background image

 

12

High 
Temperature 
Alarm  

ALHi 

High temperature 

setpoint that will 
make the alarm go 
off and the error 
message appear on 
the display 

Range: from – 40  to 83

°

F or –40 to 

23

°

50

°

 F 

 

Important Note: To change from degrees C to F or vice-versa, the user must reprogram all the 
parameters that are related to the temperature. The unit does not convert the parameters 
automatically from degrees F to C or vice-versa. 

 

Example 1 - To adjust the time-of-day 

-

 

Press and hold SET for 5 seconds 

-

 

Press SET again 

-

 

Press UP or DOWN until the correct time appears on the display 

-

 

Press SET to accept the new time 

-

 

Press DOWN twice to exit the programming mode

 

Example 2 - To set one defrost  a day, at 11:59 PM 

-

 

Press and hold SET and DOWN for 10 seconds 

-

 

Press DOWN five times to get to go to the Defrost Interval (

dFIn

-

 

Press SET to change the parameter 

-

 

Press DOWN until 

tdAy

 appears on the display 

-

 

Press SET to accept the option 

-

 

Press DOWN seven times to go to the Number of Defrosts (

noDF

-

 

Press SET to change it 

-

 

Press UP or DOWN until 

1

 appears on the display 

-

 

Press SET to accept the change 

-

 

Press DOWN to go to Defrost Start Time (

dEF1

-

 

Press SET to change the time 

-

 

Press UP or DOWN until the 

11:59

 PM appears on the display 

-

 

Press SET 

-

 

Press DOWN ten times to exit the programming level

 

 

 
Error Codes  

 

Display Control 

Status 

Er 1 

ERC Fault – software or hardware failure 

Er 2 

ERC Communication Fault – indicates that there is a problem with the display module cable 

Er 3 

Zone Sensor Fault – indicates an open or shorted temperature sensor 

Er 4 

Evaporator Sensor Fault – indicates  an open or shorted evaporator sensor 

Er 5 

ERC Fault – software or hardware failure 

Er 6 

Low Temperature Alarm – indicates that the temperature has dropped below the low alarm setpoint 

Er 7 

High Temperature Alarm – indicates that the temperature has gone above the high alarm setpoint 

Er 8 

Relay and display modules are incompatible 

For Error Codes 1, 2 and 5 cut the power to the unit and correct the problem to reset the 
display. 
For Codes 3 and 4, press the UP or DOWN button on the display to reset the error message. 
If the display still shows the message, the sensor must be replaced. 
The Error Codes 6 and 7 will be automatically reset once the temperature is back within the 
two set points.

 

 
 

Содержание TAF-27 ERC2 s

Страница 1: ...Installation Operations Manual Master Bilt Products 908 Highway 15 North New Albany MS 38652 Phone 800 684 8988 PN 228 90000 Rev 05 04 04 bhs...

Страница 2: ...2...

Страница 3: ...TRUCTIONS 6 Inspection for ShippingDamage 6 INSTALLATION INSTRUCTIONS 6 General Instructions 6 Electrical 6 Leg and Condensate Pan Installation 7 ELECTRONIC REFRIGERATION CONTROL ERC 8 FINAL CHECK LIS...

Страница 4: ...If this case is to be located against a wall there should be at least 6 space between the wall and the back of the case see page 7 This space will allow for the circulation of air behind the case whi...

Страница 5: ...ing signal words are used in the warnings and safety messages DANGER Severe injury or death will occur if you ignore the message WARNING Severe injury or death can occur if you ignore the message CAUT...

Страница 6: ...if the cabinet is malfunctioning or if there is a drainpipe leaking MECHANICAL Remove front grille and check refrigeration lines to see that they are free not touching each other or compressor Spin co...

Страница 7: ...temperatures for short periods of time 6 When replacing burned out fluorescent tubes be sure that the electrical power to the lighting circuit is turned off ELECTRICAL WARNING Before servicing electr...

Страница 8: ...s The TAF 27 models are cord connected and operate on a 15 amp 115 60 1 circuit The TAF 48 and TAF 74 models have two junction boxes mounted on top of the cabinet at the right rear for permanent conne...

Страница 9: ...T to accept the new time Step 5 Press DOWN to go to the next parameter Set point Temperature cut out Step 6 Press SET to change the set point temperature Step 7 or Press UP or DOWN to go to the desire...

Страница 10: ...Status dSPL Information shown on the display during operation conditions tdAy time of day rSP zone temperature CyCL cycle between time and zone temperature Epr evaporator coil temperature rSP Clock Fo...

Страница 11: ...e Range from 0 to 15 min 2 for LT 0 for MT Pump Down Pudn Pump down duration Range from 0 to 59 min 0 min Drip Time driP Drip time duration Range from 0 to 59 min 2 for LT 0 for MT Setpoint Differenti...

Страница 12: ...on the display Press SET to accept the change Press DOWN to go to Defrost Start Time dEF1 Press SET to change the time Press UP or DOWN until the 11 59 PM appears on the display Press SET Press DOWN...

Страница 13: ...s in the probe the control has LED functions as a diagnostic tool When power is supplied to the control the LED will turn on and will remain on as long as this condition is satisfied When there is a f...

Страница 14: ...Compressor starts and runs but cycles on overload A Low voltage B Dropped phase 3 phase C Overload protector defective D High head pressure see 1 6 Compressor will not start hums but cycles on overloa...

Страница 15: ...Gasket 37 01207 37 01211 37 01211 Door Handle 35 01488 35 01488 35 01488 Door Hinge Assembly A35 01501 A35 01501 A35 01501 Door Light Switch 35 01506 35 01506 35 01506 Door Opening Trim 29 01481 29 01...

Страница 16: ...ster Bilt at 800 684 8988 The customer service department at Master Bilt should be contacted at the time of sale or disposal of your cabinet so records may be kept of its new location If you sell or g...

Страница 17: ...17...

Страница 18: ...18...

Отзывы: