P1)
3: Switch relay directly, off on standby
4: Switch relay directly, unaffected by
standby
2
A83
Function of unlabelled button
0: Disabled
0
0