background image

Mass Combi Ultra, Mass Combi Pro 

– Installation Manual Multiple Units 

Parallel configuration with DIP switches 

 
 

 

13

 

 

 

 

 

 

4.6 

Configuration with DIP switches 

Pre-commissioning 

1.  Make sure that the units are switched off. 
2.  Make sure that all connections are firmly tightened. 

Configuration 

3.  Use a small screwdriver to carefully set the DIP switches of block A: 

 

DIP switch location MCU & MCP 

On the Primary unit set DIP switch A1 on (position 1) and keep A2 off (position 0). 

 

On the Replica unit keep DIP switch A1 off (position 0) and set A2 on (position 1). 

 

All other DIP switches 

(B1…B8 and A3…A8) on the Replica unit must match the settings on the Primary unit. For an 

overview of DIP switch settings, please see the user manual. 

4.7 

Initial start-up 

1.  Install the DC fuses and close the battery switch. 
2.  Close the covers of all units. 
3.  Close the AC breaker in AC output 1 of each unit. 
4.  Switch on all units. 
5.  Check that the units are working as inverter. 
6.  Close the AC breaker in the Mains Input of each unit. 
7.  Check that the units are working as charger when 230V

AC

 is applied to the Mains Inputs. 

8.  If applicable repeat this procedure for the generator.

Содержание MASS COMBI PRO

Страница 1: ...MULTIPLE UNITS MASS COMBI ULTRA MASS COMBI PRO Parallel or three phase configurations INSTALLATION MANUAL 10000007117 03 ...

Страница 2: ...nits 8 3 6 Configuration with MasterAdjust 8 3 7 Initial start up 10 4 PARALLEL CONFIGURATION WITH DIP SWITHES 11 4 1 Materials needed 11 4 2 Preparation 11 4 3 DC wiring of parallel units 11 4 4 AC wiring of parallel units 12 4 5 Network wiring of parallel units 12 4 6 Configuration with DIP switches 13 4 7 Initial start up 13 5 THREE PHASE CONFIGURATION WITH MASTERADJUST 14 5 1 Materials needed ...

Страница 3: ...rallel to maintain reliable power supply If one of the units should fail the remaining units continue Three MCU or MCP units can be installed in a 3 phase configuration to supply three phase AC power for high power loads like air conditioning By connecting more units in parallel as well virtually unlimited three phase power can be made available 1 4 General installation guidelines When using units...

Страница 4: ...ry positive 4 Secondary battery positive 5 Solar DC terminal 6 Mains AC input terminal 7 Generator AC input terminal 8 AC output 1 9 AC output 2 switched 10 DIP switch units 2x8 11 Fan 3x 12 Ground stud 13 Sync connector 2x 14 Temperature sensor connector 15 MasterBus connector 2x MCU 12 3000 150 and 24 3500 100 only Remove the cover by loosening these two screws ...

Страница 5: ...e 14 for the 3 phase with MasterAdjust installation procedure Start 3 Phase More than 2 units Lithium Ion Batteries Click here or go to page 6 for the parallel with MasterAdjust installation procedure YES Parallel configuration 3 Phase configuration NO Click here or go to page 11 for the parallel with DIP switches installation procedure YES NO NO YES Setup via DIP switches NO YES ...

Страница 6: ...roduct code e g 3 meter 77040300 n 1 Sync cables to interconnect all units product code e g 3 meter 6502000030 n 1 MasterBus USB Interface product code 77030100 1 Windows based PC with the MasterAdjust configuration tool 1 DC cable with fuse n DC cable n AC cable to connect the AC input of the unit to an external power source n AC cable to connect the external load to OUTPUT 1 n AC cable to connec...

Страница 7: ...ction Inline fuse Recommended battery bank Indicated cable sizes are for cables from unit to busbar and shorter than 3m Cables from busbar to battery bank should be twice the diameter When cables are longer than 3m the size should be increased to compensate for cable losses 12V 95 mm2 350 A 800 Ah 24V 50 mm2 175 A 400 Ah 48V 35 mm2 80 A 200 Ah 3 4 AC wiring of parallel units Neutral to ground bond...

Страница 8: ...Switch on all units 7 If not already available connect a MasterBus USB Interface to the MasterBus network and to a PC and open MasterAdjust Installation or configuration errors may come up in MasterAdjust while the configuration is in progress This is normal Configuration 8 In MasterAdjust check that the units are running the latest firmware software version See the Mastervolt Portal for more info...

Страница 9: ...ured the same on all units 12 Return to the Configuration tab of the Primary unit All settings are done here However if Mastervolt Lithium Ion batteries are connected all events like Stop Discharge for example must be configured for ALL units separately 13 From the Cluster drop down list select Single Phase You may need to maximize the MasterAdjust window or scroll all the way to the right to see ...

Страница 10: ...tion state of the cluster Click the Activate cluster button to finish the cluster configuration In the device list in the left pane of MasterAdjust the Replica unit s will now be listed under the Primary unit 3 7 Initial start up 1 Switch all units off and on again 2 Check that the units are working as inverter 3 Close the AC breaker in the Mains Input of each unit 4 Check that the units are worki...

Страница 11: ...C input of the unit to an external power source 2 AC cable to connect the external load to OUTPUT 1 2 AC cable to connect the external load to OUTPUT 2 2 4 2 Preparation Make sure that all power sources AC and DC are switched off 4 3 DC wiring of parallel units Note Always use the same length positive and negative cables Be aware that to keep the drawings in this chapter clear and easy to read the...

Страница 12: ... size Max 3 5 kW 2 5 mm2 20 A 3 6 7 kW 4 0 mm2 40 A 7 1 10 kW 6 0 mm2 50 A 10 kW 10 0 mm2 63 A Mains power AC cable cross section Max 16 A 3x 2 5 mm2 Max 32 A 3x 4 0 mm2 4 5 Network wiring of parallel units Residual Current Device RCD Circuit Breaker no RCD Breaker AC OUT 2 50 A max PRIMARY UNIT REPLICA UNIT Battery temperature sensor Sync cable MasterBus cable MasterBus network or terminator Mast...

Страница 13: ...eplica unit keep DIP switch A1 off position 0 and set A2 on position 1 All other DIP switches B1 B8 and A3 A8 on the Replica unit must match the settings on the Primary unit For an overview of DIP switch settings please see the user manual 4 7 Initial start up 1 Install the DC fuses and close the battery switch 2 Close the covers of all units 3 Close the AC breaker in AC output 1 of each unit 4 Sw...

Страница 14: ... MasterBus cables between units product code e g 3 meter 77040300 2 Sync cables to interconnect all units product code e g 3 meter 6502000030 2 MasterBus USB Interface product code 77030100 1 Windows based PC with the MasterAdjust configuration tool 1 DC cable with fuse 3 DC cable 3 AC cable to connect the AC input of the unit to an external power source 3 AC cable to connect the external load to ...

Страница 15: ...ted cable sizes are for cables from unit to busbar and shorter than 3m Cables from busbar to battery bank should be twice the diameter When cables are longer than 3m the size should be increased to compensate for cable losses 12V 95 mm2 350 A 800 Ah 24V 50 mm2 175 A 400 Ah 48V 35 mm2 80 A 200 Ah 5 4 AC wiring of three phase units Mains power cable cross section 2 5 mm2 Generator power AC cable cro...

Страница 16: ...ts are running the latest firmware See the Mastervolt Portal for more information 8 In the device list in the left pane of MasterAdjust right click the L1 unit and select Login 9 Select Installer and enter the installer code 10 Go to the Configuration tab and give the unit a logical name For example MCU L1 MCU L2 and MCU L3 11 Return to the Configuration tab of the L1 unit All settings are done he...

Страница 17: ...wn list select PER PHASE the number of units in parallel Primary Replica In our example this is 1 14 Click the Select devices button to be able to select the L2 and L3 units In the Phase L2 section from the Phase master Primary drop down list select the L2 unit In the Phase L3 section from the Phase master Primary drop down list select the L3 unit ...

Страница 18: ...will only switch over to charger mode if all three phases are present and accepted gen and or mains 5 8 General remark on three phase public power grids Depending on national guidelines the rotation of the three phase public grid can be different The field rotation of the configured Combi system is always L1 L2 L3 L1 L2 L3 etc If the public grid has a in respect to the Combi rotation reverse rotat...

Страница 19: ...ble throw switch of at least 32A 400V Use of an AC 1x6 relay controlled by MasterBus product code 77031500 To control the relay suitable events need to be configured This can be done from an EasyView 5 for example See the relevant user manual for more information on events INCOMING THREE PHASE N 400 230 TO MASTERVOLT COMBI UNITS L1 L2 L3 ...

Страница 20: ... are not connected to each other breakers The Mains LED on the Replica unit will keep blinking while the same LED on the Primary unit will be solid on when the MAINS AC input is accepted This normal behavior Likewise LED GEN on the Replica unit will keep blinking while the same LED on the Primary unit will be solid on when the GEN AC input is accepted This is also normal behavior LED 1 is MCU 12 3...

Страница 21: ...in overload inverted power exceeds 3500 W Check the load connected and disconnect 10 red Battery low Battery voltage low Stop inverting start charging 11 blinking Error in sec charger Internal Hardware error Contact Mastervolt 10 blinking red Charging a low battery Disconnect all DC loads Errors MCU MCP shuts down 4 and 10 red 5 yellow Overtemperature Combi too hot Restart when alarm is over Check...

Страница 22: ... Shipping Advanced Systems Group US N85 W12545 Westbrook Crossing Menomonee Falls Wisconsin 53051 United States Asia Pacific Customer Service T 64 9 415 7261 Option 1 E enquiries bepmarine com Technical Support T 64 9 415 7261 Option 3 E technical apac powerprodllc com Location Shipping Advanced Systems Group APAC 42 Apollo Drive Rosedale Auckland 0632 New Zealand Copyright 2021 Advanced Systems G...

Отзывы: