18
4-1 Cancel power outage protection (LN)
Power outage protection is installed in standard (see.3-8-c), but this function can be cancelled with this
option, which enable you turn on and off power supply by AC input on and off.
4-2 RMS display of output voltage and output current (LPr)
The average output voltage and output current values are display in standard model, but those rms values
can be displayed with this option.
4-3 Master slave option (LMs)
Output current can be increased by master slave control with LMs option among the same model. LMs
option is available only at same lot.
Master slave connection cable is added to the accessory. (1pcs/1set)
(see “5 LMs option Instruction Manual” for use method.)
4-4 Floating ground (LF)
Power supply can be floated up to 200Vdc between chassis and output terminal
4-5 Output voltage limit (LVc)
Variable from 0 to approx 110% with Output voltage limiter in front panel.
Set the following procedure.
1.
Turn off the power, wait one minute, and open the load.
2.
Turn off the bias switch, turn off the output switch, and set to the CV mode.
3.
Input the power, turn on the output switch, and input DC12V to the Vcon-in terminal.
Present limit voltage is output.
(Factory: about 110% of the rated output voltage)
4.
Set to the desired value by turning the limiter.
*Cautions for use of LMs option.
To make the function move right, when using by Master Slave, Please be sure to use after OVP
volume of slave set to counterclockwise maximum.
4
Optional Features
4 Optional Features