31
i-32V5
Pompe di calore inverter aria/acqua con ventilatori assiali
Parame-
ter
Description
Unit
Default
Range
Visibility
Allowed configurations:
Description
Notes
Coo
First cooling setpoint
°C
7.0
25÷Coo2
U
Hea
First heating setpoint
°C
45.0
Hea2÷H01
U
San
Sanitary setpoint
°C
48.0
25÷H01
U
If sanitary function
active. See par. 10.2
Coo2
Second cooling setpoint
°C
18.0
Coo÷25
U
Hea2
Second heating setpoint
°C
35.0
25÷Hea
U
*rCO
Mixing valve summer set
-
point
°C
15.0
-50÷80
I
Config if Gi accessory
present
*rHE
Mixing valve winter setpoint
°C
30.0
-50÷80
I
Config if Gi accessory
present
H10
Sanitary function enabling
/
0
0÷6
I
See par. 10.2
H17
Input configuration
Analogue ST6
/
0
0÷49
I
0 = Input disabled
6 = Domestic hot water probe
H18
Input configuration
Analogue ST7
/
0
0÷49
I
0 = Input disabled
41 = Remote water temperature
probe
H22
0-10vDC live input configu
-
ration
Analogue ST11
/
0
0÷49
I
0 = Input disabled
40 = Plant setpoint decalibration
*H27
Input configuration
Analogue ST5E
/
0
0÷49
I
0 = Input disabled
44 = Mixer probe
Only if Gi accessory
present
*H28
Input configuration
Analogue ST6E
/
0
0÷49
I
0 = Input disabled
39 = Solar storage tank probe
Only if Gi accessory
present
*H29
Input configuration
Analogue ST7E
/
0
0÷49
I
0 = Input disabled
38 = Solar collector probe
Only if Gi accessory
present
H46
Input configuration
Digital ID2
/
0
0÷30
I
0 = Input disabled
3 = Summer/winter mode change
H47
Input configuration
Digital ID3
/
2
0÷30
I
0 = Input disabled
2 = Remote On / Off
H52
Input configuration
Digital ID8
/
0
0÷30
I
0 = Input disabled
28 = DHW thermostat call
H53
Input configuration Digital
ID9
/
0
0÷30
I
0 = Input disabled
21= Hz min/max remote
25= Silenced version
26 = Double set-point call
*H63
Input configuration
Digital ID9E
/
0
0÷30
I
0 = Input disabled
19 = room thermostat
Only if Gi accessory
present
H75
Digital inputs polarity
/
0
0÷255
I
0 = Digital inputs N.A.
1 = ID1 polarity inverted
2 = ID2 polarity inverted
4 = ID3 polarity inverted
8 = ID4 polarity inverted
16 = ID5 polarity inverted
32 = ID6 polarity inverted
64 = ID7 polarity inverted
128 = ID8 polarity inverted
H76
Digital inputs polarity
/
0
0÷255
I
0 = Digital inputs N.A.
1 = ID9 polarity inverted
2 = ID10 polarity inverted
4 = ID1E1 polarity inverted
8 = ID2E1 polarity inverted
16 = ID3E1 polarity inverted
32 = ID4E1 polarity inverted
64 = ID5E1 polarity inverted
128 = ID6E1 polarity inverted
H77
Digital inputs polarity
/
0
0÷255
I
0 = Digital inputs N.A.
1 = ID7E1 polarity inverted
2 = ID8E1 polarity inverted
4 = ID9E1 polarity inverted
8 = ID10E1 polarity inverted
16 = ID1E2 polarity inverted
32 = ID2E2 polarity inverted
64 = ID3E2 polarity inverted
128 = ID4E2 polarity inverted
H81
Output configuration
In DO3 power
/
22
0÷47
I
0 = Output disabled
22 = Plant integration heater
26 = DHW integration heater
H84
Output configuration
In DO6 power
/
6
0÷47
I
0 = Output disabled
6 = DHW valve
H85
Output configuration
In DO7 power
/
25
0÷47
l
0 = Output disabled
25 = Double set-point valve
29 = Boiler enabling
24 = Alarm warning
31 = Summer/winter operating
mode warning
21 = Defrost warning
47 = Machine block warning