5
-
5.
Installation Method
※
In an environment with a lot of dust, metal powder, etc., place the product in a dust-proof case and
take heat radiation measures.
※
Avoid vibrations and impacts as much as possible, since they may cause failures.
※
Avoid use in a place where the ambient temperature exceeds the range of -15
°
C to +55
°
C (13°F to 131°F),
where the ambient humidity exceeds the range of 30 to 90% RH, or where condensation occurs, since it
affects the lifetime and operation.
Install the product on the DIN rail with the slider side facing down.
5-1.Installation Method
As shown in Figure 3, hang the upper hook on the rear side on the DIN rail, and then push the bottom part to
install the product.
5-2.Remove Method
As shown in Figure 4, push down the slider using a minus screw-driver, pull out the bottom part from the
DIN rail, and then remove the equipment from the DIN rail.
6.
Connection Method
※
Do not install wires (power supply wires, input signal wires, and output signal wires) close to noise
sources (switches, relay driving wires, high frequency lines, etc.).
※
Do not bind wires together with those in which noise or surge is mixed, nor install them into the same conduit.
6-1.Terminal Layout
Here is the terminal number layout of the terminal block.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
①
②
①
②
③
Fig.3
.
DIN rail installation
Fig.4
.
DIN rail removal
Fig.5
.
Terminal number layout