Troubleshooting and remedies

Fault indication

Possible cause

Remedy

Green “Power” LED does 

not light up

No or incorrect supply voltage

1.  Check supply voltage, compare with 

type plate

2.  Check terminal assignment

If supply voltage is correctly connected: 

control unit is faulty

 

Ä

Replace control unit

Green “Sensor” LED 

does not light up 

and

  

signal output M1 is set 

to LOW

Incorrect monitoring resistor on the 

sensor

 

Ä

Connect sensor to monitoring resis-

tor 1k2 or 8k2

Sensor incorrectly connected

 

Ä

Check terminal assignment

 

Ä

Sensor with 1k2 connected to Y1 

and Y2?

 

Ä

Sensor with 8k2 connected to Y1 

and Y3?

If monitoring resistor is correct: sensor is 

faulty

 

Ä

Replace sensor

Green “Sensor” LED 

lights up

and

 

green “Output” LED 

does not light up

Manual reset: reset button not activated

 

Ä

Activate reset button

Manual reset: connection to button in-

terrupted

 

Ä

Check connection to button

Manual reset: button jammed/sticking

 

Ä

Replace buttons on S1 and S3

Automatic reset: bridge missing

 

Ä

Connect bridge between S1 and S2

Control unit is faulty

 

Ä

Replace control unit

Green “Power”, “Sensor” 

and “Output” LEDs light 

up

and

 

switch channel K2 is 

open

Control unit is faulty

 

Ä

Replace control unit

Red “Fault” LED lights 

up 

and

 

signal output M2 is 

LOW

Incorrect monitoring resistor on the 

sensor

 

Ä

Connect sensor to monitoring resis-

tor 1k2 or 8k2

Sensor incorrectly connected

 

Ä

Check terminal assignment

 

Ä

Sensor with 1k2 connected to Y1 

and Y2?

 

Ä

Sensor with 8k2 connected to Y1 

and Y3?

Cable break

 

Ä

Replace sensor

Troubleshooting and remedies

Prerequisites: 

 

The sensor system has passed the latest test (see sensor installation instruc-
tions).

 

The control unit is connected to the supply voltage and sensor.

 

No sensor is activated.

Still unable to resolve the fault?

 

Ä

Contact Mayser-Support: Tel. +49 731 2061-0.

 

Ä

In the event of enquiries, have the information from the type plate to hand.

Type plate

There is a type plate on the side of the control unit for identification purposes.

Содержание 1005196

Страница 1: ...ions 1005196 SG EFS 104 2W AC DC 24 V Mayser GmbH Co KG rlinger Strasse 1 3 89073 Ulm GERMANY Tel 49 731 2061 0 Fax 49 731 2061 222 E mail info ulm mayser com Website www mayser com Innovative by trad...

Страница 2: ...the product Add any supplement received from the manufacturer to the instruc tions Observe the information under Safety starting on page 5 Conformity The Declaration of Conformity is available in the...

Страница 3: ...Automatic reset 9 Manual reset 9 Installation 9 Reset 10 Automatic reset 10 Manual reset 10 Signal outputs 11 Signal outputs with US AC 11 Signal outputs with US DC 11 Connection examples 11 Commissio...

Страница 4: ...he environ ment Information on easier and safer working practices Other applicable documents Please also observe the following documents Drawing of the sensor system optional Wiring diagram optional I...

Страница 5: ...n these zones In the event of a fault put out of operation In the event of malfunctions and visible damage put the control unit out of operation by decommissioning it Prevent the machine from restarti...

Страница 6: ...connecting the supply volt age Protect relay contacts Risk of contact welding provide the relay contacts with external fuse protec tion Do not overload control unit Ensure that the specified switching...

Страница 7: ...matic reset S1 S3 Manual reset button Parts supplied 1 Control unit Enclosure with electronics module and plug in connectors 1 Operating Instructions 1 Declaration of Conformity Upon receipt immediate...

Страница 8: ...or and Output LEDs go out the M1 signal output is set to LOW and the M2 signal output is set to HIGH The signal circuit is in the ON state The control unit is operated with a voltage of 24 V AC DC Whe...

Страница 9: ...d start up again immediately Manual reset The control unit works with a reset function If the protective device stops being actuated the output signal switching devices of the control unit remain in t...

Страница 10: ...als S1 and S3 The control unit reacts when the button changes from activated to not activated i e if the button sticks no reset function is initiated Remove the bridge between cable terminals S1 and S...

Страница 11: ...nal output M2 fault Wire the load between cable terminals M2 and A2 Signal outputs with US AC Signal outputs M1 and M2 are semiconductor outputs and are short circuit proof In the HIGH state a voltage...

Страница 12: ...Operating instructions SG EFS 104 2W Page 12 19 Installation Connection example 2 Connection example 3 Connection example 4 Manual reset Contact multiplication Automatic reset Contact multiplication...

Страница 13: ...ghts up OSSDs 1 and 2 are open Signal circuit closed Signal outputs M1 and M2 are set to LOW 5 Repeat step 1 1 Make sure no sensors are activated Green Power and Sensor LEDs light up OSSDs 1 and 2 are...

Страница 14: ...ps 1 and 2 5 Disconnect the sensor Green Sensor and Output LEDs go out Red Fault LED lights up OSSDs 1 and 2 are open Signal circuit closed Signal outputs M1 and M2 are set to LOW 6 Repeat steps 1 and...

Страница 15: ...or operation Open Closed LOW HIGH Sensor activated Open Closed LOW LOW Fault on sensor cable break Correlations Recommissioning Decommissioning Carry out the commissioning process see Commissioning Di...

Страница 16: ...errupted Check connection to button Manual reset button jammed sticking Replace buttons on S1 and S3 Automatic reset bridge missing Connect bridge between S1 and S2 Control unit is faulty Replace cont...

Страница 17: ...the devices may be returned to us for disposal WEEE reg no DE 39141253 Disposal Control unit Packaging Wood cardboard plastics When disposing of the product Ensure compliance with the relevant nationa...

Страница 18: ...Category 3 PL d MTTFD 257 a 257 a DCavg 60 60 B10D load DC 24 V 1 A 1 8 106 1 8 106 nop assumption 52560 a 52560 a CCF Requirements met Requirements met IEC 60664 1 creep distance and air gap Polluti...

Страница 19: ...3 A quick acting 6 3 A quick acting Line length max 30 m 30 m Signal output PNP M1 S1 M2 S1 M1 A2 M2 A2 Signal type Sensor Fault Sensor Fault Voltage DC 20 to 29 V DC 20 to 29 V DC 18 to 22 V DC 18 to...

Отзывы: