Matelec FPC-32020 Скачать руководство пользователя страница 3

3

 

1.  Controller enclosure must be 
     mounted in a vertical position.
2.  Ensure mounting method 
     does not compromise enclosure 
     weather proof rating.
3.  Ensure access to main isolator 
     is not restricted.
4.  Ensure cables/conduits 
     entering the panel have 
     mechanical protection and that 
     the penetrations are 
     sealed and do not compromise 
     the weather proof rating of the 
     enclosure.

MOUNTING

FRONT VIEW

CONNECTION

INSTALLATION

Top

Bottom

Mounting 

Frame/

Wall

SIDE VIEW

Top

Bottom

MAIN ISOLATOR

OFF

  ON 

PUMP ON
FAULT

PUMP ON
FAULT

SYSTEM

TEST

MAINS WATER

RAIN WATER

SYSTEM FAULT

Rain / Mains Water Controller

 

DANGER - HIGH VOLTAGE

DO NOT REMOVE COVER.  AUTHORIZED PERSONS ONLY

PUMP 1

240Vac

MAINS POWER

SUPPLY

BLUE NOT

REQUIRED

COMMON

N/O  C

LOSE  ON  RISE

COMMON

N/O  C

LOSE  ON  RISE

COMMON

N/O  C

LOSE  ON  RISE

COMMON

N/O  C

LOSE  ON  RISE

PUMP 2

SUPPLY

Neu

tr

al

240Vac

PUM

P

 1 E

art

h

Active

Neutral

Neutral

Active

Ear

th

A

ctiv

e

PUMP 1

INPUT SWITCHES

SOLENOID

12Vdc Connections

Input 2

Lead

Press.

Input 4

Low

Press.

Low

Float
Level

Input 3

Lag

Press.

+

-

Valve

PUM

P

 2 E

art

h

PUMP 2

LOW

LEVEL

LOW

Pressure

Switch

LAG

Pressure

Switch

LEAD

Pressure

Switch

®

Australia

PULSE LATCHING

12Vdc SOLENOID

VALVE

Содержание FPC-32020

Страница 1: ...ating Instructions P U M P C O N T R O L OWNER S OPERATION MANUAL MODEL FPC 32020 MAIN ISOLATOR OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Cont...

Страница 2: ...nctional reliable and user friendly operation Please read this manual prior to installation and operation of the controller OPERATION 4 Operations Features WARNING All electrical connections must be c...

Страница 3: ...OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Controller DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY PUMP 1 240Vac MAINS POWER...

Страница 4: ...active Low Level input The Low Level input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run both pumps Input funct...

Страница 5: ...rom close of Input contacts This run on occurs even if Lead Pressure switch opens circuit during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon Open Cir...

Страница 6: ...ll be powered up for inspection Fault Reset To reset all faults on the controller press and old the Mute Reset button on the Keypad continuously for a period of 3 seconds until an acknowledgement beep...

Страница 7: ...2 AUX C NO R1 BUZZER TRANSFORMER 32amp 2 POLE PUMP 1 ISOLATOR 32amp 2 POLE PUMP 2 ISOLATOR 12Vac 240Vac INPUT 2 LEAD INPUT 3 LAG INPUT 4 LOW 12Vdc 12Vdc 1 L O T 2 L O T N E PUMP 1 1 R O T C A T N O C...

Страница 8: ...resent PUMP ON ON STEADY A pump fault overload has occurred ON STEADY Pump switched on to run If selected the LED indicator will confirm if on the pump is set to Manual Pumping Mode MAN If selected th...

Отзывы: