Hi
‐
T
Centralized
controller
22
41/44
Bitmap
forcing
icons
Numb
0
0
4095
42/44
Dew
‐
point
temp.
margin
°C
5.0
0.0
50.0
43/44
Min.
staying
time
in
dehumidification
Seconds
300
0
600
44/44
Max.
staying
time
in
dehumidification
Seconds
600
0
1200
Table
4.
Keyboard
menu
service
parameters.
The
fan
coil
service
parameters
are
shown
in
the
following
table:
N.
PARAMETERS
NAME
UNIT
DEFAULT
VALUE
MINIMUM
VALUE
MAXIMUM
VALUE
1/9
Knob
offset
°C
0.0
0.0
15.0
2/9
Hot
start
setpoint
°C
0.0
0.0
50.0
3/9
Too
cool
setpoint
°C
0.0
0.0
50.0
4/9
T
OFF
fan
for
Heat
floor
Minutes
0
0
255
5/9
T
OFF
fan
for
Heat
ceiling
Minutes
0
0
255
6/9
T
OFF
fan
for
Cool
Minutes
0
0
255
7/9
T
ON
fan
for
Heat
floor
Seconds
0
0
255
8/9
T
ON
fan
for
Heat
ceiling
Seconds
0
0
255
9/9
T
ON
fan
for
Cool
Seconds
0
0
255
Table
5.
Fan
coil
service’s
parameters.
To
change
a
the
value
of
a
parameter:
•
entered
in
the
parameter
list
of
chillers,
fan
coils
or
keyboard,
use
the
up
and
down
arrows
to
scroll
through
pages
of
the
parameters,
until
you
find
the
desired
parameter;
•
Press
on
the
currently
set
value;
•
the
present
value
turns
red
to
indicate
that
it
can
be
changed
by
using
the
up
and
down
arrows;
•
Select
the
desired
value
and
press
the
confirmation
tick.
Note:
If
you
press
outside
the
confirmation
area,
it
returns
again
the
previously
value.
3.6.5.3
MANUFACTURER
MENU
To
access
to
the
manufacturer
menu
you
must
set
the
manufacturer
password.
From
here
you
can:
•
access
to
the
manufacturer
parameters
of
the
chiller,
by
pushing
on
"Chiller";
•
access
to
the
manufacturer
parameters
of
the
Hi
‐
T,
by
pushing
on
"Keyboard".
3.6.6
HELP
PAGE
On
the
instructions
are
given
guidance
on
the
meaning
of
the
icons;
in
the
list
that
appears,
for
each
icon
is
indicated
its
function.