KK-641.002 Rev.No:1 01.08.12 ML-121X User Manual Page | 4
2- WARNINGS
The panel contains static-sensitive high quality electronic control equipment. Do not use the
panel before reading this manual.
In case of any fault, only the technicians of the manufacturer or technicians authorized by the
manufacturer should repair or maintain the panel.
The person who will operate the system should be well trained on powering and operating the
system.
Two years of warranty is valid from the production date as long as the system is used with
regard of obeying the rules, instructions and recommendations provided by the manufacturer.
Use the recommended cable types defined in this manual for cabling of panel power supply,
sounder power supply and detector line. Do not remove any connections and do not make any
connections while mains power supply is connected. Pane
l’s earth connection must be made
definitely.
Do NEVER apply 230V AC 50Hz mains power into the detectors and manual call points input
terminals, sounder line outputs and battery connection inputs.
This panel has been designed to operate on 230 V AC 50 Hz power supply. The protective
earth connection must be made definitely and the mains power supply must be presented
through the device via a fuse assigned only to this device. If the earth connection is not made
appropriately, all the conductive parts in the device may result in electrical leakage and this
may create hazard.
‘Automatic Learning’ causes erasing of existing configuration data at the panel. Therefore, it is
recommended to download the configuration data to PC, before
‘Automatic Learning’.
3- MOUNTING
The chosen mounting site of the panel must be clean, dry, not subject to shock or vibration
and easily accessible. The temperature must be in between the temperature range of
-5C
° and +50C°. The relative humidity must not be m ore than 95%.
The panel should be mounted on a flat surface in such a way that, the indicators should be at
the eye-level and must not be mounted near the sources of excessive heat or cold and inside
of any cabinet.
Uncover the panel via the allen key provided with the panel.
Panel cable entries from back and top of the panel are available for easy mounting. Mark the
position of the fixing holes according to the respective Annex-A, Figure-2; ensuring that the
wall is flat at the chosen location.
Screws or bolts of a minimum of 4mm diameter must be used to mount the cabinet in all four
mounting positions. Drill and plug the wall then fix the cabinet using all fixing points.
Содержание ML-121X
Страница 29: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 29 ANNEX B CONNECTION SCHEME...
Страница 30: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 30 ANNEX C PANEL SPARE PARTS...
Страница 31: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 31 ANNEX D SERIAL COMMUNICATION CABLE...
Страница 32: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 32 ANNEX E SCHEME OF MENU FUNCTIONS...
Страница 33: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 33...
Страница 34: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 34...
Страница 35: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 35...
Страница 36: ...ANNEX F NETWORK CONNECTION SCHEME KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 36...