background image

Page 3

 

Startup

 

1) Plug in the power plug into a standard 115VAC wall outlet
2) Upon power

-

up, the company information screen will be shown for 15 seconds.

3) After 15 seconds, the screen will change to the manifold pressure screen  and will begin monitoring differential pressure across

the strainer.

Automatic Flushing

 

Under normal operation, a timed flush will be initiated on a periodic schedule defined by the PDA/ATF

-

MAX programmed setting. 

(every 24 hours per factory setting).  

 

In addition, a timed flush will be initiated when the differential pressure reaches the setpoint defined by the PDA/ATF

-

MAX 

settings.  

 

See the 

MENU SCREENS 

section for information on changing factory settings.

 

Consecutive Flush Alarm

 

If three consecutive flushing operations are detected by the PDA/ATF

-

MAX, a consecutive flush alarm will be triggered and no addi-

tional flush cycles will be initiated until the alarm is cleared.

 

To reset the Consecutive Flush Alarm, first, correct the cause of the alarm, then push the red ESC button on the controller while a 
Status screen is displayed. The optional Customer

s Remote Reset input, Input iB, allows for a remote reset of the Consecutive 

Flush Alarm.

 

Scrolling through Menu Screens 

The 

PDA/ATF

-

MAX

 allows the operator to scroll through a selection of menu screens by pressing the 

or 

buttons. Press 

to scroll backward to the previous menu or press 

to scroll forward to the next menu. The LCD backlight will automatically 

turn on for 5 minutes when a button is pressed, thus allowing the operator to easily view the menus in low light situations.

 

Changing Parameter Values

 

To change an adjustable value, first scroll to the appropriate menu screen using the A or B button. Follow the directions below to 
modify the value.

 

1) The current selected value will show flashing blocks. Use the + or 

-

 keys to select another value if desired.

2) Press OK on the selected value. The value will change from flashing blocks to flashing numbers. Flashing blocks indicate the

value is locked into memory. Flashing numbers indicates the value is unlocked and can be changed.

3) Press the + or 

-

 buttons to change the value. Holding the + or 

-

 button will allow the value to increase at a faster rate after the

first 10 increments have passed.

4) When finished, press OK to save the change to memory. The value will return to flashing blocks.

REFER TO THE MENU SCREENS SECTION FOR DETAILED INFORMATION ON EACH SCREEN AND/OR PARAMETER.

 

IV. OPERATION

Содержание THOMPSON MILLER LEAMAN PDA/ATF-MAX

Страница 1: ...nstallation and or operation of controller Failure to Comply with instructions and safety precautions could lead to personal injury or product damage Please call and ask to speak with one of our custo...

Страница 2: ...roller screen and keypad interface as shown The clear cover provides protection for the controller and can be opened with the two latches on the side of the controller housing to access the keypad A P...

Страница 3: ...ows for a remote reset of the Consecutive Flush Alarm Scrolling through Menu Screens The PDA ATF MAX allows the operator to scroll through a selection of menu screens by pressing the A or B buttons Pr...

Страница 4: ...atus OFF MAX High PSID Status OFF MAX The Inlet Pressure transducer is monitored to sense sufficient Inlet Pressure and allow Timed Flushes and Differential Pressure Flushing When the inlet pressure i...

Страница 5: ...ut will instead indicate Flush Cycle The Flush Valve is opened and the Alarm Light Sounder output is flash ing This output flashes the Light and Sounder throughout the entire Flush cycle The Flush Dur...

Страница 6: ...is 7 PSID This set point is located on Screen 2 Flush Duration Screen The time allotted for the Flush Valve to be open This time should be set according to the type of filter and the nature of the mat...

Страница 7: ...elapsed since the system last Flushed example 00011 30 is 11 hours and 30 minutes and how the last Flush was triggered There are four trigger possibilities 1 Local Operator Flush triggered manually by...

Страница 8: ...t input will signal the PDA ATF MAX to remotely reset the Consecutive Flush Alarm The Analog Digital Input locations allow Miller Leaman Inc to design customer specific programs These programs are the...

Страница 9: ...assigned to the input IC or ID blue to the Common terminal and the brown to the 24VDC Power terminal Customer Initiated Flush Signal Optional The optional Customer Initiate Flush Signal input is conn...

Страница 10: ...Page 10 VIII ELECTRICAL SCHEMATIC...

Страница 11: ...te preparation maintenance or environmental conditions MLI MAKES NO OTHER REPRESENTATIONS OR WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRAN TY OF MERCHANTABILITY OR FITN...

Отзывы: