Page | 37
MINT – IO
REF NO: m25A/om/101
Issue No: 11
High pulse
width
High pulse
width
Low pulse
width
4.2.5.2 Type of Channel:
This parameter enables the user to configure the channel output type. The
user configurable options are:
Discrete Output:
The channel output will remain constant as the controller requires.
Single Pulse:
When working in single pulse mode, “1” means starting a high level period
which is defined in the Pulse Width parameter. When a high level period time
expires the Output will stay low
. “0” means canceling the last starting action.
Before starting the next
Single pulse a canceling “0” is required.
Continuous Pulse:
When working in continuous
pulse mode, ‘1’ means starting a continuous
pulse train, the
High and low level lengths of which are defined in Parameters.
‘0’ means canceling the last
Starting action. The factory default is “Discrete
Output” for this parameter.
4.2.5.3 Pulse Width of Channel
This parameter is used to define the pulse width in conjunction with the “Type
of channel” parameter. When the Single Pulse or the Continuous Pulse option
is set, the high width and low width are configured separately. The unit is
10ms. 1 - 500 the factory def
ault is “500” for this parameter. The user
configurable parameters are:
1
– 500.
Example: If pulse width register value is written 1 count than Digital Output
signal’s pulse width is 10ms accordingly 1 x 10ms. If pulse width count is
written 2, then output signal pulse width is 20ms.