Mastervolt 55006010 Скачать руководство пользователя страница 9

SPECIFICATIONS 

9

 

5 SPECIFICATIONS 

GENERAL

Function of the product: 

Automatic transfer switch between two single phase AC power sources and one output. 
Additional external circuit breakers must be applied (installation dependent). 

Manufacturer:

Mastervolt, 

Amsterdam, the Netherlands 

Specified operation temperature  

-5…+60 °C (will meet specified tolerances)

Allowed operating temperature:  

-40…+70 °C (may not meet all specified tolerances)

None operating temperature:  

-60…+80 °C (storage temperature)

Relative humidity: 

95% max., non-condensing  

Earth leakage breaker (RCCB): 

N/A, must be applied externally (installation dependent) 

Automatic circuit breakers: 

N/A, must be applied externally (installation dependent) 

230V VERSIONS 

Masterswitch 0 - 5kW 230V/20A 

Masterswitch 0 - 10kW 230V/40A 

Part number: 

55006010 

55006015 

Nominal voltage:  

Single phase 200 – 250 VAC / 50-60Hz 

Nominal current INPUT 1: 

20A  

40A  

Nominal current INPUT 2: 

20A  

40A 

Nominal current OUTPUT: 

20A  

40A 

Switching current (I eff, IEC947): 

250A  

450A 

Power consumption:  
(AC available on INPUT 1) 

7 VA ± 10% 

7 VA ± 10% 

Power consumption:  
(only AC available on INPUT 2)  

0 VA 

0 VA 

Transfer time by making 

12-22 msec

12-22 msec.

Transfer time by braking 

4-19 msec

4-19 msec.

Delay time INPUT1: 

Approximately 10 sec. (adjustable, see chapter 4.6) 

Dimensions, H x W x D: 
(see also chapter 6) 

200 x 123 x 111.5 mm 
7.9 x 4.8 x 4.4 inch. 

200 x 123 x 111.5 mm 
7.9 x 4.8 x 4.4 inch. 

Approximate weight: 

1.2 kg / 2.6 Lbs ± 5% 

1.3 kg / 2.9 Lbs ± 5% 

Protection degree: 

IP55 (IEC-529)

IP55 

(IEC-529)

Recomm. torque connections: 

1.7 Nm / 15 In-Lbs 

2.5 Nm / 22 In-Lbs 

117V VERSIONS 

Masterswitch 0 – 3.5kW 
117V/32A 

Masterswitch 0 – 7kW 
117V/60A 

Masterswitch 0–9kW 
117V/80A 

Part number: 

55106000 

55106100 

55106200 

Nominal voltage:  

Single phase 100 – 125 VAC / 50-60Hz 

Nominal current INPUT 1: 

32A  

60A  

80A  

Nominal current INPUT 2: 

32A  

60A 

80A 

Nominal current OUTPUT: 

32A  

60A 

80A 

Switching current (I eff, IEC947): 

300 A  

1000 A 

1000 A 

Power consumption:  
(AC available on INPUT 1) 

7 VA ± 10% 

26 VA ± 10% 

26 VA ± 10% 

Power consumption:  
(only AC available on INPUT 2)  

0 VA 

0 VA 

0 VA 

Transfer time by making 

12-22 msec

20-26 msec

20-35 msec

Transfer time by breaking 

4-19 msec

8-12 msec

6-20 msec

Delay time INPUT1: 

Approximately 10 sec. (adjustable, see chapter 4.6) 

Dimensions, H x W x D: 
(see also chapter 6) 

200 x 123 x 111.5 mm 
7.9 x 4.8 x 4.4 inch. 

214 x 162 x 128 mm 
8.4 x 6.4 x 5.0 inch. 

214 x 162 x 128 mm 
8.4 x 6.4 x 5.0 inch. 

Approximate weight: 

1.2 kg / 2.6 Lbs ± 5% 

2.6 kg / 5.7 Lbs ± 5% 

2.7 kg / 6.0 Lbs ± 5%

 

Protection degree: 

IP55 (IEC-529) 

IP66 (IEC-529) 

IP66 (IEC-529) 

Recomm. torque connections: 

1.7 Nm / 15 In-Lbs 

6 Nm / 53 In-Lbs 

6 Nm / 53 In-Lbs 

All specifications are subject to change without prior notice.

 

Содержание 55006010

Страница 1: ...INSTALLATION AND USERS MANUAL MASTERSWITCH 0 Automatic AC transfer switch...

Страница 2: ...ended purpose 4 2 3 Organizational measures 4 2 4 Warning of special dangers 4 3 HOW IT WORKS 5 3 1 Source priority 5 3 2 INPUT 1 generator or shore input 5 3 3 INPUT 2 inverter input 5 4 INSTALLATION...

Страница 3: ...ICATIONS Mastervolt guarantees that this unit has been built according to the legally applicable standards and specifications Should work take place which is not in accordance with the guidelines inst...

Страница 4: ...er use the Masterswitch 0 in situations where there is danger of gas or dust explosion or potentially flammable products 3 Use of the Masterswitch 0 other than mentioned in point 2 is not considered t...

Страница 5: ...mately 10 seconds The 10 seconds delay time provides an easy start up for the generator In normal situations the generator is stabilized after app 3 sec To make sure no voltage and frequency variation...

Страница 6: ...n mm AWG 0 16 Amp 2 5 mm AWG 13 16 32 Amp 4 mm AWG 11 32 48 Amp 6 mm AWG 9 48 80 Amp 10 mm AWG 7 WARNING Use cable with the right cable diameter Under sized cables and or loose connections can cause d...

Страница 7: ...re 2 Installation of the Masterswitch 0 Masterswitch 0 7kW 117V 60A Masterswitch 0 9kW 117V 80A Masterswitch 0 5kW 230V 20A Masterswitch 0 10kW 230V 40A Masterswitch 0 3 5kW 117V 32A Delay time INPUT1...

Страница 8: ...h on the Masterswitch 0 1 Tighten all cable glands to ensure the pull relief 2 Check all wiring and connections 3 Close the cabinet 4 Switch on the AC power sources 4 8 DECOMMISSIONING If it is necess...

Страница 9: ...ely 10 sec adjustable see chapter 4 6 Dimensions H x W x D see also chapter 6 200 x 123 x 111 5 mm 7 9 x 4 8 x 4 4 inch 200 x 123 x 111 5 mm 7 9 x 4 8 x 4 4 inch Approximate weight 1 2 kg 2 6 Lbs 5 1...

Страница 10: ...DRAWINGS All dimensions are in millimeters Figure 5 dimensions of the Masterswitch 0 Masterswitch 0 5kW 230V 20A Masterswitch 0 10kW 230V 40A Masterswitch 0 3 5kW 117V 32A Masterswitch 0 7kW 117V 60A...

Страница 11: ...A Is in conformity with the provision of the EC EMC directive 89 336 EEC and amendments 92 31 EEC 93 68 EEC The following harmonized standards have been applied Generic emission standard EN 50081 1 19...

Отзывы: