Mastervolt 70403105 Скачать руководство пользователя страница 25

 
 
 
 
 
 

 

November 2004 / Masterlink MICC / EN

 

25

 

9  PROGRAM MENU 

 
The Program menu is used to set the Masterlink 
MICC according the users requirements.  
 

This  menu  can  be  entered  by 
and  holding  the 

Select

  button 

for  5  seconds  until  the  Select-
LED is flashing.  

 

Now  press  the 

Set-up

-button 

shortly  to  enter  the  “program 
menu”  

 

With the 

Select

 button you can 

scroll  through  the  levels  of  this 
menu. 
 

For  more  information  see  also  the  set-
up  drawing  (figure  8).  The  numbers  of 
the  mentioned  levels  below  correspond 
with this drawing. 

 

Sleep mode (F01) 

The first level that can be set is the sleep mode. 
For  an  even  lower  power  consumption  of  the 
MICC,  as  often  required  in  solar  applications, 
the MICC can be set so that the backlight of the 
display will be switched off if the buttons are not 
used  for  15  seconds.  In  this  way  the  power 
consumption  is  reduced  till  28  mA.  As  soon  as 
one  of  the  buttons  will  be  touched  the  display 
will  be  lit  again  for  an  easy  reading  of  the 
display.  This  function  is  very  useful  if  smaller 
battery  capacities  are  used  or  in  solar 
applications  where  as  low  a  possible  power 
consumption as possible is required. The sleep 
mode can be switched on or off by means of the 

Set-up

  button.  The  factory  default  setting  is 

"On". 
 

Setting alarm function on or off (F02) 

With the second level it is possible to switch the 
output of the alarm function on or off. The alarm 
status  will  still  be  shown  in  the  display  but  the 
external  alarm  contact  of  the  MICC  will  not  be 
activated  (check  chapter  section  for  more 
information about alarm settings). If this mode is 
entered, the alarm function can be switched on 
or  off  by  means  of  the 

Set-up

  button.  The 

factory default for this level is off. 
 

Adjustment  of  the  charger/inverter  LED- 
indication (F03) 

With  the  third  and  last  level  it  is  possible  to 
change the function of the LED-indication of the 
charger  and  inverter  buttons.  Factory  settings 
for  this  function  is  ‘OFF’  which  means  that  the 
charger  LED  and  the  inverter  LED  will  only 
illuminate 

when 

the 

battery 

charger, 

respectively  the  inverter  are  actually  switched 
on and that they are operating without failures.  
With  the 

Set-up 

button  you  can  switch  this 

function  to  ‘ON’.  When  switched  ON  the 
indication  LED  will  illuminate  as  soon  as  the 
Battery charger or the inverter is switched on by 
means  of  the  Charger-button,  respectively  the 
Inverter-button.  Then  the  LED  will  illuminate 
immediately,  whether  the  charger  is  operating 
without failures or not.  
 

Activate Mass Combi setting (F04) 

You only have to activate (ON) this setting if you 
are  using  the  Masterlink  MICC  in  combination 
with  the  Mass  Combi.  The  default  setting  is 
“OFF”. 

 

Return to users menu (F05)  

 
If this level is entered you can return to the user 
menu by means of the 

Set-up

 button. 

Select 

Select 

Set-up 

Select 

 SLEEP MODE 
     ON 

Select 

LOW BAT CONT. 
    OFF 

Select 

LED IS SWITCH 
    OFF 

Select 

EXIT LEVEL 
 ->PRESS SET-UP 

Select 

HFC MODE 

OFF 

Содержание 70403105

Страница 1: ...ANUAL MASTERLINK MICC MASS INVERTER CHARGER CONTROL MASTERVOLT Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 www mastervolt com Language English Version V4 0...

Страница 2: ...2 November 2004 Masterlink MICC EN...

Страница 3: ...ials needed for installation 7 3 3 Step by Step installation 8 3 4 Installation of an external alarm 10 3 5 Connection of the charger and the inverter 10 4 SYNCHRONISATION AND SETTING THE BATTERY CAPA...

Страница 4: ...ting alarm function 26 10 2 Exponent adjustment 26 10 3 Reset menu 27 11 ADDITIONAL INFORMATION 28 11 1 The Peukert Exponent 28 11 2 Time Remaining CEF History 29 12 GENERAL BATTERY INFORMATION 30 13...

Страница 5: ...This manual has 16 chapters 1 2 Guarantee Specifications Mastervolt guarantees that this unit has been built in accordance with the legally applicable standards and specifications Should work take pla...

Страница 6: ...the Masterlink MICC at locations where there is danger of gas or dust explosion 3 Use other than as mentioned under 2 is not considered to be consistent with the intended purpose MASTERVOLT is not li...

Страница 7: ...x0 25 mm shielded twin twisted pair x Or One cable 2x0 25 mm shielded twisted pair and three normal 2 core cables 2x0 25 mm x Two 6 pole modular communication cables RJ12 cross wired see figure 1 to c...

Страница 8: ...nk MICC 4 Run the twisted wired cable 2x 0 25 mm between the shunt and the Masterlink MICC Be sure that the wires are long enough to be connected at the left side of the shunt The shunt s output volta...

Страница 9: ...the total stand by power consumption will be reduced from 50mA to 30mA if the Mass Combi is switched off by means of the Inverter button on the Masterlink MICC panel When installed it is not possible...

Страница 10: ...the Masterlink MICC to the charger or inverter If it is necessary to disconnect batteries and charger inverter then first disconnect Masterlink MICC from the charger inverter For an appropriate operat...

Страница 11: ...ry signal n o Chassis ground or Ship s ground in case required Shunt 500A 50mV Minus DC distribution MASS INVERTER CHARGER CONTROL AC present Select Inverter Charger Time remain 03 hr 20 min Float Abs...

Страница 12: ...ion LED flashes Press the Ah Time button shortly to display the battery capacity Adjust the required capacity of the main battery by pressing the Set up button If the Select button is held for five se...

Страница 13: ...ED is flashing Now press the Set up button shortly to enter the program menu Press the Select button 4 times shortly until the HFC MODE is displayed Select the required setting using the Set up button...

Страница 14: ...e major parts remote control of the battery charger remote control of the inverter and retrieving information you re your batteries see figure 6 5 2 Remote control of the battery charger By pressing t...

Страница 15: ...ication LED flashes Press the Charger button shortly to display CURRENT CONT Adjust the desired output current 10 100 by pressing the Set up button If the Select button is held for five seconds the ar...

Страница 16: ...rter By pressing the Inverter switch the inverter can be switched on and off After a few seconds the Inverter LED illuminates when the inverter is in operation AC output Figure 7 Set up drawing user l...

Страница 17: ...rge of the battery This value is automatically compensated by the charge efficiency factor C E F and the Peukert exponent check chapter 11 for more information about the C E F and about the Peukert ex...

Страница 18: ...H03 The second level shows the Peukert exponent Standard batteries are rated for a 20 hour discharge This means that a 100 Ah battery can supply 5 amps for 20 hours before a voltage of 1 75 volt cell...

Страница 19: ...a battery can handle depends strongly on the type of battery and its quality One cycle is reached if the battery is discharged from 100 state of charge down to 0 followed by a charge up to 100 One cyc...

Страница 20: ...n level 1 DEPT 1 Charger Ahr time Volt Amp Inverter Select MICC Installer level Hold select 2 4 sec untill led flashes and select the function below DEPT 7 DEPT 7 A07 Exit level A07 Exit level M03 Set...

Страница 21: ...roll through the levels of this menu and adjust several alarm set points For more information see also the set up drawing figure 8 and figure 10 The numbers that are mentioned behind the levels corres...

Страница 22: ...attery voltage the alarm will be activated after 30 seconds This prevents the alarm being activated during a small dip in the battery voltage Low battery alarm off setting M03 The fourth level is used...

Страница 23: ...our rating and set the MICC according this value For 12 volt systems the capacities of all the installed batteries of the main battery bank can be added If a 24 volt battery system will be used all th...

Страница 24: ...easured at the output terminals of the charging system and therefore it is necessary for these voltages to be set approx 0 4 volt lower to compensate for the voltage drop in the wiring In the above me...

Страница 25: ...nction on or off The alarm status will still be shown in the display but the external alarm contact of the MICC will not be activated check chapter section for more information about alarm settings If...

Страница 26: ...ions Return to users menu M07 By pressing the Select button you can scroll to the EXIT LEVEL If this level is entered you can return to the user menu by means of the Set up button 10 2 Exponent adjust...

Страница 27: ...ased by means of the Set up button If the arrow is pointing upwards the set value can be increased Return to users menu A10 If this level is entered you can return to the user menu by means of the Set...

Страница 28: ...a high and one at a low discharge rate which are about the minimal and maximal discharge rate for your situation enables you to calculate a value n for the Peukert exponent which fits best to your si...

Страница 29: ...aches 1 75 V per cell 10 5V for a 12 V battery This would be equivalent to a discharge rate of 25 A for a 100 Ah battery If the battery delivered 67 134 Ah the appropriate Peukert s exponent would be...

Страница 30: ...available However using a generator to charge the battery up to more than 85 is not efficient The reason for this is that the charging current is strongly reduced after reaching 80 85 of the battery...

Страница 31: ...tion between battery side and system side chapter 3 3 Back light switches off after 15 seconds Unit in sleep mode Press one of the buttons or refer to chapter 9 step F01 to disable the sleep mode No a...

Страница 32: ...ger switched off because of a battery sense error The battery voltage sense wires are connected wrong or the charger has reached the maximum compensation value The charger compensates the voltage loss...

Страница 33: ...Measurement 7 35 volts 0 01 volt resolution Amperage Measurement 0 500 Amp 0 2A resolution 0 42A 2A resolution 42 500A Amp Hours Measurement 0 2000 Ah 1 Ah resolution Time remaining 0 255 hours 1 min...

Страница 34: ...Panel Minimum required dimensions for installing panel only width x height x depth 120 x 65 x 40mm Grey mounting box Dimensions grey mounting box width x height x depth 140 x 85 x 50mm Dimensions for...

Страница 35: ...onformity with the following provisions of the EC EMC directive EMC 89 336 EEG and amendments 92 31 EEC and 93 68 EEC The following harmonized standards have been applied Generic emission standard EN...

Страница 36: ...Snijdersbergweg 93 1105 AN Amsterdam The Netherlands Tel 31 20 3422100 Fax 31 20 6971006 Email info mastervolt com...

Отзывы: