13.2 Error codes
The following error codes are displayed when the Masterlink MICC detects a problem. The display
alternates between the selected monitoring function and the error code. The error code continues to
flash until the error is corrected.
Code Description
Action
E1
Battery Temperature error, the batteries
are too warm to be charged safely.
The charger will stop charging until the battery
temperature is within the safe margin. Make sure that the
batteries are ventilated properly.
E2
DC error, automatic charger shut down
due to too low or too high DC Voltage
DC system voltage has dropped below 10.5V (12V
system), 21.0V (24V system), or has risen above 15.5V
(12V system), 31.0V (24Vsystem)
E3
Short-circuit of the charger output.
Possible short-circuit on the output, The charge current
will be reduced to a quarter of the maximum value.
E4
Charger is too hot, automatic charger
shutdown due to too high temperature
The charger switches automatically on after it has cooled
down sufficiently. Make sure that the charger is ventilated
properly
E5
Charger switched off because of a
battery sense error
The battery voltage sense wires are connected wrong or
the charger has reached the maximum compensation
value. The charger compensates the voltage loss with a
maximum of 2,5V
E6
Inverter error.
The inverter is in overload, reduce load. Inverter
temperature is too high, inverter will automatically switch
off and on if temperature has dropped sufficiently. Make
sure that the inverter is ventilated. DC supply voltage to
high switch off charger .
The following error code is displayed when the Masterlink MICC detects a communication problem with
the battery charger.
Code
Description
Action
NO COMM Communication error with the battery
charger. The battery charger is switched
off or the AC-input is disconnected.
Switch on the battery charger or adjust the
charger’s DIP-switch correctly (refer to the
charger’s operation manual, “ContMon”;
REMARK: When the ContMon function is enabled
while the battery charger is switched off, energy is
withdrawn from the battery connected to the
battery charger.
NO COMM Communication error with the battery
charger. The battery charger is
disconnected from the Masterlink MICC
or connected by a wrong modular
communication cable (RJ12, cross wired)
Check the wiring of the 6 pole modular
communication cable (Chapter 3.2 and 3.3, step
9)