Ref. No: m94A/OM/201
Issue No: 01
Operator’s manual
Page 18 of 26
TSPH
stands for
Temperature Set Point High. It is user input menu, user can simply
enter 2 Digit Temperature Set Point High value followed by 1 decimal point value with
the help of menu key, increment key and decrement key. If Actual Temperature goes
high above TSPH set value then it will send Temperature High alarm indication on
Zigbee to CDU/85xx+. Temperature High Alarm indication appear as symbol ‘
h
’ ahead of
temperature reading during run-mode.
(3)
HSPL
(Humidity Set Point Low) Mode:
HSPL
stands for
Humidity Set Point Low. It is user input menu, user can simply enter 2 Digit
Humidity Set Point Low value followed by 1 decimal point value with the help of menu key
,increment key& decrement key. If Actual Humidity goes low below HSPL set value then it
will send Humidity low alarm indication on Zigbee to CDU/85xx+.HumidityLow Alarm
indication appear as symbol ‘
L
’ ahead of humidity reading during run-mode.
(4)
HSPH
(Humidity Set Point High) Mode:
HSPH
stands for
Humidity Set Point High. It is user input menu, user can simply enter 2 Digit
Humidity Set Point High value followed by 1 decimal point value with the help of menu key,
increment key& decrement key. If Actual Humidity goes high above HSPH set value then it
will send Humidity high alarm indication on Zigbee to CDU/85xx+. Humidity High Alarm
indication appear as symbol ‘
h
’ ahead of humidity reading during run-mode.
(5)
DTMR
(Display Update Timer)Mode:
DTMR
is
LCD-Display update Timer mode. It is user input menu, user can simply enter 3
Digit second timer value ranging from
000
to
999
with the help of operating keys. At
defined
DTMR
interval it will measure & updates temperature & humidity values on
LCD display.
Factory default
dtmr
value is
015
seconds.
(6)
PTMR
(Push Timer)Mode:
PTMR
is for
Push timer minute. User can set the
PTMR
minute value with INC key.
Device will transmits frame at regular interval which is defined by
PTMR
value. At every
hour HT16Ew transmits one communication frame to CDU/85xx+ irrespective of
PTMR
value. User can only configured
PTMR
value from below set:
{1,5,10,15,30,60,120,180,240,360,480,720,1440,2880} this values are in minutes.
Factory default
PTMR
value is
0001
minutes.
(7)
c.pwd
(change password)Mode:
c.pwd
use to change unit password ranging from
0000
to
9999
with the help of
operating keys.
Once left most digit is set, on the press of MENU key, save Yes/ save No (
S.Y
/
S.n
)
screen will appear for saving new changed password. If user will press “
S.n
” (INC Key)
then it will discards new changes. If user will press “
S.Y
” (DCR Key) then it will set new
change password.
(8)
Min dft
Minimum Value Reset (Default) Mode:
Min dft
stands for Minimum Value Reset
mode. It is user input menu.
On the press of MENU key, save Yes/ save No(
S.Y
/
S.n
)screen will appear for saving
new changed minimum reset value. If user will press “
S.n
” (INC Key) then it will not
Содержание HT16Ew
Страница 6: ...Ref No m94A OM 201 Issue No 01 Operator s manual Page 6 of 26 6 HT16EwAPPLICATIONDIAGRAM...
Страница 10: ...Ref No m94A OM 201 Issue No 01 Operator s manual Page 10 of 26...
Страница 11: ...Ref No m94A OM 201 Issue No 01 Operator s manual Page 11 of 26...
Страница 12: ...Ref No m94A OM 201 Issue No 01 Operator s manual Page 12 of 26...
Страница 13: ...Ref No m94A OM 201 Issue No 01 Operator s manual Page 13 of 26...
Страница 14: ...Ref No m94A OM 201 Issue No 01 Operator s manual Page 14 of 26...
Страница 15: ...Ref No m94A OM 201 Issue No 01 Operator s manual Page 15 of 26...