V. MENU SCREENS (CONT.)

Status: AUTO MAX

 

 PSID : 0003.0

 

 Press OK to Start

 

 A Flush Cycle

 

Status: AUTO MAX

 

>> High PSID <<
Press OK to Start
A Flush Cycle

Status: ON MAX

 

Flush Cycle

 

Press ESC to Stop

 

Status: AUTO MAX

 

 PSID : 0003.2

 

 Press OK to Start

 

 A Flush Cycle

 

Status: ON MAX

 

>> System Alarm <<

Press ESC to Stop

 

Status: AUTO MAX 

Indicates that the Inlet Pressure is not Low, and the controller is waiting 
for a Flush cycle to begin. The system is assumed to be in normal filtra-
tion mode and flowing water. The Flush interval timer is running. The 
controller displays Status: AUTO MAX when the Inlet Pressure in not 
low and a Flush cycle has not begun. A Flush can occur from the Timer, 
a high pressure differential via the Pressure Transducers, indicated as 
>> High PSID << on the display, manually by the operator by pressing
the green OK button on the controller, or by the Customer Input Signal.

Status: ON MAX 

Indicates that the system is in a Flush cycle, initiated either by the Oper-
ator, by the Flush Interval Timer, the Pressure Transducers, or by the 
Customer Input Signal. The controller will stop displaying the PSID val-
ue, but will instead indicate Flush Cycle.

 

The Flush Valve is opened, and the Alarm Light/Sounder output is flash-
ing. This output flashes the Light and Sounder throughout the entire 
Flush cycle. The Flush Duration is nominally set for 8 seconds. The Flush 
Duration time is adjustable 

-

 see Setup screen #3 for information.

 

After this Flush duration time, the Flush Cycle is complete. The Open 
Flush Valve Output will be turned off, the Alarm Light/Sounder will be 
turned off, and the Status Screen will display Status: AUTO MAX.

 

Status: System Alarm

 

On any of the status screens, a System Alarm screen can be activated. 
The second line down will be alternately flashing >> System Alarm << 
and whatever was on line 2 before the system alarm occurred.

 

A system alarm can be any customer specific alarm. The only standard 
system alarm is the Consecutive Flush Alarm. This alarm occurs when 
the Flush cycle has been initiated three times in a row by the Pressure 
Transducers (PSID). Output #4 will be turned ON, which will then ener-
gize Relay 1 (R

-

1). Relay 1 provides a Dry Contact signal for the Custom-

er

s Consecutive Flush Alarm monitoring.

 

The Consecutive Flush Alarm will also cause the Alarm Light/Sounder to 
change from flashing to steady ON. The Consecutive Flush Alarm will 
also disable any additional Flush Cycles from occurring.

 

Содержание THOMPSON MILLER LEAMAN PDA/ATF-MAX

Страница 1: ...nstallation and or operation of controller Failure to Comply with instructions and safety precautions could lead to personal injury or product damage Please call and ask to speak with one of our custo...

Страница 2: ...roller screen and keypad interface as shown The clear cover provides protection for the controller and can be opened with the two latches on the side of the controller housing to access the keypad A P...

Страница 3: ...ows for a remote reset of the Consecutive Flush Alarm Scrolling through Menu Screens The PDA ATF MAX allows the operator to scroll through a selection of menu screens by pressing the A or B buttons Pr...

Страница 4: ...atus OFF MAX High PSID Status OFF MAX The Inlet Pressure transducer is monitored to sense sufficient Inlet Pressure and allow Timed Flushes and Differential Pressure Flushing When the inlet pressure i...

Страница 5: ...ut will instead indicate Flush Cycle The Flush Valve is opened and the Alarm Light Sounder output is flash ing This output flashes the Light and Sounder throughout the entire Flush cycle The Flush Dur...

Страница 6: ...is 7 PSID This set point is located on Screen 2 Flush Duration Screen The time allotted for the Flush Valve to be open This time should be set according to the type of filter and the nature of the mat...

Страница 7: ...elapsed since the system last Flushed example 00011 30 is 11 hours and 30 minutes and how the last Flush was triggered There are four trigger possibilities 1 Local Operator Flush triggered manually by...

Страница 8: ...t input will signal the PDA ATF MAX to remotely reset the Consecutive Flush Alarm The Analog Digital Input locations allow Miller Leaman Inc to design customer specific programs These programs are the...

Страница 9: ...assigned to the input IC or ID blue to the Common terminal and the brown to the 24VDC Power terminal Customer Initiated Flush Signal Optional The optional Customer Initiate Flush Signal input is conn...

Страница 10: ...Page 10 VIII ELECTRICAL SCHEMATIC...

Страница 11: ...te preparation maintenance or environmental conditions MLI MAKES NO OTHER REPRESENTATIONS OR WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRAN TY OF MERCHANTABILITY OR FITN...

Отзывы: