background image

 

13

FINAL CHECK LIST 

A. 

Check operating pressures. 

 
B. 

Check electrical requirements of unit to supply voltage. 

 
C. 

Set temperature control for desired temperature range. 

 
D. 

Check system for proper defrost settings and operation. 

 
E. 

Check condensing unit for vibrating or rubbing tubing.  Dampen and clamp as required. 

 
F. 

All valves should be completely open counter-clockwise. 

 
G. 

Check packing nuts on all service valves. 

 
H. 

Replace all service valve caps and latch unit covers. 

 

SENSOR PROBE  

 

NOTICE:

  If the probe assembly is disconnected from the main board during normal operation (unit running), 

the connectors must be installed in the same position that they had before disconnection (P1 and P2), 
otherwise the control will not function properly. 
 
The Electronic  Refrigeration Control sensors  have NTC thermistors.  The reference resistance is 30,000 
ohms at 77

°

F (25

°

C).  It carries NTC thermistors with a range of –40

°

 to 199

°

 F.   In case there is a failure, 

these sensors should be used in replacement of the sensors shipped with the control.  In order to diagnose 
faults in the probe, the control has LED functions as a diagnostic tool.  When power is supplied to the control, 
the LED will turn on and will remain on as long as this condition is satisfied.  When there is a fault in the probe, 
the LED will blink intermittently.  When this occurs, the probe assembly needs to be replaced.  If power is 
supplied to the control and the LED remains off, there is a failure in the main relay control and it needs to be 
replaced. 
 
In case of a probe failure, the control will go into a safety mode of operation.  While in safety mode the control 
ignores probe inputs and cycles the compressor on for 5 minutes and off for 3 hours.  The LED will be blinking 
and signaling that  there is something wrong with the probe.  To replace the sensor probes, disconnect power 
to the control, replace the probes and restart the unit.  Since the wire is fixed to the cabinet, a technician may 
cut the sensor wire inside the cabinet and splice it with a new sensor.   
 

SENSOR PROBE TEMPERATURE AND RESISTANCE 

Temperature Resistance 

°

°

Ohms 

-29.2 -34 

683,100 

-20.2 

-29 

499,200 

-9.4 -23 

347,100 

-0.4 

-18 

259,500 

10.4 -12 

185,200 

19.4 

-7 

141,200 

30.2 -1 

103,100 

32.0 

97,950 

39.2 4 

80,040 

50.0 

10 

59,700 

60.8 16 

45,000 

69.8 

21 

35,820 

80.6 27 

27,500 

89.6 

32 

22,210 

 

 

Содержание TAF-27 ERC2 s

Страница 1: ...Installation Operations Manual Master Bilt Products 908 Highway 15 North New Albany MS 38652 Phone 800 684 8988 PN 228 90000 Rev 05 04 04 bhs...

Страница 2: ...2...

Страница 3: ...TRUCTIONS 6 Inspection for ShippingDamage 6 INSTALLATION INSTRUCTIONS 6 General Instructions 6 Electrical 6 Leg and Condensate Pan Installation 7 ELECTRONIC REFRIGERATION CONTROL ERC 8 FINAL CHECK LIS...

Страница 4: ...If this case is to be located against a wall there should be at least 6 space between the wall and the back of the case see page 7 This space will allow for the circulation of air behind the case whi...

Страница 5: ...ing signal words are used in the warnings and safety messages DANGER Severe injury or death will occur if you ignore the message WARNING Severe injury or death can occur if you ignore the message CAUT...

Страница 6: ...if the cabinet is malfunctioning or if there is a drainpipe leaking MECHANICAL Remove front grille and check refrigeration lines to see that they are free not touching each other or compressor Spin co...

Страница 7: ...temperatures for short periods of time 6 When replacing burned out fluorescent tubes be sure that the electrical power to the lighting circuit is turned off ELECTRICAL WARNING Before servicing electr...

Страница 8: ...s The TAF 27 models are cord connected and operate on a 15 amp 115 60 1 circuit The TAF 48 and TAF 74 models have two junction boxes mounted on top of the cabinet at the right rear for permanent conne...

Страница 9: ...T to accept the new time Step 5 Press DOWN to go to the next parameter Set point Temperature cut out Step 6 Press SET to change the set point temperature Step 7 or Press UP or DOWN to go to the desire...

Страница 10: ...Status dSPL Information shown on the display during operation conditions tdAy time of day rSP zone temperature CyCL cycle between time and zone temperature Epr evaporator coil temperature rSP Clock Fo...

Страница 11: ...e Range from 0 to 15 min 2 for LT 0 for MT Pump Down Pudn Pump down duration Range from 0 to 59 min 0 min Drip Time driP Drip time duration Range from 0 to 59 min 2 for LT 0 for MT Setpoint Differenti...

Страница 12: ...on the display Press SET to accept the change Press DOWN to go to Defrost Start Time dEF1 Press SET to change the time Press UP or DOWN until the 11 59 PM appears on the display Press SET Press DOWN...

Страница 13: ...s in the probe the control has LED functions as a diagnostic tool When power is supplied to the control the LED will turn on and will remain on as long as this condition is satisfied When there is a f...

Страница 14: ...Compressor starts and runs but cycles on overload A Low voltage B Dropped phase 3 phase C Overload protector defective D High head pressure see 1 6 Compressor will not start hums but cycles on overloa...

Страница 15: ...Gasket 37 01207 37 01211 37 01211 Door Handle 35 01488 35 01488 35 01488 Door Hinge Assembly A35 01501 A35 01501 A35 01501 Door Light Switch 35 01506 35 01506 35 01506 Door Opening Trim 29 01481 29 01...

Страница 16: ...ster Bilt at 800 684 8988 The customer service department at Master Bilt should be contacted at the time of sale or disposal of your cabinet so records may be kept of its new location If you sell or g...

Страница 17: ...17...

Страница 18: ...18...

Отзывы: