KK-641.002 Rev.No:1 01.08.12 ML-121X User Manual Page | 17
Panel is energized while
‘Write Enable Switch’ is in ‘ON’ position. The screen to select
operating mode appears:
Re-Initiate System
(Automatic learning results in erasing the already existing data (such as
zone location texts etc.). For this reason this information must be well noted.)
PC Program
(It is also possible to update data in normal operating mode.)
Use Valid Data
8.2.2.1. Updating panel configuration file:
Previously created (if it exists) configuration file (*.hrz) is open through Loop Manager
software or the data is downloaded from the panel. The desired changes are made and finally,
the file is uploaded to panel. (See, Section 8.1.4.2. PC Program)
8.2.2.2. Using valid data:
In order to select
‘Use Valid Data’ option, panel is energized while ‘Write Enable Switch’ is
‘ON’. In this configuration type; the latest data is reloaded to the panel and activated. If there
is no correct data kept in the panel memory, then this option will not be available to be
selected. (It is also possible to load
automatically
the data saved to panel by turning ON the
panel while
‘Write Enable Switch’ is ‘ON’.)
To keep the previous data in panel memory is provided by the battery. If the battery detaches
or broken then all the data kept in the panel get lost.
9- FIRE EVENT MESSAGE FORMAT on PANEL LCD SCREEN
On fire event, the panel displays a message in 4 lines as shown below; alarm relays and fire
relays get activated, buzzer and sounders ring.
Z o n e s
I n
A l a r m :
1
D i s . : 2
F a u l t : 1
*
F I R E : M G 6 2 0 8
8 - W a y
S W . M o n .
Z o n e : 1 *
P : 0
L : 1
A : 2 8 M L - 1 2 X X
R e - i n i t i a t e d
F L O O R
C O R R I D O R
1.
In the 1
st
row following information is displayed;
Zone In Alarm: Number of Alarm at the zones
Disablements: Total number of disablements
Fault: Total number of faults
2.
In the 2
nd
row; the device model and zone number in which fire alarm comes is
dispalyed.
3.
In the 3
rd
row; panel, loop, address number, and panel name of the device in which fire
alarm comes is displayed.
4.
In the 4
th
row; zone name of the device where fire alarm comes is displayed.
Содержание ML-121X
Страница 29: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 29 ANNEX B CONNECTION SCHEME...
Страница 30: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 30 ANNEX C PANEL SPARE PARTS...
Страница 31: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 31 ANNEX D SERIAL COMMUNICATION CABLE...
Страница 32: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 32 ANNEX E SCHEME OF MENU FUNCTIONS...
Страница 33: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 33...
Страница 34: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 34...
Страница 35: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 35...
Страница 36: ...ANNEX F NETWORK CONNECTION SCHEME KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 36...