CALIBRATE TENSION USING KEYPAD
www.maxcessintl.com
DLCA NET-S1
MI 850A374 1 A
Page 24 of 67
5.0
Calibrate tension using the keypad
See section 9.0 to perform calibrations from the
communication interface.
The DLCA NET-S1 uses Precision calibration. Precision
calibration is used when applying a known weight with a rope
in the web path to the load cells for calibration. Typically, this
known weight should be 10% of the load cell rating or greater.
Calibration menus
Tension zone
Calibration mode
Use menu
1
Precision
CAL1.1
2
Precision
CAL2.1
1 and 2
Precision
CAL3.1
5.1
Precision calibration
When editing a number, the digit being edited will flash. Use
the [
] button to select the digit to edit. Use the [+] and [-]
buttons to increment or decrement the digit number.
Press and hold [+] and [-] for two seconds to enter
programming mode.
Use [+] and/or [-] to go to parameter P.02.
Press [Enter] to see the present load cell excitation voltage.
Select 7.5V if using MAGPOWR load cells.
Select either 5V or 7.5V if using non-MAGPOWR load cells.
Press and hold [Enter] for two seconds (until the display starts
flashing) to store the changes.
The following calibrations must be done in order listed and in
full.