The basic logic on which a High or Low Level Alarm is determined, is set out in the Table below:

If there is a Low Level Alarm, then both Pumps will be locked out until the alarm is manually reset. This lockout will only be 

over ridden upon a High Level condition where both the Pump Start and High level inputs are closed.

Note that after a High level is triggered, the pumps will both run until the Pump Start and Stop inputs are opened.

is running, the Prime Loss input opens, for a continuous 2 minute period, a fault is immediately triggered for that pump 

and duty alternates. Input functions are as follows:

Duty Pump:  

Lead Pump

Standby Pump: 

Lag Pump

Input functions are as follows:

Typical Operation for Mode D:

 

Pressure drops to 400kPa: Lead (for this cycle) Pump cuts in.

 

Pressure increases and Pump cuts out.

 

Cycle continues with duty  alternating between the two pumps.

 

If pressure continues to drop to

   

350kPa, the Lag Pump will cut in and remain running until the

Then duty alternates.

 

No faults are logged against the Lead Pump if the Lag Pump starts.

 

The controller has inbuilt timers for “Delayed” Start and Stop to obviate pump chatter. Upon Input 2 contact closure, 

the pump will not start (delay start) for 1 second and will not stop (minimum run time) for 10 seconds (or 11 sec-

onds from close of Input contacts). This “run on” occurs even if Lead Pressure switch opens circuit during this initial 

period. If however run time exceeds 11 seconds, the pump will stop immediately upon “Open Circuit” occurring.

 

If the Lead Pressure Switch input closes circuit as well as he Low Pressure Switch input, both pumps will be turned 

on and the Low Pressure Timer will begin counting. If this condition exists for a period of 60 seconds, then both 

pumps are shut down and the system signals a level alarm. This would be typical of a Loss of Prime, or Burst main 

situation.

P

Prime Loss functions as per mode Mode C.

ressure switches are normally Closed and Opened on High Pressure.

Input 2

Pump Stop

Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed
Open/Closed

Input 1

Low Level

Closed
Closed
Closed
Closed

Open
Open
Open
Open

Input 3

Pump Start

Open

Closed
Closed

Open
Open

Closed

Open

Closed

Input 4

High Level

Open
Open

Closed
Closed

Open
Open

Closed
Closed

Pump

State

Off
On

Both On
Both On

Off
Off
Off

Both On

Alarm

-
-

High Level (after Timeout)
High Level (after Timeout)

-

Low Level
Low Level

High Level (after Timeout)

Input         Function

Input 1      Prime Loss
Input 2      Pump Stop
Input 3      Pump Start
Input 4      High Level

Input

Function

Input 1      Prime Loss (BRIDGE IF NOT REQUIRED)
Input 2      Lead Pump Pressure Switch (set at say 400kPa)
Input 3      Lag Pump Pressure Switch (set at say 350kPa)
Input 4      Low Pressure Switch (set at say 200kPa)

 Lead Pressure Switch

 

opens circuit. 

Содержание FPC-32020

Страница 1: ...ating Instructions P U M P C O N T R O L OWNER S OPERATION MANUAL MODEL FPC 32020 MAIN ISOLATOR OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Cont...

Страница 2: ...nctional reliable and user friendly operation Please read this manual prior to installation and operation of the controller OPERATION 4 Operations Features WARNING All electrical connections must be c...

Страница 3: ...OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Controller DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY PUMP 1 240Vac MAINS POWER...

Страница 4: ...active Low Level input The Low Level input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run both pumps Input funct...

Страница 5: ...rom close of Input contacts This run on occurs even if Lead Pressure switch opens circuit during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon Open Cir...

Страница 6: ...ll be powered up for inspection Fault Reset To reset all faults on the controller press and old the Mute Reset button on the Keypad continuously for a period of 3 seconds until an acknowledgement beep...

Страница 7: ...2 AUX C NO R1 BUZZER TRANSFORMER 32amp 2 POLE PUMP 1 ISOLATOR 32amp 2 POLE PUMP 2 ISOLATOR 12Vac 240Vac INPUT 2 LEAD INPUT 3 LAG INPUT 4 LOW 12Vdc 12Vdc 1 L O T 2 L O T N E PUMP 1 1 R O T C A T N O C...

Страница 8: ...resent PUMP ON ON STEADY A pump fault overload has occurred ON STEADY Pump switched on to run If selected the LED indicator will confirm if on the pump is set to Manual Pumping Mode MAN If selected th...

Отзывы: