5

 

 

 

5.

Installation Method 

         

  In an environment with a lot of dust, metal powder, etc., place the product in a dust-proof case and 

                  take heat radiation measures.

 

         

  Avoid vibrations and impacts as much as possible, since they may cause failures.

 

         

  Avoid use in a place where the ambient temperature exceeds the range of -15

°

C to +55

°

C (13°F to 131°F),   

                where the ambient humidity exceeds the range of 30 to 90% RH, or where condensation occurs, since it   

                affects the lifetime and operation. 

                Install the product on the DIN rail with the slider side facing down.

 

 

        5-1.Installation Method 

                As shown in Figure 3, hang the upper hook on the rear side on the DIN rail, and then push the bottom part to   

install the product. 

 

 

 

5-2.Remove Method 

                As shown in Figure 4, push down the slider using a minus screw-driver, pull out the bottom part from the   

                DIN rail, and then remove the equipment from the DIN rail. 

 

 

 

 

 

 

 

 

 

 

6.

Connection Method 

     ※

Do not install wires (power supply wires, input signal wires, and output signal wires) close to noise   

              sources (switches, relay driving wires, high frequency lines, etc.). 

     ※

Do not bind wires together with those in which noise or surge is mixed, nor install them into the same conduit. 

 

 

 

6-1.Terminal Layout 

                Here is the terminal number layout of the terminal block. 

 

 

 

 

 

 

 

 

 

10 

11 

12 

13 

14 

15 

16 

17 

18 

19 

20 

① 

② 

① 

② 

③ 

Fig.3

DIN rail installation     

Fig.4

DIN rail removal     

Fig.5

Terminal number layout   

Содержание MSC-01

Страница 1: ...er TYPE MSC 01 1 8 18 Norimatsu Higashi Yahatanishi ku Kitakyushu 807 0837 Japan Phone No 8193 691 3731 Fax No 8193 691 3735 http www matsushima m tech com E mail sales matsushima m tech com The operator should read this Instruction Manual carefully and handle the device correctly ...

Страница 2: ...ettings and Functions 10 8 1 Display Unit Setting 11 8 2 Decimal point position Setting 12 8 3 Scaling Setting 13 8 4 No 1 Limit Setting 14 8 5 No 2 Limit Setting 15 8 6 Sensor Failure Relay Setting 16 8 7 Sensor Failure Mode Setting 17 8 8 Damping Setting 18 8 9 Failure Setup In Setting 19 8 10 Analog Output Setting Test 20 8 11 No 1 Relay Output Setting Test 21 8 12 No 2 Relay Output Setting Tes...

Страница 3: ... a correct wiring before applying power source Do not have a shock or strong impact to the equipment Failure to observe this CAUTION may result in equipment damage Be sure to connect necessary terminals grounding etc Remove all wiring to the equipment before doing electrical welding work near the equipment Do not forcedly bend or pull the lead wire also do not use unnecessarily long wire Tighten t...

Страница 4: ...al display Display setting range 99999 99999 Decimal point setting range 0 to 3 digits after the decimal point 00000 00 000 Unit Selection ton m ft Pa kPa MPa bar kgf cm2 psi mg m3 µg m3 m3 h ft3 h t h kg h lb h mL s F mA Blank Non display LED Power Green 1 Limit Yellow 2 Fault Red 1 Sensor failure Red 1 2 8 Installation Method DIN Rail 9 Connection Method M3 Screw terminal Tightening torque 0 5N ...

Страница 5: ...ED Green HART sensor connection terminal Main unit Limit LED Yellow Equipment error LED Red Sensor error LED Red Operation button LCD display screen Fixing screw of terminal M3 Slider Terminal block Fig 2 Names of parts The terminal block can be attached detached independently When energizing the product be sure to confirm that the terminal block is attached DIN Rail ...

Страница 6: ...ng the upper hook on the rear side on the DIN rail and then push the bottom part to install the product 5 2 Remove Method As shown in Figure 4 push down the slider using a minus screw driver pull out the bottom part from the DIN rail and then remove the equipment from the DIN rail 6 Connection Method Do not install wires power supply wires input signal wires and output signal wires close to noise ...

Страница 7: ...Failure Power ON Not in operating COM NC Closed LED turns OFF COM NC Closed LED turns OFF COM NO Closed LED turns OFF COM NO Closed LED turns OFF Power ON In operating COM NO Closed LED turns ON COM NO Closed LED turns ON COM NC Closed LED turns ON COM NC Closed LED turns ON Power OFF COM NC Closed LED turns OFF COM NC Closed LED turns OFF COM NC Closed LED turns OFF COM NC Closed LED turns OFF 1 ...

Страница 8: ...nt error contact Fig 8 Block diagram Voltage output Current output No 2 Limit contact No 1 Limit contact 19 18 17 8 13 16 15 14 6 5 4 Analog Output circuit Isolated circuit Output signal Conditioning circuit Contact Output circuit Relay Relay No 2 Limit LED No 1 Limit LED Microcomputer Current input circuit LED Display Button operation 249Ω NC NO NC NO COM 20 10 9 2 wire Sensor Current input ...

Страница 9: ... Mount the converter Execute the wiring Check the wiring Check the power supply Check that no error code is displayed Adjust using the operation buttons on the front panel OK OK OK Start measurement Y N Y N Y N Fig 9 Start up flow Turn on the power Check that there is no problem with setting values N Check the error code And symptom Inform our persons in charge of the details Return the equipment ...

Страница 10: ...ng value or item Shift of the setting value OK Confirmation of the setting value or item 2 5 0 Operation buttons LCD screen measuring screen Menu display Unit display Measurement value display Scale display The displayed measurement value corresponds to the input signal Error display Item display Menu 0 1 Basicsetting 2 Test 3 Reset 4 Language 5 Deviceinfo OK once Menu screen Fig 10 LCD screen and...

Страница 11: ...ure setup In Setting value Analog output Relay output No 1 Limit No 2 Limit FAULT Sensor failure Parameter reset Factory reset Menu 0 Menu 1 Menu 2 Menu 3 Menu 4 Menu 5 Menu 1 1 Menu 1 2 Menu 1 3 Menu 1 4 Menu 1 5 Menu 1 3 3 Menu 1 1 1 Menu 1 1 2 Menu 1 1 3 Menu 1 2 1 Menu 1 2 2 Menu 1 2 3 Menu 2 1 Menu 2 2 Menu 2 2 1 Menu 2 2 2 Menu 2 2 3 Menu 2 2 4 Menu 3 1 Menu 3 2 Password input is required ES...

Страница 12: ...Display 1 1 1 Displayedunit 2 Decimalpoint 3 Scaling Displayedunit 1 1 1 ton m ft Pa kPa Displayedunit 1 1 1 ton m ft Pa kPa Display 1 1 1 Displayedunit 2 Decimalpoint 3 Scaling 5 0 0 m ESC 3 O K 1 O K 1 For example the display Unit is changed from to m O K 1 Use the button to move the mark to m Return to the previous menu screen Measuring screen Measuring screen Use ESC button to return to the me...

Страница 13: ... it should be changed before the scaling setting 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo Basicsetup 1 1 Display 2 Relayoutput 3 Analogoutput S failuremode 4 Damping 5 Failuresetup In Display 1 1 1 Displayedunit 2 Decimalpoint 3 Scaling Decimalpoint 1 1 2 0000 0 5 0 0 ESC 4 O K 1 O K 1 O K 1 O K 1 1 O K 1 Display 1 1 1 Displayedunit 2 Decimalpoint 3 Scaling The decimal poin...

Страница 14: ...ond 4mA 0 0 20mA Correspond 20mA 100 0 7 5 0 ESC 4 O K 1 O K 1 O K 1 O K 1 2 O K 1 Measuring screen Measuring screen Use ESC button to return to the measuring screen Display 1 1 1 Displayedunit 2 Decimalpoint 3 Scaling For example the 4mA display is changed from 0 0 to 50 0 Scaling 1 1 3 4mA Correspond 4mA 0 0 20mA Correspond 20mA 100 0 Scaling 1 1 3 4mA Correspond 4mA 50 0 20mA Correspond 20mA 10...

Страница 15: ... 4 Damping 5 Failuresetup In 5 0 0 O K 1 O K 1 1 ESC 4 Measuring screen O K 1 Use ESC button to return to the measuring screen Relayoutput 1 2 1 No 1Limit 2 No 2Limit 3 S failurerelay Ablinking indicates the item to be set Use and buttons to change the value to 80 0 O K 1 Setting is saved Measuring screen O K 1 No 1Limit 1 2 1 ONpoint 95 0 OFFpoint 85 0 For example the ON point is changed from 95 ...

Страница 16: ... 4 Measuring screen O K 1 Use ESC button to return to the measuring screen Relayoutput 1 2 1 No 1Limit 2 No 2Limit 3 S failurerelay Ablinking indicates the item to be set Use and buttons to change the value to 94 0 O K 1 Setting is saved Measuring screen 1 No 2Limit 1 2 2 ONpoint 95 0 OFFpoint 85 0 For example the ON point is changed from 85 0 to 94 0 1 Basicsetup 1 1 Display 2 Relayoutput 3 Analo...

Страница 17: ...ailuresetup In 5 0 0 O K 1 O K 1 1 ESC 4 Measuring screen O K 1 Use ESC button to return to the measuring screen Relayoutput 1 2 1 No 1Limit 2 No 2Limit 3 S failurerelay Setting is saved Measuring screen 2 S failurerelay 1 2 3 Relayaction Execution Non Execution For example the setting is changed to Non Execution 1 Basicsetup 1 1 Display 2 Relayoutput 3 Analogoutput S failuremode 4 Damping 5 Failu...

Страница 18: ...elayoutput 3 Analogoutput S failuremode 4 Damping 5 Failuresetup In 5 0 0 O K 1 O K 1 2 ESC 4 Measuring screen O K 1 Use ESC button to return to the measuring screen S failuremode out 1 3 1 Rawmode 2 Holdmode 3 Settingvalue Rawmode Setting is saved Measuring screen 2 Settingvalue 1 3 3 Setvalue 3 6 mA 0 90 V For example Arbitrary setting mode is selected and the setting is changed to 22mA Basicset...

Страница 19: ...evel 100 Time Normal output level 63 2 Fig 12 Time constant and primary delay element 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo Basicsetup 1 1 Display 2 Relayoutput 3 Analogoutput S failuremode 4 Damping 5 Failuresetup In 5 0 0 O K 1 O K 1 3 ESC 3 Measuring screen O K 1 Use ESC button to return to the measuring screen Damping 1 4 Dampingtime 000s Setting is saved Measuring s...

Страница 20: ...setup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 O K 1 Basicsetup 1 1 Display 2 Relayoutput 3 Analogoutput S failuremode 4 Damping 5 Failuresetup In Measuring screen 4 ESC 3 O K 1 Setting is saved Use ESC button to return to the measuring screen Failuresetup In 1 5 Upper 20 0 24mA 20 5mA Lower 3 0 4 0mA 3 8mA Failuresetup In 1 5 Upper 20 0 24mA 22 0mA Lower 3 0 4 0mA 3 8mA Ablinking indicates th...

Страница 21: ...utton to return to the measuring screen ESC 1 5 0 0 Measuring screen For example a 12mA 3V output is simulated Ablinking indicates the item to be set O K 1 Use and buttons to change the value to 12 0mA 5 0 0 Analogoutputtest 2 1 Outputvalue 3 0mA 0 75V OK Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Test 2 1 Analogoutput 2 Relayoutput Analogoutputtest 2 1 Outputvalue 3 0mA 0 75...

Страница 22: ... 2 1 Outputmode No 1Limit OK Running Relay Test 2 2 1 Outputmode No 1Limit OK O K 1 ESC 1 Use ESC button to return to the measuring screen 5 0 0 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Test 2 1 Analogoutput 2 Relayoutput Test 2 1 Analogoutput 2 Relayoutput Relayoutput Test 2 2 1 No 1Limit 2 No 2Limit 3 FAULT 4 Sensorfailure Relay Test 2 2 1 Outputmode No 1Limit OK O ...

Страница 23: ...g Relay Test 2 2 2 Outputmode No 2Limit OK O K 1 ESC 1 Use ESC button to return to the measuring screen 5 0 0 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Test 2 1 Analogoutput 2 Relayoutput Test 2 1 Analogoutput 2 Relayoutput Relayoutput Test 2 2 1 No 1Limit 2 No 2Limit 3 FAULT 4 Sensorfailure Relay Test 2 2 2 Outputmode No 2Limit OK O K 1 O K 1 Simulative output is star...

Страница 24: ...tputmode FAULT OK O K 1 ESC 1 Use ESC button to return to the measuring screen 5 0 0 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Test 2 1 Analogoutput 2 Relayoutput Test 2 1 Analogoutput 2 Relayoutput Relayoutput Test 2 2 1 No 1Limit 2 No 2Limit 3 FAULT 4 Sensorfailure Relay Test 2 2 3 Outputmode FAULT OK O K 1 O K 1 Simulative output is started Measuring screen For exam...

Страница 25: ...ing Relay Test 2 2 4 Outputmode Sensorfailure OK O K 1 ESC 1 Use ESC button to return to the measuring screen 5 0 0 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Test 2 1 Analogoutput 2 Relayoutput Test 2 1 Analogoutput 2 Relayoutput Relayoutput Test 2 2 1 No 1Limit 2 No 2Limit 3 FAULT 4 Sensorfailure Relay Test 2 2 4 Outputmode Sensorfailure OK O K 1 O K 1 Simulative outp...

Страница 26: ... after completion ESC 3 Parameterreset 3 1 Parameterreset OK Use ESC button to return to the measuring screen 5 0 0 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Reset 3 1 Parameterreset 2 Factoryreset Parameterreset 3 1 Parameterreset OK Parameterreset 3 1 Parameterreset OK Resetnow Parameterreset 3 1 Parameterreset OK Resetnow Running O K 1 Reset is performed Measuring s...

Страница 27: ...xecute a reset The password screen appears O K 1 Use and buttons to enter the password 5 0 0 Factoryreset 3 2 Factoryreset OK Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Reset 3 1 Parameterreset 2 Factoryreset Reset 3 1 Parameterreset 2 Factoryreset Password 3 0 Pleaseenterthe 6 digitpassword 000000 Password 3 0 Pleaseenterthe 6 digitpassword 100001 Factoryreset 3 2 Factoryres...

Страница 28: ...0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 3 Measuring screen O K 1 ESC 2 ゲンゴセンタク 4 ヒョウジゲンゴ ニホンゴ エイゴ Use ESC button to return to the measuring screen 5 0 0 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Language 4 Displaylanguage Japanese English Measuring screen For example the setting is changed to Japanese Setting is saved ...

Страница 29: ...he equipment Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 4 Measuring screen ESC 2 Use ESC button to return to the measuring screen 5 0 0 Menu 0 1 Basicsetup 2 Test 3 Reset 4 Language 5 Deviceinfo O K 1 Deviceinfo 5 Revision 00 00 Measuring screen 5 0 0 ...

Страница 30: ...tion point of the No 2 limit relay by value Range 0 0 100 0 ON 95 0 OFF 85 0 6 Sensor failure relay Menu 1 2 3 Select and set the operation of the sensor error relay at an error signal input to Execution or Non Execution Execution 7 Sensor failure mode Menu 1 3 Select the output signal mode at an error signal input Raw mode Hold mode Setting value Raw mode Setting value Menu 1 3 3 Select the outpu...

Страница 31: ... supplied supply it to the sensor If the signal is normally output from the sensor check the input signal If the input signal is 0 mA check the wiring line 3 ERROR 0001 Equipment error The CPU recognizes abnormal resets due to intermittent noises surges etc Check the wiring line If this error code disappears after taking measures against a suspicious wiring line using the noise filter etc take app...

Отзывы: