Operating instructions SG-EFS 104/2W 

Page 18/19

Technical data

SG-EFS 104/2W

AC 24 V

DC 24 V

Testing basis

EN 12978, EN 61000-6-3, ISO 13849-1, ISO 13856-1, ISO 13856-2, 

ISO 13856-3

Connecting voltage U

S

Nominal voltage

AC 24 V

DC 24 V

Voltage tolerance

−10% to +10%

−10% to +10%

Nominal current

70 mA

60 mA

Nominal frequency

50 to 60 Hz

External fuse protection

200 mA time-lag

200 mA time-lag

Power consumption

< 4 VA

< 3 W

Times

Reaction time t

a

< 15 ms

< 15 ms

Restart time t

w

< 50 ms

< 50 ms

Safety classifications

ISO 13856: reset function

With/without

With/without

ISO 13849-1:2015

Category 3 PL d

Category 3 PL d

 MTTF

D

257 a

257 a

 DC

avg

60%

60%

 B

10D  

(load: DC 24 V / 1 A)

1.8× 10

6

1.8× 10

6

 n

op

 (assumption)

52560/a

52560/a

 CCF

Requirements met

Requirements met

IEC 60664-1: creep distance and 

air gap

Pollution degree 2, overvoltage cat-

egory III / 250 V, basic insulation

Pollution degree 2, overvoltage cat-

egory III / 250 V, basic insulation

Inputs

Sensor

Y1, Y2  

 

Y1, Y3

Y1, Y2  

 

Y1, Y3

 

Monitoring resistor

1k2 Ohm   8k2 Ohm

1k2 Ohm   8k2 Ohm

 

Short-circuit resistance

≤ 400 ohms   

≤ 400 ohms

≤ 400 ohms   

≤ 400 ohms

 

Line resistance

≤ 10 ohms   

≤ 10 ohms

≤ 10 ohms   

≤ 10 ohms

 

Line length (max.)

100 m 

  100 m

100 m 

  100 m

 

Switching thresholds

 

  Sensor activated

< 0.6 kiloohms 

 < 4 kiloohms

< 0.6 kiloohms 

 < 4 kiloohms

 

  Cable break

> 1k8 ohms   

> 12 kiloohms

> 1k8 ohms    

> 12 kiloohms

Reset
 Automatic

S1, S2

S1, S2

 Manual

S1, S3

S1, S3

 

Line length (max.)

30 m

30 m

Technical data

Содержание 1005196

Страница 1: ...ions 1005196 SG EFS 104 2W AC DC 24 V Mayser GmbH Co KG rlinger Strasse 1 3 89073 Ulm GERMANY Tel 49 731 2061 0 Fax 49 731 2061 222 E mail info ulm mayser com Website www mayser com Innovative by trad...

Страница 2: ...the product Add any supplement received from the manufacturer to the instruc tions Observe the information under Safety starting on page 5 Conformity The Declaration of Conformity is available in the...

Страница 3: ...Automatic reset 9 Manual reset 9 Installation 9 Reset 10 Automatic reset 10 Manual reset 10 Signal outputs 11 Signal outputs with US AC 11 Signal outputs with US DC 11 Connection examples 11 Commissio...

Страница 4: ...he environ ment Information on easier and safer working practices Other applicable documents Please also observe the following documents Drawing of the sensor system optional Wiring diagram optional I...

Страница 5: ...n these zones In the event of a fault put out of operation In the event of malfunctions and visible damage put the control unit out of operation by decommissioning it Prevent the machine from restarti...

Страница 6: ...connecting the supply volt age Protect relay contacts Risk of contact welding provide the relay contacts with external fuse protec tion Do not overload control unit Ensure that the specified switching...

Страница 7: ...matic reset S1 S3 Manual reset button Parts supplied 1 Control unit Enclosure with electronics module and plug in connectors 1 Operating Instructions 1 Declaration of Conformity Upon receipt immediate...

Страница 8: ...or and Output LEDs go out the M1 signal output is set to LOW and the M2 signal output is set to HIGH The signal circuit is in the ON state The control unit is operated with a voltage of 24 V AC DC Whe...

Страница 9: ...d start up again immediately Manual reset The control unit works with a reset function If the protective device stops being actuated the output signal switching devices of the control unit remain in t...

Страница 10: ...als S1 and S3 The control unit reacts when the button changes from activated to not activated i e if the button sticks no reset function is initiated Remove the bridge between cable terminals S1 and S...

Страница 11: ...nal output M2 fault Wire the load between cable terminals M2 and A2 Signal outputs with US AC Signal outputs M1 and M2 are semiconductor outputs and are short circuit proof In the HIGH state a voltage...

Страница 12: ...Operating instructions SG EFS 104 2W Page 12 19 Installation Connection example 2 Connection example 3 Connection example 4 Manual reset Contact multiplication Automatic reset Contact multiplication...

Страница 13: ...ghts up OSSDs 1 and 2 are open Signal circuit closed Signal outputs M1 and M2 are set to LOW 5 Repeat step 1 1 Make sure no sensors are activated Green Power and Sensor LEDs light up OSSDs 1 and 2 are...

Страница 14: ...ps 1 and 2 5 Disconnect the sensor Green Sensor and Output LEDs go out Red Fault LED lights up OSSDs 1 and 2 are open Signal circuit closed Signal outputs M1 and M2 are set to LOW 6 Repeat steps 1 and...

Страница 15: ...or operation Open Closed LOW HIGH Sensor activated Open Closed LOW LOW Fault on sensor cable break Correlations Recommissioning Decommissioning Carry out the commissioning process see Commissioning Di...

Страница 16: ...errupted Check connection to button Manual reset button jammed sticking Replace buttons on S1 and S3 Automatic reset bridge missing Connect bridge between S1 and S2 Control unit is faulty Replace cont...

Страница 17: ...the devices may be returned to us for disposal WEEE reg no DE 39141253 Disposal Control unit Packaging Wood cardboard plastics When disposing of the product Ensure compliance with the relevant nationa...

Страница 18: ...Category 3 PL d MTTFD 257 a 257 a DCavg 60 60 B10D load DC 24 V 1 A 1 8 106 1 8 106 nop assumption 52560 a 52560 a CCF Requirements met Requirements met IEC 60664 1 creep distance and air gap Polluti...

Страница 19: ...3 A quick acting 6 3 A quick acting Line length max 30 m 30 m Signal output PNP M1 S1 M2 S1 M1 A2 M2 A2 Signal type Sensor Fault Sensor Fault Voltage DC 20 to 29 V DC 20 to 29 V DC 18 to 22 V DC 18 to...

Отзывы: