50
13.
Charging Management
Charging Parameter
Default
Value
Note
Charging current
60A
It can be adjusted via software from
5Amp to 120Amp.
Floating charging voltage (default) 54.0 Vdc It can be adjusted via software from
50Vac to 62Vdc.
Max. absorption charging voltage
(default)
56.0 Vdc
It can be adjusted via software from
50Vac to 62Vdc.
Battery overcharge protection
64.0 Vdc
Charging process based on default
setting.
3 stages:
First – max. charging voltage
increases to 56V;
Second- charging voltage will
maintain at 56V until charging
current is down to 12 Amp;
Third- go to floating charging at
54V.
Bulk
Floating
Absorption
time
U
time
I
Bulk Voltage
Float Voltage
This inverter can connect to battery types of sealed lead acid battery, vented battery, gel
battery and lithium battery. The detail installation and maintenance explanations of the
external battery pack are provided in the manufacturer’s external battery pack of manual.