1x2x1,5+0,8J-Y(st)Y,   1x2x0,8+0,8J-Y(st)Y   or   1x2x1,5+0,8J-H(st)H,   1x2x0,8+0,8J-H(st)H 
coded cables should be used. While cabling (starting from Loop + terminal), cable

’s earth line 

must be connected to appropriate earth terminal in the control panel (See Annex-B, Figure-2). 
This  earth  line  should  be  installed  throughout  all  detectors  and  call  points.  Earthing  cables 
should  be  wired  after  placing  detectors  and/or  call  points  and  line  should  be  ended. When  a 
return is performed to (Loop -), earthing line should be done as it is shown in Annex-B, 
Figure-2 and line is ended. 

 
 

4.4 Panel PC Connection 

4.4.1 PC Port

 

 

Cable  connection  between  panel  and  PC  for  data  communication  is  plugged  into  the  PC 
Socket  which  found  on  front  panel  of  (See  Annex-B,  Figure-11).  The  communication  cable 
shown in Annex-D must be used for communication with computer. 

 

 

4.4.2 Write Enable Switch

 

 

Write  enable  switch  has  two  positions  as 

“ON”  and  “OFF”.  (Annex-B,  Figure-8)  When  the 

panel  is  energized  while  the  switch  is  OFF,  the  panel  runs  previously  saved  data. When  the 
panel  is  energized  while  the  switch  is  ON,  panel  operation  modes  appears  on  the  screen. 
More details are provided in Section-8. 

4.5 Remote Control Inputs

 

 

There are remote control inputs on the panel which are likely to control the panel remotely by 
the  help  of  any  remote  button.  One  terminal  of  the  button  is  connected  to  the  desired  input 
and other one is connected to GND. (See Annex-B, Figure-6). It should be used the cable with 
this code; 2x1,5 N2XH or 2x1,5 NYY for remote control input line. 

 

AL       : 

Reactivates alarm condition, sounders and relays which was silenced and positioned 

by Silence Alarm. 

FLT     : 

Activates fault condition. 

RS       : 

Resets the panel. 

SIL      : 

Silences sounders and returns the relays to their initial position. 

 

5- PANEL OUTPUTS 

 

5.1 Sounder Outputs (4 Units) 

 

The panel has 4 sounder outputs rated 24 V DC 500mA. In order to monitor the line against to 
open  or  short  circuit  conditions,  normally  16  V  DC  reverse  voltage  is  seen from  the  sounder 
outputs.  During fire alarm  outputs  are  driven by  24  V DC (Annex-B,  Figure-4).  Current driven 
more than 0.5A leads the panel into the fault condition. 

 

2x1,5  N2XH  or  2x1,5  NYY  cable  should  be  used  for  the  sounder  line.  10KOhm  resistor, 
located  on  sounder  outputs  from  factory  default  is  used  as  end-of-line  resistor  and  must  be 
connected  to  the  end  of  the  sounder  line.  Otherwise,  open  circuit  fault  is  monitored  on  the 
sounder  line  of  panel.  In  case  of  any  open  circuit  or  short  circuit  faults  occurred,  it  can  be 
displayed on the screen of panel with the line number. 
 
 
 
 

 

Содержание ML-121X

Страница 1: ...COMMISSIONING OPERATING AND MAINTENANCE MANUAL MODEL MAXLOGIC SERIES SUB MODEL INTELLIGENT ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL ML 121X...

Страница 2: ...ontrol Buttons 8 6 2 Front Panel Indicators 10 6 3 Internal Indicators 11 7 PANEL FUSES 11 8 POWERING THE PANEL 12 8 1 First Boot of Panel 12 8 2 Booting Previously ConfiguredPanel 16 9 FIRE EVENT MES...

Страница 3: ...Panel also contains 3 volt free 30 V DC 1A relay outputs fire relay alarm relay fault relay and a 24V DC 500mA auxiliary power supply output Furthermore 4 remote control inputs alarm silence sound al...

Страница 4: ...st be made definitely and the mains power supply must be presented through the device via a fuse assigned only to this device If the earth connection is not made appropriately all the conductive parts...

Страница 5: ...he control panel must be as like in Annex B Figure 7 A 0 resistor must be connected to the unused loops Each device in the loop must be addressed via MG 8200 Address Programmer depending on the archit...

Страница 6: ...in Section 8 4 5 Remote Control Inputs There are remote control inputs on the panel which are likely to control the panel remotely by the help of any remote button One terminal of the button is conne...

Страница 7: ...utput is activated on any fire event and it can be used to trigger any other system The output is returned to its initial position only by pressing Reset button on panel 5 3 2 Alarm Relay The output i...

Страница 8: ...uate Used for the purpose of evacuation It requires to be programmed by the Loop Manager Program Pressing this button Buzzer sounds Sounders ring Alarm and fire relays get activated Fire LEDs and Evac...

Страница 9: ...t Pre Alarms Securities Internal Events Direction buttons Button number 1 It is used to go upward in the panel s main menu screen and in the More Events menu Button number 2 It is used to select the d...

Страница 10: ...led It shows that the sounder outputs on the panel has been disabled and illuminates as yellow Disablement If any device or line disabled in the system this LED illuminates as Yellow More Fires It ind...

Страница 11: ...circuit message is seen Panel s sounder 2 output becomes unusable Sounder 3 Self resetting fuse FSO5 Self resetting and become active on 0 5 current overload Sounder fault Led illuminates and on LCD s...

Страница 12: ...ON ON Position 8 1 First Boot of Panel 8 1 1 Cabling Before powering the panel all connections should be made properly depending on the connection scheme in ANNEX B 8 1 2 Checking cabling All the con...

Страница 13: ...o n f i g T y p e C l e a r V a l i d D a t a _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ E x i t C a n c e l E n t e r A c c e p t Activating this option will era...

Страница 14: ...which found on the panel front cover For the cable connection see Annex D The selection of Download from Panel or Upload to Panel operations is made through the Loop Manager Software as shown on the...

Страница 15: ...case the panel should be deenergized the connection cables should be checked and all the above steps should be repeated after debugging the problem 8 1 5 Booting panel At the end of automatic learnin...

Страница 16: ...1 32 Printer Port 0 I O Driver Zone Leds 33 64 Network Status information format of checked units in the panel is as like OK Fault In case the internal device has version number then this number appea...

Страница 17: ...panel memory then this option will not be available to be selected It is also possible to load automatically the data saved to panel by turning ON the panel while Write Enable Switch is ON To keep th...

Страница 18: ...the faulty device is displayed 6 In the 6th row fault type is displayed 11 PANEL MENU There are 3 access levels in order to prevent unauthorized access a Access level 1 Button Control key is Disabled...

Страница 19: ...values which are assigned to output devices through Loop Manager software TEST It is possible to test the system by activating loop s zone s and device s for a while Access level 3 Test Reset Delay T...

Страница 20: ...vices is selected here Resound on an event From any zone Resound on an event From diff zone Resound on an event From the same zone Never resound Bypassing Condition Delay value which is assigned to ou...

Страница 21: ...ARM Mode Sounders do not ring the pre alarm message appears on screen In case of any other fire alarm from any zone the same or different zone within the adjusted time the panel goes into ALARM mode a...

Страница 22: ...n be done with the aid of this feature Version update can only be done by the manufacturer LCU 1 B V 1 0 0 A P P V 1 0 12 Contamination Control The system devices may be contaminated in time because o...

Страница 23: ...1 L 1 A 4 3 C o n t a m i n a t e d d e v i c e _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ U p D o w n S c r o l l E n t e r U p d a t e Analog Update Due to this...

Страница 24: ...N ML 123X N ML 124X N ML 125X N GCU Gateway Controller allows the network to be monitored graphically and controlled remotely from a distant place GCU connect to the network line as a control panel T...

Страница 25: ...istor of Panel which will operate in the network 250 Kbps 1 0 0 0 0 0 100 Kbps 0 1 0 0 0 0 50 Kbps 0 0 1 0 0 0 20 Kbps 0 0 0 1 0 0 10 Kbps 0 0 0 0 1 0 5 Kbps 0 0 0 0 0 1 Communication Speed 1 2 3 4 5...

Страница 26: ...sions Weight 1 to 2 loops 4 x 24 V DC 500 mA programmable Supervised self resetting fuse protected 10 kOhm end of line resistor 30 V DC 1 A volt free contact programmable 30 V DC 1 A volt free contact...

Страница 27: ...sable fire alarm panel 1 Loop 127 Address 230V AC 50 Hz 83 Watt IP30 ML 1211 N Maxlogic intelligent analogue addressable fire alarm panel 1 Loop 127 Address Network 230V AC 50 Hz 83 Watt IP30 ML 1212...

Страница 28: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 28 ANNEX A PANEL DIMENSIONS AND MOUNTING HOLES Figure 1 Panel Dimensions Figure 2 Mounting Holes...

Страница 29: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 29 ANNEX B CONNECTION SCHEME...

Страница 30: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 30 ANNEX C PANEL SPARE PARTS...

Страница 31: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 31 ANNEX D SERIAL COMMUNICATION CABLE...

Страница 32: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 32 ANNEX E SCHEME OF MENU FUNCTIONS...

Страница 33: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 33...

Страница 34: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 34...

Страница 35: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 35...

Страница 36: ...ANNEX F NETWORK CONNECTION SCHEME KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 36...

Отзывы: