OPERATION

4

This controller can perform control functions for most Dual Pump  pumping applications. It is more than likely that the con-

There are 6 DIP switches located on the lower side of the control module, which allows for selecting “mode” and “feature” 

options, as per the following table:

Start/Stop/High Level operation. When the Pump Start input is closed contact (triggered), the Duty Pump will be turned on. 

The pump will remain on until both the Pump Start and Pump Stop Inputs have turned off (Open Circuited). Upon High Level, 

both pumps will run until the Pump Stop Input turns off.

In addition to this, there is a maximum idle timer, which will trigger a Pump Start condition, if either pump has not run for 4 

hours, and the Stop Float Contacts are closed. The pump will continue to run until the Stop Float Contacts open. Input func-

tions are as follows:

As per Mode A, except it has an active Low Level input. The Low Level input must be closed, for Pump Start and Pump Stop 

inputs to function. The High Level input however, will still override the Low Level and run both pumps. Input functions are as 

follows:

 

      

Position

Off/Off

Off/On

On/Off

On/On

Off

On

Off

On

Off

On

Off

On

Function

Mode A:

Mode B:

Mode C:

Mode D:

Operating Pump alternates each time a pump start is triggered, or after 30 minutes continuous 

running.

Operating Pump alternates after 6 hours continuous running.

Anti-seize Timer disabled

Anti-seize Timer 6 seconds every 7 days enabled

When placed in Manual Mode, pump remains in Manual Mode

When placed in Manual Mode after 5 minutes the pump will revert to Auto

High Level Alarm automatically resets upon open circuit of high level input. High Level alarm 

has 15 minute delay.

High Level Alarm can only be reset manually. High Level Alarm has 5 minute delay. 

DIP Switch

1/2

3

4

5

6

Input        Function

Input 1     Not used

Input 2     Pump Stop

Input 3     Pump Start

Input 4     High Level

Input         Function

Input 1      Low Level

Input 2      Pump Stop

Input 3      Pump Start

Input 4      High Level

Содержание FPC-32020

Страница 1: ...ating Instructions P U M P C O N T R O L OWNER S OPERATION MANUAL MODEL FPC 32020 MAIN ISOLATOR OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Cont...

Страница 2: ...nctional reliable and user friendly operation Please read this manual prior to installation and operation of the controller OPERATION 4 Operations Features WARNING All electrical connections must be c...

Страница 3: ...OFF ON PUMP ON FAULT PUMP ON FAULT SYSTEM TEST MAINS WATER RAIN WATER SYSTEM FAULT Rain Mains Water Controller DANGER HIGH VOLTAGE DO NOT REMOVE COVER AUTHORIZED PERSONS ONLY PUMP 1 240Vac MAINS POWER...

Страница 4: ...active Low Level input The Low Level input must be closed for Pump Start and Pump Stop inputs to function The High Level input however will still override the Low Level and run both pumps Input funct...

Страница 5: ...rom close of Input contacts This run on occurs even if Lead Pressure switch opens circuit during this initial period If however run time exceeds 11 seconds the pump will stop immediately upon Open Cir...

Страница 6: ...ll be powered up for inspection Fault Reset To reset all faults on the controller press and old the Mute Reset button on the Keypad continuously for a period of 3 seconds until an acknowledgement beep...

Страница 7: ...2 AUX C NO R1 BUZZER TRANSFORMER 32amp 2 POLE PUMP 1 ISOLATOR 32amp 2 POLE PUMP 2 ISOLATOR 12Vac 240Vac INPUT 2 LEAD INPUT 3 LAG INPUT 4 LOW 12Vdc 12Vdc 1 L O T 2 L O T N E PUMP 1 1 R O T C A T N O C...

Страница 8: ...resent PUMP ON ON STEADY A pump fault overload has occurred ON STEADY Pump switched on to run If selected the LED indicator will confirm if on the pump is set to Manual Pumping Mode MAN If selected th...

Отзывы: