Doc.Ref No.:m92E/om/101 
Issue No.:09 

 

 

 

9000C

 

 

 

Dimensions 

 

9000C

 

STANDARD

 

SOP 

 

 

 

9000C

 

STANDARD

 

DOP 

 

 

 

9000C

 

SOP/DOP

 

HART

 

PASS 

 

 

 

 

All dimensions are in mm. 

 

S

PECIFICATION

 

 

Input 

 

Input Type 

Voltage/ Current 

Input Range 

 

‘S’ Model - 4-20mA Standard  

 

‘M’ Model – For Voltage: Min: 0 to 
±100mV,Max:0 to ±10VDC.  
For Current:Min:0 to ±1mA, Max:0 to 
±10mA/+20mA 

 

‘H’ Model – 4-20mA, HART Pass  

Input Impedance 

Current I/P 

10 

; Voltage I/P 

1 M

 

Output 

 

Output  Type 

Voltage/Current 

Output  Range 

 

‘S’ Model - 4-20mA Standard  

 

‘M’ Model – For Voltage:Min:0 to 
±100mV,Max:0 to ±10VDC  
For  Current:Min:0 to ±1mA, 
Max:0 to ±10mA/+20mA  

 

‘H’ Model – 4-20mA HART Pass on OP1, 
 4-20mA Standard on OP2 

Response Time 

50 ms 

Accuracy

 

± 0.1% of FS  

Output Load resistance 

For 0/4mA  to 20mA : 

 750 

 (

 600 

 for  

HART Pass OP1) 
For 0/1 to ±5V: 

 470 

 

For 0 to ±10V: 

 1 K

Ω

 

TPS Output 

Transmitter Power Supply 24VDC 
Max current Limit: 26mA Electronic 

Power Supply 

 

Power Supply 

20 to 265VDC/AC, 45Hz-65Hz  

Power Consumption 

5VA 

CMRR 

>100dB 

NMRR 

>70dB 

Isolation 

 

Isolation 

Power to Input / Output, Input to Output, 
Output to Output– 1.5KV AC for 1 minute 

Environmenta

 

Operating temperature 

0 to 55ºC 

Temp. Co-efficient 

100 PPM 

Relative humidity  

30 to 95% RH (Non-Condensing) 

Protection

 

Conformal Coating on PCB 

Physical 

 

Mounting Type 

DIN RAIL (35 mm) Mounting 

Dimensions

 

12.5(W)x99.7(H)x114.7(D) mm(for SOP) 
17.5(W)x99.7(H)x114.7(D) mm(for DOP and 
HART Pass) 

Weight

 

100 gms Approx. For SOP model 
130 gms Approx. For DOP model  

Enclosure Material 

PA66 

Terminal Detail 

 

Terminal type and cable 
size 

Screw type, 2.5mm

2

 

 

 

Содержание 9000C Series

Страница 1: ...Doc Ref No m92E om 101 Issue No 09 9000C INDEX APPLICATION EXAMPLE 1 SPECIFICATION 2 SAFETY AND WARNING 3 CONNECTION 3 INSTALLATION 4 ORDERING CODE 4 TROUBLE SHOOTING 4 ...

Страница 2: ...vironments with full 3 port isolation between input output and power supply 9000C Series are flexible for DIN rail mounting and easily installable Its compact design consumes less space and hence reduces cost of overall installation 9000C with HART Pass through is dedicated Signal Isolator with HART Pass capability and all enhanced features of 9000C Series and can provide an additional Output of C...

Страница 3: ...racy 0 1 of FS Output Load resistance For 0 4mA to 20mA 750 Ω 600 Ω for HART Pass OP1 For 0 1 to 5V 470 Ω For 0 to 10V 1 KΩ TPS Output Transmitter Power Supply 24VDC Max current Limit 26mA Electronic Power Supply Power Supply 20 to 265VDC AC 45Hz 65Hz Power Consumption 5VA CMRR 100dB NMRR 70dB Isolation Isolation Power to Input Output Input to Output Output to Output 1 5KV AC for 1 minute Environm...

Страница 4: ...icient fuse protection and are of correct size All output cables are of correct size for the maximum device output current or have separate fuse protection Sufficient convection is ensured After installation the terminal area must be covered to provide sufficient protection against unauthorized Access to live parts This is ensured by installing the device in the control Cabinet or distributor box ...

Страница 5: ...fore attempting any re calibration Unstable Reading Check for loose connections First verify that all conventional instrumentation norms have been followed for wiring Make noise away from signal isolator Fluctuation in Reading The reason can be reverse input connections Ordering Code Model Input Type No of O P O P Type 9000C S X X X C 4 20mA 1 One 1 4 20mA 2 Two Model Input Type No of O P O P Type...

Отзывы: