Pompe di calore inverter aria/acqua con ventilatori assiali
14.13
POWER FAILURE
When restored:
•
the instrument goes back to the condition it was in prior to the power failure
•
if a defrost cycle is in progress, it is cancelled
•
all of the timers in progress are cancelled and reinitialized
14.14
UTILITIES BLOCK ALARM TABLE
Code
DESCRIPTION
Block
E00
Remote off
Machine
E001
High pressure alarm
Machine
E002
Low pressure alarm
Machine
E005
Antifreeze alarm
Machine
E006
Flow alarm
Machine
E008
Compressor driver limitation alarm
Machine
E009
Discharge high temperature alarm
Machine
E010
Solar collector high temperature alarm
Solar pump
E018
Cooling high temperature alarm
Machine
E020
Inverted trasductors pressure alarm
Machine
E041
Inconsistent temperatures alarm
Macchina
E050
DHW storage tank high temperature alarm
Machine/sanitary
E101
Communication timeout with Slave 1
Machine
E611
Water inlet probe failure
Machine
E621
Water outlet probe failure
Machine
E631
Compressor intake probe failure
Machine
E641
Compressor discharge probe fault / high pressure switch trip
Machine
E651
Outdoor air probe failure
Machine
*E652
Mixer probe failure
Machine
E661
DHW probe failure
Machine
*E662
Solar storage tank probe failure
Machine
E671
Plant remote probe failure
Machine
*E672
Solar collector probe failure
Machine
E691
Low pressure transducer failure
Machine
E701
High pressure probe failure
Machine
E711
0-10Vdc live input failure
Machine
E801
Pressure inverter timeout
Compressor
E851
Inverter Hardware problem
Compressor
E861
Motor current too high
Compressor
E871
Heatsink over-heat protection
Compressor
E881
Supply voltage out of limits (DC Bus Error)
Compressor
E891
Driving protection-output phase loss
Compressor
E901
Compressor driver and model mismatch
Compressor
E911
Overload protection
Compressor
E921
PFC_POE over current
Compressor
E931
Comunication error with main controller
Compressor
E941
PFC converter fault
Compressor
E951
Heatsink and/or ambient temperature sensor error
Compressor
E961
Abnormal condition
Compressor
E971
EEPROM not initialize
Compressor
(*) If Gi module present
15. MODBUS VARIABLES
The controller is configured as follows by default:
BAUD RATE
9600
PARITY
EVEN
DATA BIT
8
STOP BIT
1
DEVICE ID
1