By default, 2 of the inputs are reserved for the door
contact
and the request to exit. The door contact is assigned to
input
Door STS IN+ at terminals 29 & 30, and the associated
request-to-exit detector to input Exit SW at terminals 19 &
20. It is advisable to use these pre-assigned inputs for the
relevant application as it would make the configuring and
servicing of the site simpler.
External Reader Wiring
The COSEC DOOR supports a maximum of 3 readers (2
internal and one External). The External reader port supports
a single reader with Wiegand / Serial interface. To fully utilize
Wiegand reader port, a shielded 11-conductor cable (18-22
AWG) is required. The maximum recommended length of
wiring is 500 feet per reader.
Connecting the Wiegand HID R10/RW100 Prox Reader:
The HID R10 and RW100 readers come with the Pigtail
option which has color coded conductors as specified in the
following connection diagram.
HID
R10
Reader
Red
Black
Green
White
Orange
Brown
Yellow
Blue
Reader Power
Ground
D0
D1
Green LED
Red LED
Beeper
Hold
Data Return
In the absence of the pigtail option on the RW100 reader