background image

 

 

 

 
 
Doc.Ref No.:m92E/om/101 
Issue No.:09 

 

 

 

9000C

 

 

 

 

 
 
 
 
 
 
 
 
 

 
 

 
 

 
 
 
 
 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
A

PPLICATION 

E

XAMPLE

 

 

 

 
 
 
 

 

 

I

SOLATED 

C

ONVERTER 

9000C

 

S

ERIES

 

 

 

9000C  Series  are  compact  yet  rugged  4  wire  Signal 
isolators  designed  for  conditioning  and  safe  guarding 
custom-built wide range of voltage and current field signals. 
Field  Signal  is  then  isolated  and  converted  to  standard 
instrumentation  signals,  acceptable  to  commercially  off  the 
shelf (COTS) automation products. 

 

Equipped with Advanced Extended Power Supply Range of 
20V to 265V AC or DC. 

 

9000C  Series  offer  a  wide  range  of  input  /  output  signal 
types  like  mA,  VDC  which  are  Switch  Selectable  and  also 
factory settable as per user requirements. 

 

9000C  is  equipped  with  Built  in  transmitter  power  supply 
(TPS)  that  can  drive  filed  transmitters  in  case  of  4-20mA 
DC input signal.  

 

9000C  Series  isolators  act  as  signal  distributor  when  used 
with more number of outputs. 

 

9000C  Offers  excellent  accuracy  and  stability  delivering 
reliable  operation  in  hostile  environments  with  full  3  port 
isolation between input, output and power supply. 

 

9000C  Series  are  flexible  for  DIN  rail  mounting  and  easily 
installable.  Its  compact  design  consumes  less  space  and 
hence reduces cost of overall installation. 

 

9000C with HART Pass through is dedicated Signal Isolator 
with  HART  Pass  capability  and  all  enhanced  features  of 
9000C  Series  and  can  provide  an  additional  Output  of 
Current for Non HART compatible devices

.

 

 

F

EATURES

 

 

 

Slimmest  in  its  class:12.5mm  Single  output  and  17.5mm 
Dual output 

 

Extended  Universal  Power  Supply  Range:20V  to  265V  DC 
or  AC 

Capable  to  provide  Safe  and  Sufficient  Power  For 

Field Transmitter 

 

Switch Selectable  Input/output.  So user  can  change I/O as 
per their requirement. 

 

“Active Output” LED indication for Both Voltage and Current 
Outputs

 

 

Rugged & accurate 4 wire isolator

 

 

Up to 2 outputs with Short Circuit Protection

 

 

Wide zero & span adjustment limits

 

 

1.5KV AC

 Isolation between I/P, O/P and Supply

 

 

SOP & DOP

 

 

 

 

  Universal AC/ DC Aux. supply 

  Front Calibration Facility 

  Signal Isolator, dual output 

  Three port isolation 

  Excellent long term stability 

  Built in transmitter’s power 

  Compact DIN rail enclosure 

 

 

 

Содержание 9000C Series

Страница 1: ...Doc Ref No m92E om 101 Issue No 09 9000C INDEX APPLICATION EXAMPLE 1 SPECIFICATION 2 SAFETY AND WARNING 3 CONNECTION 3 INSTALLATION 4 ORDERING CODE 4 TROUBLE SHOOTING 4 ...

Страница 2: ...vironments with full 3 port isolation between input output and power supply 9000C Series are flexible for DIN rail mounting and easily installable Its compact design consumes less space and hence reduces cost of overall installation 9000C with HART Pass through is dedicated Signal Isolator with HART Pass capability and all enhanced features of 9000C Series and can provide an additional Output of C...

Страница 3: ...racy 0 1 of FS Output Load resistance For 0 4mA to 20mA 750 Ω 600 Ω for HART Pass OP1 For 0 1 to 5V 470 Ω For 0 to 10V 1 KΩ TPS Output Transmitter Power Supply 24VDC Max current Limit 26mA Electronic Power Supply Power Supply 20 to 265VDC AC 45Hz 65Hz Power Consumption 5VA CMRR 100dB NMRR 70dB Isolation Isolation Power to Input Output Input to Output Output to Output 1 5KV AC for 1 minute Environm...

Страница 4: ...icient fuse protection and are of correct size All output cables are of correct size for the maximum device output current or have separate fuse protection Sufficient convection is ensured After installation the terminal area must be covered to provide sufficient protection against unauthorized Access to live parts This is ensured by installing the device in the control Cabinet or distributor box ...

Страница 5: ...fore attempting any re calibration Unstable Reading Check for loose connections First verify that all conventional instrumentation norms have been followed for wiring Make noise away from signal isolator Fluctuation in Reading The reason can be reverse input connections Ordering Code Model Input Type No of O P O P Type 9000C S X X X C 4 20mA 1 One 1 4 20mA 2 Two Model Input Type No of O P O P Type...