32
INSTALLATION AND MAINTENANCE MANUAL
PUBLICATION DATE 03/02
504 766
Fig.5.13. Overcurrent relay
5.14. VALUES OF FUSES
Values of fuses you can find on electrical scheme delivered with machine.
Marking
Destined for:
FU1, FU2
transformer - primary winding
FU3
control circuits
FU5
clutch of 2-motor version
pumps
external dosing
Tab.5.14.
5.15. EARTH LEAKAGE TRIPS
If the laundry is equipped with the earth leakage trip in the inlet circuit of the electric switchboard it is
necessary to test it regularly. The earth leakage trip is a very sensitive device and it provides a safety for
operators avoiding a risk of an electric shock while the machine is in operation.
WARNING !
A QUALIFIED WORKER MUST PERFORM A TEST OF THE EARTH LEAKAGE TRIP FUNCTION AT LEAST
ONCE IN 3 MONTHS.
THE TEST PROCEDURE:
Press the test push button of the earth leakage trip while it is under tension. The earth leakage trip must go off !
!