  Temperature Controller 

 METICOM TM10 Module 

6. PID self-adjusting function

 (when SuP=453 or 845)

The controller will start to learn the system after power up (the process temperature should be less than 90% of set point).
Once the controller finishes "learning" the system, it returns to a standard PID control with the heat PID values automatically
set.

7. Boost (speed up heating) function

 (when boS=1)

In normal (auto PID) control mode (soft start process is over or terminated), press MODE key to activate the boost function.
For the next 15 seconds (or until you press the MODE  key again, whichever is sooner), 20% is added to the controller
output (100% output or parameter Pub limited maximum).
Normal indicator flashes.

8. Parameters

8-1. General parameters

1) SV: Setting Value, full scale.

2) ALH: high deviation alarm value.

When present value > SV+ALH, the buzzer is beeping, and the output is shut off. 

  No alarm when power on or after modifying the setting until new alarm happens. 

3) ALL: low deviation alarm value.

When present value < SV+ALL, the buzzer is beeping.   
No alarm when power on or after modifying the setting until new alarm happens. 

4) LCK: parameter setting lock.

 0: Off;    1: On, all parameters cannot be changed; 

11: On, all parameters cannot be changed except SV. 

8-2. Engineer parameters 1

1) A-n: initial power output percent for manual control, 0~100%, used with parameter nSL.

Note: When A-n is effective, its value is auto-refreshed by latest manual output percent.

2) P: control proportional band, 1~999.

3) i: integral time, 0~999s.

4) d: differential time, 0~999s.

5) Pb: PV bias, -120~120. Sensor correction is made by adding Pb to measured value (PV).

6) AdS: ambient temperature (internal mainframe) high alarm value, temperature unit is same as parameter C-F setting.

When Ads=0, this function is off. 

7) SuP: SV setting upper limit / AT target setting (see AT function) / PID self-adjusting (see Section 7), full scale.

SuP ≤ 900, the controller executes auto-tune function by making 80% of setting value as target. 
SuP> 900, the controller executes auto-tune function by making setting value as target. 
SuP = 453 or SuP = 845, PID self-adjusting function is on.   

8) nSL: Manual/Auto control mode.

Содержание METICOM TM10

Страница 1: ...Hot Runner Temperature Controller with METICOM TM10 module User Guide Ver 1 01...

Страница 2: ...ic equipment you must observe standard safety procedures to protect both yourself and the equipment Cautions Service and installation of this equipment should only be performed by qualified service pe...

Страница 3: ...nel of the mainframe This diagram indicates the input voltage configuration that was prewired at the factory Make sure it matches what you ordered 3 INSTALLATION 1 You are installing a piece of electr...

Страница 4: ...Page 4 Copyright Mastip Technology Limited Information subject to alteration V3 51a www mastip com Temperature Controller METICOM TM10 Module 4 BACK PANEL WIRING...

Страница 5: ...Page 5 Copyright Mastip Technology Limited Information subject to alteration V3 51a www mastip com Temperature Controller METICOM TM10 Module 5 TYPICAL SYSTEM WIRING DIAGRAM...

Страница 6: ...teration V3 51a www mastip com Temperature Controller METICOM TM10 Module 6 Default CONNECTOR WIRING can be customized Combination Power Thermocouple Connector 16 or 24 Pin Separate Power Thermocouple...

Страница 7: ...le is set to be automatic closed loop control mode before shipping The temperature control module will show the code of the expected thermocouple type please check it and adjust the related setting ac...

Страница 8: ...m Thermocouple reverse alarm Temperature high alarm Temperature low alarm Heater fault alarm Heating invalid alarm High alarm of ambient temperature High limit of load current High limit of output per...

Страница 9: ...trol is an open loop system and requires no thermocouple feedback signal It can be used when thermocouple is failed or without thermocouple in system The controller s PV displays present temperature v...

Страница 10: ...difying the setting until new alarm happens 3 ALL low deviation alarm value When present value SV ALL the buzzer is beeping No alarm when power on or after modifying the setting until new alarm happen...

Страница 11: ...be changed quickly by press DISP key 9s 2 C F temperature unit 0 1 3 Sot soft start heater dehumidify function 0 Off 1 10 On soft start time Sot 80s Notes The rest of soft start time reduced to one th...

Страница 12: ...0 the controller will auto start standby mode until the operator end it by pressing MODE key 0 Off filtering value Std s number in the tens place ones place Used to reduce the influence of interferen...

Страница 13: ...ng make Snb 0 if the connection is right E r H Yes Thermocouple open Check the sensor or switch to manual control mode E r L Yes Thermocouple inverse H E A HEA No Heater fault Check the heater t r S Y...

Отзывы: