1- INTRODUCTION 

 

Maxlogic  ML-121X  series  intelligent  analogue  addressable  fire  alarm  control  panels  are 
provided  with  0,  1,  2  loop  options  and 1000  user-defined  zone  capacity.  Up  to 127  analogue 
addressable devices per loop are allowed to be connected. 

 

Devices operating with VIP protocol such as Photo-Electric Smoke Detectors, Heat Detectors, 
Multi-Sensor   Detectors,   Switch   Monitor   Modules,   Relay   Controller   Modules,   Sounder 
Controller  Modules,  Loop-powered  Addressable  Sounders  and  Zone  Monitor  Modules  are 
compatible with ML-121X series control panels. 

 

The  project  planning  must  be  made  carefully,  in  order  not  to  have  any  difficulties  when 
commissioning the system. Zone location text (up to 40 characters including blank spaces) for 
each  device  should  be  predetermined.  Then,  the  devices  should  be  categorized  in  zones 
depending  on  the  physical  specifications  of  the  building.  After  these  steps,  the  panel  can  be 
configured via the software program called 

‘Loop Manager’. 

 

The  panel  is  equipped  with  4  programmable  and  fault  monitored  24  V  DC  500mA  sounder 
outputs. Panel also contains 3 volt-free 30 V DC 1A relay outputs (fire relay, alarm relay, fault 
relay)  and  a  24V  DC  500mA  auxiliary  power  supply  output.  Furthermore,  4  remote  control 
inputs (alarm, silence/sound alarm, reset and fault) exist in the panel. 

 

ML-121X series fire alarm control panels have the optional functions described in TS EN 54-2 
standards; 

 

Sounder outputs 

 

ML-121X  series  fire  alarm  control  panels  have  also  the  supporting  functions  described  in  TS 
EN 54-2 standards; 

 

Network: The supporting function used to communicate in network. 

 

 

NOTE: This user manual is valid for the panel models indicated in 14

th 

section. 

 

 

Producer-manufacturer or importer firms’ title, address, and telephone number 

Manufacturer Firm: 

MAVILI ELEKTRONIK TICARET VE SANAYI A.S. 
SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY 

TEL: +90 216 466 45 05 - +90 216 466 45 10 
 

Service stations’ communication information that related spare parts have been 
provided 

Authorized Services: 

MAVILI ELEKTRONIK TICARET VE SANAYI A.S. 

SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/1-2-4 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 466 45 05 - +90 216 466 45 10 
TEKSIS TEKNIK ELEKTRONIK SIS.TIC. VE SAN. LTD. STI. 

SERIFALI MAHALLESI, KUTUP SOKAK NO: 27/3 UMRANIYE / ISTANBUL / TURKEY 
TEL: +90 216 313 60 60 - +90 216 313 47 49 

 

Expected operation life which has been determined and announced by related ministry 

This device’s expected operation life is 7 years. 

 

Содержание ML-121X

Страница 1: ...COMMISSIONING OPERATING AND MAINTENANCE MANUAL MODEL MAXLOGIC SERIES SUB MODEL INTELLIGENT ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL ML 121X...

Страница 2: ...ontrol Buttons 8 6 2 Front Panel Indicators 10 6 3 Internal Indicators 11 7 PANEL FUSES 11 8 POWERING THE PANEL 12 8 1 First Boot of Panel 12 8 2 Booting Previously ConfiguredPanel 16 9 FIRE EVENT MES...

Страница 3: ...Panel also contains 3 volt free 30 V DC 1A relay outputs fire relay alarm relay fault relay and a 24V DC 500mA auxiliary power supply output Furthermore 4 remote control inputs alarm silence sound al...

Страница 4: ...st be made definitely and the mains power supply must be presented through the device via a fuse assigned only to this device If the earth connection is not made appropriately all the conductive parts...

Страница 5: ...he control panel must be as like in Annex B Figure 7 A 0 resistor must be connected to the unused loops Each device in the loop must be addressed via MG 8200 Address Programmer depending on the archit...

Страница 6: ...in Section 8 4 5 Remote Control Inputs There are remote control inputs on the panel which are likely to control the panel remotely by the help of any remote button One terminal of the button is conne...

Страница 7: ...utput is activated on any fire event and it can be used to trigger any other system The output is returned to its initial position only by pressing Reset button on panel 5 3 2 Alarm Relay The output i...

Страница 8: ...uate Used for the purpose of evacuation It requires to be programmed by the Loop Manager Program Pressing this button Buzzer sounds Sounders ring Alarm and fire relays get activated Fire LEDs and Evac...

Страница 9: ...t Pre Alarms Securities Internal Events Direction buttons Button number 1 It is used to go upward in the panel s main menu screen and in the More Events menu Button number 2 It is used to select the d...

Страница 10: ...led It shows that the sounder outputs on the panel has been disabled and illuminates as yellow Disablement If any device or line disabled in the system this LED illuminates as Yellow More Fires It ind...

Страница 11: ...circuit message is seen Panel s sounder 2 output becomes unusable Sounder 3 Self resetting fuse FSO5 Self resetting and become active on 0 5 current overload Sounder fault Led illuminates and on LCD s...

Страница 12: ...ON ON Position 8 1 First Boot of Panel 8 1 1 Cabling Before powering the panel all connections should be made properly depending on the connection scheme in ANNEX B 8 1 2 Checking cabling All the con...

Страница 13: ...o n f i g T y p e C l e a r V a l i d D a t a _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ E x i t C a n c e l E n t e r A c c e p t Activating this option will era...

Страница 14: ...which found on the panel front cover For the cable connection see Annex D The selection of Download from Panel or Upload to Panel operations is made through the Loop Manager Software as shown on the...

Страница 15: ...case the panel should be deenergized the connection cables should be checked and all the above steps should be repeated after debugging the problem 8 1 5 Booting panel At the end of automatic learnin...

Страница 16: ...1 32 Printer Port 0 I O Driver Zone Leds 33 64 Network Status information format of checked units in the panel is as like OK Fault In case the internal device has version number then this number appea...

Страница 17: ...panel memory then this option will not be available to be selected It is also possible to load automatically the data saved to panel by turning ON the panel while Write Enable Switch is ON To keep th...

Страница 18: ...the faulty device is displayed 6 In the 6th row fault type is displayed 11 PANEL MENU There are 3 access levels in order to prevent unauthorized access a Access level 1 Button Control key is Disabled...

Страница 19: ...values which are assigned to output devices through Loop Manager software TEST It is possible to test the system by activating loop s zone s and device s for a while Access level 3 Test Reset Delay T...

Страница 20: ...vices is selected here Resound on an event From any zone Resound on an event From diff zone Resound on an event From the same zone Never resound Bypassing Condition Delay value which is assigned to ou...

Страница 21: ...ARM Mode Sounders do not ring the pre alarm message appears on screen In case of any other fire alarm from any zone the same or different zone within the adjusted time the panel goes into ALARM mode a...

Страница 22: ...n be done with the aid of this feature Version update can only be done by the manufacturer LCU 1 B V 1 0 0 A P P V 1 0 12 Contamination Control The system devices may be contaminated in time because o...

Страница 23: ...1 L 1 A 4 3 C o n t a m i n a t e d d e v i c e _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ U p D o w n S c r o l l E n t e r U p d a t e Analog Update Due to this...

Страница 24: ...N ML 123X N ML 124X N ML 125X N GCU Gateway Controller allows the network to be monitored graphically and controlled remotely from a distant place GCU connect to the network line as a control panel T...

Страница 25: ...istor of Panel which will operate in the network 250 Kbps 1 0 0 0 0 0 100 Kbps 0 1 0 0 0 0 50 Kbps 0 0 1 0 0 0 20 Kbps 0 0 0 1 0 0 10 Kbps 0 0 0 0 1 0 5 Kbps 0 0 0 0 0 1 Communication Speed 1 2 3 4 5...

Страница 26: ...sions Weight 1 to 2 loops 4 x 24 V DC 500 mA programmable Supervised self resetting fuse protected 10 kOhm end of line resistor 30 V DC 1 A volt free contact programmable 30 V DC 1 A volt free contact...

Страница 27: ...sable fire alarm panel 1 Loop 127 Address 230V AC 50 Hz 83 Watt IP30 ML 1211 N Maxlogic intelligent analogue addressable fire alarm panel 1 Loop 127 Address Network 230V AC 50 Hz 83 Watt IP30 ML 1212...

Страница 28: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 28 ANNEX A PANEL DIMENSIONS AND MOUNTING HOLES Figure 1 Panel Dimensions Figure 2 Mounting Holes...

Страница 29: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 29 ANNEX B CONNECTION SCHEME...

Страница 30: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 30 ANNEX C PANEL SPARE PARTS...

Страница 31: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 31 ANNEX D SERIAL COMMUNICATION CABLE...

Страница 32: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 32 ANNEX E SCHEME OF MENU FUNCTIONS...

Страница 33: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 33...

Страница 34: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 34...

Страница 35: ...KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 35...

Страница 36: ...ANNEX F NETWORK CONNECTION SCHEME KK 641 002 Rev No 1 01 08 12 ML 121X User Manual Page 36...

Отзывы: