Door closer:
A standard hydraulic door closer is almost
mandatory to insure that the door closes automatically after
an entry or exit and to prevent "door open too long" or "door
left open" alarms.
Door contact:
When the door is closed, the access
controller supervises the door contact and will report a "door
forced open" alarm if the door is opened without the use of a
card. When the door is opened for a valid credential, the
condition of the door contact is still supervised but no alarms
are generated.
Step 5:
Connecting the Door Locking Device
The lock NO, COM, NC and +12VDC terminals are located
at terminal nos. 21, through to 24 on the top right of the
COSEC DOOR terminal strip. The locking device output is
controlled by the software according to preset parameters for
allowing access or unlocking doors according to schedules
and access levels. The NO or NC output can operate DC
powered locking devices such as electromechanical strikes
and Magnetic Locks. The maximum permitted current is 500
mA @ 12VDC per output. For locks of higher capacity an
external 12 / 24 VDC power supply has to be used based on
the technical specifications of the magnetic lock.
T2
21
COM
NC
NO
0V
+12V
Door Magnet
0V