Your  Dual  Pump  Controller  reflects  the  superior  quality  and  attention  to  detail  in  design,  engineering  and

manufacturing that has distinguished MATelec Products for decades. The controller incorporates the very latest in 

micro-processor technology, ensuring you, the owner/operator, of many years of functional, reliable and ‘user friendly’ 

operation.

Please read this manual prior to installation and operation of the controller.

WELCOME TO DUAL PUMP CONTROL

CONTENTS

SAFETY

• 

Prior to Installation, ensure power supply is isolated.

• 

Power supply must be Circuit Breaker Protected. (Qualified Electrician to determine appropriate amp rating.)

• 

Electrical connection to the panel must be carried out in accordance with ‘Connection Instructions’, see page 3.

• 

Addition or modifications to the control panel are not permitted and will void warranty.

• 

The controller is not intended for use by children or infirm persons without supervision.

• 

Repairs to the Controller must only be carried out by a suitably qualified Electrician

WARNING: All electrical connections must be carried out by a suitably qualified and

registered electrician

SAFETY 

 

                2 HRH-5 DATA SHEET                     7

INSTALLATION 

                3 CIRCUIT DIAGRAM                     10

Mounting
Connection 

NOTES                                      11

AT A GLANCE                            12

Indicators

GETTING STARTED                 4

Push Buttons

Operations
Features

Содержание FPC-30020-CON

Страница 1: ...PUMP ON FAULT PUMP ON FAULT MAIN ISOLATOR P U M P C O N T R O L OWNER S OPERATION MANUAL Dual Pump Controller Installation and Operating Instructions MODEL FPC 30020 CON VER 1 0...

Страница 2: ...st be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 A...

Страница 3: ...not compromise the weather proof rating of the enclosure Note Controller must be earthed and all electrical connections must be carried out by a suitably qualified Electrician For Single Working Level...

Страница 4: ...minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed conta...

Страница 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Страница 6: ...Mode Timeout With DIP Switch 5 set to On the pump will only remain in Manual Mode for 5 minutes after which time it automatically reverts to Auto High Level Alarm Reset The controller will also use th...

Страница 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100k Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separa...

Страница 8: ...tance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts C...

Страница 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case...

Страница 10: ...10 CIRCUIT DIAGRAM...

Страница 11: ...11 NOTES...

Страница 12: ...level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears...