COMMISSIONING
5 - 2
DSE-17
www.maxcess.eu
MI 1064 1 C
∙
Calibrate the web guide controller to the lower reference
value
Note:
For further information see the Operating Instructions for the
web guide controller in the system documentation.
DP-20, DP-30: Menu 3x.1.4 Calibration for edge sensors
D-MAX: Menu 1y.5.1.1.1 Calibration
FIFE 500: Sensor setup menu
∙
Press key S1 and hold 0.5s to continue with the calibration of
the upper reference value.
LED H1 flashes (long on - short off)
Depending on the configuration, all analog outputs of the
sensor return 10mA or 20mA.
This assigned value is used to determine the reference value
for the covered sensor on the web guide controller (field of
view completely covered by material).
∙
Calibrate the web guide controller to the upper reference
value
∙
Press key S1 and hold 0.5s to return to calibration of the
lower reference value.
The web guide controller can be calibrated to the next sensor
signal.
or
Press the S1 key and hold it for 3seconds to return to the
regular operation state
Calibrating sensor
DSE-17
After final installation, the sensor must be recalibrated to
achieve the best accuracy.
Due to certain circumstances such as changes in environmental
conditions (major changes in temperature, etc.) or wear tracks
on the safety panes of the sensor, it may become necessary to
recalibrate the sensor. Especially when transparent material is
being scanned, regular calibration may be required to maintain
measurement accuracy.
Note:
If no key is pressed for more than 2minutes the sensor returns
to its regular operation state. No calibration data will be saved.