Mastip METICOM TM10 Скачать руководство пользователя страница 9

 Page |  - 9 -  

© Copyright Mastip Technology Limited. Information subject to alteration. V3.51a   www.mastip.com

 

  Temperature Controller 

 METICOM TM10 Module 

value are displayed.

 

2) Look over the parameters: Press SET to shift the parameters.
3) Exit the parameter mode with saving: PressSET>3sec.
If there’s any operation in 60sec., the controller will exit the parameter mode without saving automatically.

Alarm mode:

The controller displays the corresponding faulty code.

4. Control modes (selected by MODE key)

Normal (Auto PID) mode:
This type of control is a “closed-loop” system and requires a thermocouple feedback signal.

The controller’s PV displays present temperature value, and SV displays setting temperature value (power output % and
load current can be selected by DISP key).

The controller uses a PID algorithm to determine the required output power to hold the present temperature value equal
to setting temperature value.

Standby mode:
This type of control operates similar to auto mode. It is a “closed-loop” system and requires a thermocouple feedback
signal.
The controller’s PV displays present temperature value, and SV displays standby temperature value (70% of setting

temperature value; power output % and load current can be selected by DISP key).

The controller uses a PID algorithm to determine the required output power to hold the present temperature value equal
to standby temperature value.
Standby mode can be activated by an external signal (when Std’s number in the hundreds place ≠0).

Manual mode:
This type of control is an “open-loop” system and requires no thermocouple feedback signal.
It can be used when thermocouple is failed or without thermocouple in system.
The controller’s PV displays present temperature value, and SV displays power output percent (load current can be
selected).

Note: The output percent initial value, see parameter “A-n” and “nSL”.

The controller regulates output power according to the setting. The setting can be adjusted by pressing 

.

AT (PID Auto Tune) function:
This function is for getting the optimal PID value for a system.
It is a “closed-loop” system and requires a thermocouple feedback signal.
Generally, AT function only needs to be executed when PID factory setting cannot meet the system requirements.
After finished auto tuning, the optimal PID value is saved, and the controller returns to normal (auto PID) mode.
When SuP ≤ 900, the controller executes auto-tune function by making 80% of setting value as target.
When SuP

900, the controller executes auto-tune function by making setting value as target.

5. Soft start (dehumidify) function

To avoid humidity making  the heater burn out  prematurely, the soft start function heats the system  slowly to remove
excess moisture from the heater.
During soft start, the output power step’s up slowly from 0% to the setting (Manual control) or will make the temperature
rise to 100°C (212°F) slowly and hold it (Auto control).
When soft start time is over, the controller will return to auto or manual control mode according to the setting.
Soft start condition:
a) The soft start function is on (parameter Sot=1~10).
b) The process temperature is less than 100°C (212°F).
Terminate soft start process: 
The soft start process can be terminated by pressing MODE key (when boS=1). 

Содержание METICOM TM10

Страница 1: ...Hot Runner Temperature Controller with METICOM TM10 module User Guide Ver 1 01...

Страница 2: ...ic equipment you must observe standard safety procedures to protect both yourself and the equipment Cautions Service and installation of this equipment should only be performed by qualified service pe...

Страница 3: ...nel of the mainframe This diagram indicates the input voltage configuration that was prewired at the factory Make sure it matches what you ordered 3 INSTALLATION 1 You are installing a piece of electr...

Страница 4: ...Page 4 Copyright Mastip Technology Limited Information subject to alteration V3 51a www mastip com Temperature Controller METICOM TM10 Module 4 BACK PANEL WIRING...

Страница 5: ...Page 5 Copyright Mastip Technology Limited Information subject to alteration V3 51a www mastip com Temperature Controller METICOM TM10 Module 5 TYPICAL SYSTEM WIRING DIAGRAM...

Страница 6: ...teration V3 51a www mastip com Temperature Controller METICOM TM10 Module 6 Default CONNECTOR WIRING can be customized Combination Power Thermocouple Connector 16 or 24 Pin Separate Power Thermocouple...

Страница 7: ...le is set to be automatic closed loop control mode before shipping The temperature control module will show the code of the expected thermocouple type please check it and adjust the related setting ac...

Страница 8: ...m Thermocouple reverse alarm Temperature high alarm Temperature low alarm Heater fault alarm Heating invalid alarm High alarm of ambient temperature High limit of load current High limit of output per...

Страница 9: ...trol is an open loop system and requires no thermocouple feedback signal It can be used when thermocouple is failed or without thermocouple in system The controller s PV displays present temperature v...

Страница 10: ...difying the setting until new alarm happens 3 ALL low deviation alarm value When present value SV ALL the buzzer is beeping No alarm when power on or after modifying the setting until new alarm happen...

Страница 11: ...be changed quickly by press DISP key 9s 2 C F temperature unit 0 1 3 Sot soft start heater dehumidify function 0 Off 1 10 On soft start time Sot 80s Notes The rest of soft start time reduced to one th...

Страница 12: ...0 the controller will auto start standby mode until the operator end it by pressing MODE key 0 Off filtering value Std s number in the tens place ones place Used to reduce the influence of interferen...

Страница 13: ...ng make Snb 0 if the connection is right E r H Yes Thermocouple open Check the sensor or switch to manual control mode E r L Yes Thermocouple inverse H E A HEA No Heater fault Check the heater t r S Y...