COMMUNICATIONS INTERFACE
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 51 of 67
Command
Description
Range
Output 1
0x007
Sets the 0 to 10V output to 0%.
Change the value until the meter reads 0.00 volts.
{0, 9999}
0x008
Sets the 0 to 10V output to 100%
Change the value until the meter reads 10.00 volts.
{0, 9999}
0x009
Sets the 0 to 20mA output to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
0x00A
Sets the 0 to 20mA output to 100%.
Change the value until the meter reads 20.00 mA,
{0, 9999}
Output 2
0x00B
Sets the 0 to 10V output to 0%.
Change the value until the meter reads 0.00 volts.
{0, 9999}
0x00C
Sets the 0 to 10V output to 100%
Change the value until the meter reads 10.00 volts.
{0, 9999}
0x00D
Sets the 0 to 20mA output to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
0x00E
Sets the 0 to 20mA output to 100%.
Change the value until the meter reads 20.00 mA,
{0, 9999}
Output 3
0x00F
Sets the 0 to 10V output to 0%.
Change the value until the meter reads 0.00 volts.
{0, 9999}
0x010
Sets the 0 to 10V output to 100%
Change the value until the meter reads 10.00 volts.
{0, 9999}
0x011
Sets the 0 to 20mA output to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
0x012
Sets the 0 to 20mA output to 100%.
Change the value until the meter reads 20.00 mA,
{0, 9999}
Meter Output
0x013
Sets the meter output 1 to 0%.
Change the value until the meter reads 0.00 mA.
{0, 9999}
0x014
Sets the meter output 1 to 100%.
Change the value until the meter reads 1.00 mA.
{0, 9999}
0x015
Sets the meter output 2 to 0%.
Change the value until the meter reads 0.00 mA
{0, 9999}
0x016
Sets the meter output 2 to 100%.
Change the value until the meter reads 1.00 mA
{0, 9999}
8.7.5
Reset processor
For changes to take effect, the processor must be reset after
changing the IP Address, Subnet Mask, or Communications Type.