Mass Combi Ultra, Mass Combi Pro
– Installation Manual Multiple Units
Parallel configuration with MasterAdjust
9
10. Select
Installer
and enter the installer code.
11. Go to the Configuration tab and give the unit a logical name. For example, MCU Primary. Do the same for the Replica units.
It's good practice to label them Replica 1, Replica 2 etc.
Note:
battery settings must be configured the same on all units.
12. Return to the Configuration tab of the Primary unit. All settings are done here. However, if Mastervolt Lithium-Ion batteries
are connected, all events, like Stop Discharge for example, must be configured for ALL units separately.
13. From the
Cluster
drop-down list, select
Single Phase
. You may need to maximize the MasterAdjust window or scroll all the
way to the right to see this.
14. From the
Dev. Per phase
drop-down list, select the number of units in parallel (P Replica).
15. Click the
Select devices
button to be able to select the Replica unit(s).