Page 9
-
↑
+
↓
P001
Wind sensor activation threshold (5 - 50) Km/h F[30]
-
↑
+
↓
P005
Rain sensor exclusion time (0 - 10) min F[0]
-
↑
+
↓
P006
Sensor priority (1 - 3) F[1]. Priority can be selected for only one sensor,
where:
•
1=rain
•
2=wind, 3=timer
-
↑
+
↓
P101
Motor 1 work time (10 - 120) s F[60]
-
↑
+
↓
P102
Motor 1 reset time (0 - 240) s F[0]
-
↑
+
↓
P103
Motor 1 Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
•
0=none
•
1=open
•
2=close
-
↑
+
↓
P104
Motor 1 Rain sensor function (1 - 2) F[2]. Set the action when the input is
active, as follows:
•
1=open
•
2=close
-
↑
+
↓
P105
Motor 1 Timer function F[0]. Set the action when active as follows:
•
0=none
•
1=open
•
2=close
-
↑
+
↓
P201
Motor 2 Work time (10 - 120) s F[60]
-
↑
+
↓
P202
Motor 2 Reset time (0 - 240) s F[0]
-
↑
+
↓
P203
Motor 2 Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
•
0=none
•
1=open
•
2=close