081222 v2.11-RiA
Operating instructions SG-EFS 104/2W
Page 14/19
Commissioning
2. Activate the reset button.
-
Green “Power”, “Sensor” and “Output” LEDs light up
-
OSSDs 1 and 2 are closed
-
Signal circuit open
-
Signal outputs M1 and M2 are set to HIGH
3. Activate the sensor (the described state is only visible while the sensor is being
activated).
-
Green “Sensor” and “Output” LEDs go out
-
OSSDs 1 and 2 are open
-
Signal circuit closed
-
Signal output M1 is set to LOW, M2 is set to HIGH
4. Repeat steps 1 and 2.
5. Disconnect the sensor.
-
Green “Sensor” and “Output” LEDs go out
-
Red “Fault” LED lights up
-
OSSDs 1 and 2 are open
-
Signal circuit closed
-
Signal outputs M1 and M2 are set to LOW
6. Repeat steps 1 and 2.
Throughout the entire time the protective device remains activated, the OSSDs
stay in the OFF state.
If the protective device stops being activated, various states are possible for the
OSSDs. This depends on which reset type is selected (see
Function
,
Reset
).
Protective device activated
Once the functional test has been successfully completed, the protective device is
ready for operation.
If the functional test could not be completed correctly, see
Troubleshooting and
remedies.