This chapter describes the facility required for the MASSIVit 1800 printer operation.
Electrical Infrastructure
This section provides the electrical specifications of the Massivit 1800 printer. Every
system may be adapted to the mains power voltage of the country of installation.
Tables below shows the electrical requirements and power consumption of the
Massivit 1800 system.
The figure shows the recommended power connection of the Massivit 1800
system.
A dedicated power outlet should be provided for the UPS Backup unit located in
the main cabinet
Important! It is the responsibility of the customer to contact a local authorized
electrician to prepare the site with the proper wiring, circuit breakers, fuses
(and power transformer if necessary), and then to connect the Massivit 1800
system to the mains power outlet.
Table 2-Electrical Requirements
Table 3-Power Consumption
Unit
Connection type
Voltage input
CB Rating
Power Line Ø
Printing
unit
5-wire connection,
3 + N + G
380 - 400 V (±10%) between phases,
50/60 (±3 Hz)
3 x 25 A
Per local code
Unit
Nominal
Printing unit
20 A, 13 kW 15KVA