background image

13

Preoperational Test ____________

All dryers are thoroughly tested and inspected before 

leaving the factory. However, a preoperational test should be 

performed before the dryer is publicly used. It is possible that 

adjustments have changed in transit or due to marginal location 

(installation) conditions.
Turn on electric power to the dryer.
Refer to the operating instructions for starting your dryer.
Open all shutoff valves.
When a gas dryer is first started (during initial start-up), it has 

a tendency not to ignite on the first ignition attempt. This is 

because the gas supply piping is filled with air, so it may take a 

few minutes for the air to be purged from the lines.

NOTE:

 During the purging period, check to be sure that all gas 

shutoff valves are open.

Tumbler Coating

The tumbler is treated with a protective coating. We suggest 

dampening old garments or cloth material with a solution of 

water and nonflammable mild detergent and tumbling them in 

the tumbler to remove this coating.
Each tumbler should be operated through one complete cycle 

to ensure that no further adjustments are necessary and that all 

components are functioning properly.

Microprocessor Programs / Selections

Each microprocessor controller (computer) has been pre 

programmed by the factory with the most commonly used 

parameter (program) selections. If computer program changes 

are required, refer to the computer programming manual, which 

was shipped with the dryer.

Operating Instructions __________

The dryer is available for use when the appropriate side of the 

microprocessor display reads “0 minutes” and the amount 

needed to start the dryer (i.e., “25”). Once the load has been 

put into the dryer and the main door is closed, start the dryer 

as follows:

 

͜

Insert the proper number of coins into the coin acceptor. 

Once the correct “Amount To Start” has been inserted, the 

display will read “SELECT CYCLE”.

 

͜

Determine fabric setting (selection). 

Once the fabric temperature setting (selection) has been 

determined, start the dryer by pressing the fabric setting 

key.

 

͜

The dryer will now start, and the display will read the setting 

and the time vended.

 

͜

The cycle time will count down until the drying and cooling 

cycles are completed.

 

͜

Upon completion of the drying and cooling cycles, the 

dryer will shut off.

The dryer tumbler can be stopped at any time by opening the 

main door. Do not reach into the dryer if the drum is moving. To 

restart dryer, shut the main door and press desired setting.

NOTE:

 When a cycle is interrupted by opening the main door, 

cycle time will continue to count downward, regardless if the 

door is open or closed.
Selection (setting) changes can be made at any time during the 

drying cycle.

Shutdown Instructions _________

If the dryer is to be shutdown (taken out of service) for a period 

of time, the following must be performed:
Disconnect power to the dryer either at the external disconnect 

switch or the circuit breaker.
Disconnect the fuel supply: close external gas shutoff valve. 

Also close two internal gas shutoff valves.
If the dryer is to be removed from service or discarded, before 

doing so remove the door to the drying compartment.

Содержание MLG45

Страница 1: ...MLG45 Installation Manual Stack Dryer WFR113489H RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE ...

Страница 2: ...ON HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Installation and service must be performed by a qualified installer service agency or the gas supplier Do not try to light any appliance Do not touch ...

Страница 3: ...sed to prevent straining of the gas supply when the dryer is moved An external means of power removal disconnect device must be provided by the installer The dryer must be used only for drying water washed fabrics The dryer must never be operated with any of the back guards or service panels removed The wiring diagram for the dryer is located behind the front control panel List of Acronyms _______...

Страница 4: ...Hz 600 cfm 16 99 cmm HEAT INPUT PER POCKET 112000 Btu hr 28224 kcal hr EXHAUST CONNECTION DIAMETER PER POCKET 2 8 Standard 1 10 Optional 2 20 32 cm 1 25 4 cm INLET PIPE CONNECTION PER POCKET 3 4 M N P T Shaded areas are stated in metric equivalents NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation NOTE Ductwork can be 2 8 20 32 cm o...

Страница 5: ...st conform to applicable Canadian Standards CAN CGA B149 1 M91 Natural Gas or CAN CGA B149 2 M91 Propane Gas or LATEST EDITION for General Installation and Gas Plumbing The operation of this dryer may affect the operation of other types of gas dryers which take their air for safe combustion from the same room If in doubt consult the dryer manufacturer s The dryer must be installed on a sound level...

Страница 6: ...r 1000 Btu 252 kcal It is not necessary to have a separate make up air opening for each dryer Common make up air openings are acceptable However they must be set up in such a manner that the make up air is distributed equally to all the dryers EXAMPLE For a bank of four dryers two unrestricted openings measuring 20 by 221 2 50 80 cm by 57 15 cm are acceptable To compensate for the use of registers...

Страница 7: ...hrough a wall ceiling or roof made of combustible materials the opening must be 2 5 08 cm larger than the duct all the way around The duct must be centered within this opening The ductwork for this dryer must be suitable for the appliance category in accordance with national installation regulations of the country of destination Outside Ductwork Protection To protect the outside end of the horizon...

Страница 8: ...the outdoors is longer than 20 6 09 m or has more than one elbow in it IMPORTANT For extended ductwork runs the crosssectional area of the ductwork can only be increased to an extent When the ductwork approaches the maximum limits as noted in this manual a professional HVAC firm should be consulted for proper venting information Multiple Dryer Venting with 10 25 4 cm Diameter 1200 cfm 33 98 cmm Ex...

Страница 9: ... When fuses are used they must be dual element time delay current limiting class RK1 or RK5 ONLY Calculate determine correct fuse value by applying either local and or National Electrical Codes to listed appliance amp draw data B Circuit breakers are thermal magnetic industrial motor curve type ONLY For others calculate verify correct breaker size according to appliance amp draw rating and type of...

Страница 10: ...nnections materials and workmanship conform to local and state regulations or codes of the country of destination In the absence of such codes all plumbing connections materials and workmanship must conform to the applicable local requirements In the USA this is the National Fuel Gas Code ANSI Z223 1 LATEST EDITION or in Canada the Canadian Installation Codes CAN CGA B149 1 M91 Natural Gas or CAN ...

Страница 11: ...eter Specific information regarding supply line size should be determined by the gas supplier NOTE Undersized gas supply piping can create a low or inconsistent pressure which will result in erratic operation of the burner ignition system TYPICAL NATURAL GAS INSTALLATION Consistent gas pressure is essential at all gas connections It is recommended that a 3 4 19 05 mm pipe gas loop be installed in ...

Страница 12: ...stment of the valve is complete the regulator cap must be replaced and sealed with for example paint to prevent tampering by the user Leak Check 1 Be sure the gas supply is turned on 2 Turn on dryer 3 Brush or spray an approved noncorrosive leak detection solution onto all connections and inspect for leaks indicated by growing bubbles 4 If dryer was moved during testing use the same method to chec...

Страница 13: ...ructions __________ The dryer is available for use when the appropriate side of the microprocessor display reads 0 minutes and the amount needed to start the dryer i e 25 Once the load has been put into the dryer and the main door is closed start the dryer as follows Insert the proper number of coins into the coin acceptor Once the correct Amount To Start has been inserted the display will read SE...

Страница 14: ... ducting and remove any lint buildup Suggested Cleaning Schedule Every Third or Fourth Load Clean the lint screen every third or fourth load A clogged lint screen will cause poor dryer performance The lint door drawer is located just below the loading door of the dryer Open the lint door drawer brush the lint off the lint screen and remove the lint Inspect lint screen and replace if torn NOTE To r...

Страница 15: ...s Gives the number drill size used 6 Electric Service This describes the voltage and current rating for a particular model 7 Gas Manifold Pressure For Gas Dryers This describes the manifold pressure taken at the gas valve tap SECHEUSES VOL 2 INPUT ENTREE ORIFICE ORIFICE MOD SER INPUT 0 TO 2 000 FT ENTREE 0 A 610M HEAT CHALEUR TYPE 120V 60HZ 1PH 2W 16A MANIFOLD PRESSURE PRESSION A LA TUBULURE D ALI...

Страница 16: ...MLG45 Manuel D installation Sécheuses Superposées CONSERVER CES INSTRUCTIONS POUR RÉFÉRENCE ULTÉRIEURE ...

Страница 17: ...structions à l usage du client en un lieu bien visible au cas où le client percevrait une odeur de gaz Ces renseignements doivent être obtenus auprès de votre fournisseur en gaz Placer l avertissement qui suit à un endroit bien visible Ne pas entreposer ou utiliser de l essence ou d autres vapeurs ou liquides inflammables à proximité de cet appareil ou de tout autre appareil électroménager QUE FAI...

Страница 18: ...ISATION 28 INSTRUCTIONS D ARRÊT 28 RENSEIGNEMENTS SUR LA RÉPARATION ET LES PIÈCES 29 ENTRETIEN DE ROUTINE 29 INFORMATIONS SUR L ÉTIQUETTE DE DONNÉES 30 Attention Lors des contrôles d entretien placer des étiquettes sur l ensemble des câbles avant leur débranchement Des erreurs de câblage peuvent occasionner un fonctionnement incorrect Dans l État du Massachusetts les instructions d installation su...

Страница 19: ...TRÉE DE CHALEUR PAR SÉCHEUSE 112 000 Btu h 28 224 kcal h CONDUIT D ÉVACUATION DIAMÈTRE PAR SÉCHEUSE 2 8 po standard 1 10 po en option 2 20 32 cm 1 25 4 cm RACCORD D ENTRÉE DE TUYAU PAR SÉCHEUSE 3 4 po M N P T Les zones ombrées indiquent les dimensions en métrique REMARQUE Le fabricant se réserve le droit de modifier les spécifications à tout moment sans préavis ni obligation 8 po X2 OU 10 po EN OP...

Страница 20: ...91 gaz naturel ou CAN CGA B149 2 M91 gaz propane ou la DERNIÈRE ÉDITION pour l installation générale et la plomberie au gaz L utilisation de cette sécheuse peut affecter celle d autres sécheuses à gaz dont la source d approvisionnement en air se fait dans la même pièce pour une combustion sans danger En cas de doute consulter le fabricant de la sécheuse La sécheuse doit être installée sur un sol s...

Страница 21: ...ir d appoint distincte pour chaque sécheuse Les ouvertures communes pour l air d appoint sont acceptables Toutefois elles doivent être installées de sorte que l air d appoint est distribué uniformément à toutes les sécheuses EXEMPLE Pour une rangée de quatre sécheuses 2 ouvertures sans restriction de 20 po x 22 5 po 50 80 cm x 57 15 cm sont acceptables Pour compenser l utilisation de registres ou ...

Страница 22: ...e REMARQUE Lorsque les conduits d évacuation traversent un mur un plafond ou un toit en matériaux combustibles l ouverture doit être supérieure de 2 po 5 08 cm à celle du conduit tout autour Le conduit doit être centré dans cette ouverture Les conduits de cette sécheuse doivent être adaptés à la catégorie d appareils conformément aux réglementations nationales en matière d installation du pays de ...

Страница 23: ...d évacuation est plus long de 20 pi 6 09 m ou comporte plus d un coude IMPORTANT Pour les conduits de longueur prolongée l aire de la section transversale du conduit ne peut être augmentée que dans une certaine mesure Lorsque le nombre de conduits approche les limites maximales indiquées dans ce manuel il convient de faire appel à une entreprise de CVC professionnel pour obtenir des informations s...

Страница 24: ...utres calculez vérifiez la taille correcte du disjoncteur en fonction de l appel de courant de l appareil et du type de disjoncteur utilisé TENSION DE SERVICE PHASE SER VICE DE CÂBLAGE ENVIRON APPEL DE COURANT DISJONC TEUR CALIBRE DE FILS MINIMAL 60 Hz 120 1ø 2 12 15 14 Mise à la terre Une liaison à la terre doit être fournie et installée conformément aux réglementations ou codes locaux provinciau...

Страница 25: ...du National Fuel Gas Code ANSI Z223 1 DERNIÈRE ÉDITION ou au Canada des codes d installation canadiens CAN CGA B149 1 M91 gaz naturel ou CAN CGAB149 2 M91 gaz propane ou DERNIÈRE ÉDITION Il est important que les régulateurs de pression de gaz répondent aux exigences de pression applicables et que les compteurs de gaz soient calculés pour la quantité totale de Btu fournie de la sécheuse Pour facili...

Страница 26: ...ui entraînera un fonctionnement irrégulier du système d allumage du brûleur INSTALLATION TYPIQUE AU GAZ NATUREL Une pression de gaz constante est essentielle pour tous les raccordements de conduites de gaz Il est recommandé d installer une boucle de tuyauterie pour circulation de gaz de 3 4 po 19 05 mm dans la conduite d alimentation desservant une rangée de sécheuses Un détendeur doit être instal...

Страница 27: ...s fuites 1 Vérifier que l alimentation en gaz est ouverte 2 Mettre la sécheuse en marche 3 Appliquer au pinceau ou par pulvérisation une solution non corrosive de détection des fuites homologuée sur tous les raccordements rechercher les éventuelles fuites de gaz observables par la formation de bulles 4 Si la sécheuse a été déplacée pendant le test utiliser la même méthode pour vérifier l absence d...

Страница 28: ...structions d utilisation La sécheuse peut être utilisée lorsque le côté approprié de l afficheur du microprocesseur indique 0 minutes et le montant nécessaire pour démarrer la sécheuse c à d 25 Une fois que la charge a été mise dans la sécheuse et que la porte principale est fermée mettre la sécheuse en marche comme suit Insérer le nombre approprié de pièces dans le récepteur de pièces Une fois qu...

Страница 29: ...6 à 8 heures de fonctionnement par jour IMPORTANT S assurer de réinstaller les pièces retirées pendant le nettoyage Chaque 6 mois inspecter les conduits d évacuation et éliminer toute accumulation de charpie Programme de nettoyage suggéré Chaque troisième ou quatrième charge Nettoyer le filtre à charpie tous les trois ou quatre charges Un filtre à charpie obstrué entraînera une mauvaise performanc...

Страница 30: ... fabricant de rassembler des informations sur votre sécheuse particulière 3 Type de chaleur Ceci décrit le type de chaleur de votre sécheuse gaz gaz naturel ou propane électrique ou vapeur 4 Apport de chaleur pour les sécheuses à gaz Ceci décrit l apport de chaleur en unités thermiques britanniques par heure Btu h ou kilowatt kW 5 Taille de l orifice pour les sécheuses à gaz Donne le nombre de for...

Страница 31: ...31 ...

Страница 32: ...WFR113489H 03 20 Tous droits réservés 2020 Maytag All rights reserved ...

Отзывы: