background image

8

No alarms

Press OK for alarm test

ALARMS

Alarm: High level

Alarm: Pump 1 fault

Press ‘OK’ to reset alarms

ALARMS

Alarms screen with no alarms

Alarm screen with multiple alarms

1.3 Input States

The Input States screen simply gives a readout of all controller inputs, including the operation mode DIP switches and 

current loop. If the current loop is disabled it will be mentioned on the screen, otherwise both the current and the level (or 

pressure, depending on the configuration) will be reported. There are no user actions on the screen.

Input 1: 

 Input 2:

Input 2: 

 Input 4:

Fault inputs: 1: 

2:

DIP switches: 000000

Loop mode disabled

INPUT STATES

Input 1: 

 Input 2:

Input 2: 

 Input 4:

Fault inputs: 1: 

2:

DIP switches: 000000

Current: 10.3mA

Level:  

1.9 metres

INPUT STATES

Input states without current loop

Input states with current loop

1.4 Logged Data

The logged data screen displays a list of all logged data values from the controller. The up and down buttons are used to 

scroll through all of the values – a small up or down arrow will appear on the top or bottom of the left side of the screen 

while there is more data available in that direction.

Pump 1 run time

Pump 2 run time

Pump 1 start count

12 hrs

11 hrs

377

LOGGED DATA

Logged data screen

1.5 Reset Logged Data

The Reset Logged Data screen allows the user to selectively reset logged data values to zero. There are four options 

given: reset all, reset all excluding pump run hours, reset pump 1 run hours and reset pump 2 run hours. The up and 

down buttons are used to select one of these options, which is then selected using the OK button.

Reset all logged

Reset excluding run hours

Reset pump 1 run hours

RESET LOGGED DATA

Reset all logged

Press ‘OK’ to confirm

Press      to cancel

RESET LOGGED DATA

Logged data reset selection screen

Logged data reset confirmation screen

A confirmation screen is presented before the data is actually reset: the OK button is pressed to confirm resetting the 

selected logged data values or one of the left or right arrows are pressed to cancel.

Note that before this screen can be accessed a PIN number has to be entered (as discussed in section 5.6).

If any alarms are active the alarm screen will appear as shown on the right image above and list up to 5 of the active 

alarms. When the alarm triggers the controller will activate its siren and strobe outputs. The alarm LED on the HMI will 

also flash. The siren will silence after 5 minutes of continual sounding, however it can be immediately silenced by pressing 

the mute button on the HMI.

Most alarms in the controller are latching, that is the alarm remains active even if the alarm condition has

passed / corrected. In order to reset the alarm the OK button needs to be pressed when the Alarms screen is selected.

Содержание FPC-36040

Страница 1: ...PUMP 1 PUMP 2 AUTO AUTO Running Idle System OK No Alarms DUAL PUMP CONTROL MAIN ISOLATOR P U M P C O N T R O L MODEL FPC 36040 OWNER S OPERATION MANUAL Advanced Dual Pump Controller Installation and O...

Страница 2: ...olated Power supply must be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Ins...

Страница 3: ...UMP 1 P2 P3 P1 COMMON FAULT BMS VOLT FREE COMMON INPUT SHIELDED TRANSDUCER CABLE HYDROSTATIC LEVEL TRANSDUCER SHIELD EARTH 4 20mA Level Transducer 12Vdc T1 T2 Pump 1 Pump 2 THERMAL SWITCH 415Vac MAINS...

Страница 4: ...e to run until the Stop Float Contacts open Input functions are as follows Mode B Standard Configuration plus Low Level Alarm As per Mode A except it has an active Low Level input The Low Level input...

Страница 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Страница 6: ...ton on the Keypad continuously for a period of 5 seconds the Strobe Siren and indicator Lights will be powered up for inspection Fault Reset To reset all faults on the controller press and old the Mut...

Страница 7: ...Edit configuration settings 9 System information and serial number Lines marked with an asterisk require entry of a PIN number for access Note that many of the menu screens feature a prompt along the...

Страница 8: ...ged Data screen allows the user to selectively reset logged data values to zero There are four options given reset all reset all excluding pump run hours reset pump 1 run hours and reset pump 2 run ho...

Страница 9: ...the value The new value can be committed to the controller by pressing OK otherwise the operation can be canceled by pressing one of the left or right buttons As with the Logged Data Reset this scree...

Страница 10: ...en and the opportunity to enter the PIN will again be presented 1 9 4 20mA Display Modes When the APC6 current loop mode is enabled the HMI is able to report the current 4 20mA reading this is shown o...

Страница 11: ...d Periods as low as 250ms can be achieved but there can be no guarantee as to the HMI s ability to respond at this rate particularly with write commands Certain Modbus operations require the HMI to in...

Страница 12: ...lay R 3 0 255 Seconds 40 Pressure mode min run time R 3 0 255 Seconds 41 Pressure mode alarm delay R 3 0 255 Seconds 42 Alternate high level alarm delay R 3 43 Single pump enable R 3 0 Off 1 On 44 Inh...

Страница 13: ...t R 1 3 0 Off 1 On 0x10 18 Low level fault 0x10 19 Pump 1 fault 0x10 20 Pump 2 fault 0x10 21 Low pressure fault 0x10 22 Pump 1 prime loss 0x10 23 Pump 2 prime loss 0x10 24 Inhibit fault 0x18 0x1f 25 3...

Страница 14: ...Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 12Vac 0Vac A1 A2 Contactor 18A 240Vac C1 A1 A2 Contactor 18A 240Vac C2 95 96 NC Contact TOL1 95 96 NC Contact TOL2 Input 1 Low Level Input...

Страница 15: ...Isolator 3P 32A I2 Circuit Breaker 2A CB1 240V 240N 12V 0V Transformer 12Vac T1 12Vac 0Vac A1 A2 Contactor 18A 240Vac C1 A1 A2 Contactor 18A 240Vac C2 95 96 NC Contact TOL1 95 96 NC Contact TOL2 Stro...

Страница 16: ...hout notice PUMP 1 PUMP 2 AUTO AUTO Running Idle System OK No Alarms DUAL PUMP CONTROL The HMI AT A GLANCE OK MUTE A quick reference to the controller s HMI and Indicator functions and meanings Scroll...

Отзывы: