Page | 22
MINT – IO
REF NO: m25A/om/101
Issue No: 11
45014
Enable-
COM-2
0
1
0 = Disable(Default),
1= Enable
45016
IP ADDRESS
– Byte 0
0
255
Default IP Address is
192.168.100.110
45017
IP ADDRESS
– Byte 1
0
255
45018
IP ADDRESS
– Byte 2
0
255
45019
IP ADDRESS
– Byte 3
0
255
45020
Mask Address
– Byte 0
0
255
Default Mask Value is
255.255.255.0
45021
Mask Address
– Byte 1
0
255
45022
Mask Address
– Byte 2
0
255
45023
Mask Address
– Byte 3
0
255
45024
Gateway IP
Address
0
255
Default Gateway Address
is 192.168.100.254
45025
Gateway IP
Address
0
255
45026
Gateway IP
Address
0
255
45027
Gateway IP
Address
0
255
45028
Port Name
502
502
Modbus TCP Port
45029
Time-Out
Detect Value
0
65535
Modbus RTU Time-Out
Error Value
45030
Timeout(com)
0
65535
Modbus Time out value in
scale of 1ms
– (Default –
1000ms)
45031
Retry(com)
0
65535
No. of Modbus query retry
(default
– 0)
45032
Watch(com)
0
65535
Modbus Watch Time
value in scale of 1ms
–
(Default
– 10000ms)
45033
Scan
Time(com)
0
65535
Modbus Scan Time value
in scale of 1ms
– (Default
– 10000ms)
45034
Static/DHCP
0
1
0
– IP address is static,
1-IP address assign by
DHCP server. (Default
– 0
static IP) Note:Current
Model Not Support DHCP