Dual Pump Controller Installation

and Operating Instructions

MODEL: FPC-300

2

0-CON

DOC: FPC-30040-CON  

 

 

 

 

 

                  VER 1.0

Содержание FPC-30020-CON

Страница 1: ...PUMP ON FAULT PUMP ON FAULT MAIN ISOLATOR P U M P C O N T R O L OWNER S OPERATION MANUAL Dual Pump Controller Installation and Operating Instructions MODEL FPC 30020 CON VER 1 0...

Страница 2: ...st be Circuit Breaker Protected Qualified Electrician to determine appropriate amp rating Electrical connection to the panel must be carried out in accordance with Connection Instructions see page 3 A...

Страница 3: ...not compromise the weather proof rating of the enclosure Note Controller must be earthed and all electrical connections must be carried out by a suitably qualified Electrician For Single Working Level...

Страница 4: ...minute delay On High Level Alarm can only be reset manually High Level Alarm has 5 minute delay Mode A Standard Configuration Start Stop High Level operation When the Pump Start input is closed conta...

Страница 5: ...n Input 1 contact closure the pump will not start delay start for 1 second and will not stop minimum run time for 10 seconds or 11 seconds from close of Input contacts This run on occurs even if Lead...

Страница 6: ...Mode Timeout With DIP Switch 5 set to On the pump will only remain in Manual Mode for 5 minutes after which time it automatically reverts to Auto High Level Alarm Reset The controller will also use th...

Страница 7: ...ction PUMP UP Function PUMP DOWN Sensitivity adjustable by a potentiometer 5 100k Measuring frequency 10Hz prevents polarization of liquid and raising oxidation of measuring probes Galvanically separa...

Страница 8: ...tance Voltage n electrodes Current in probes Time response Max capacity of probe cable Time delay t Time delay after switching on t1 Accuracy Accuracy in setting mechanical Output Number of contacts C...

Страница 9: ...se a tank made of a conductive material you can use it as probe C In case you require monitoring of one level only it is neccessary to connect inputs H and D and connect them to one probe in this case...

Страница 10: ...10 CIRCUIT DIAGRAM...

Страница 11: ...11 NOTES...

Страница 12: ...level alarm is present ON STEADY Pump switched on to run ON STEADY A pump fault overload has occurred FLASHING A prime loss fault has occurred Silences the siren and if held down for 3 seconds clears...